Eaton Moeller MSC-DE DOL启动器(121744)产品说明书
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
Eaton 121744
Eaton Moeller® series MSC-DE DOL starter, 380 V 400 V 415 V:
5.5 kW, Iq= 100 kA, Ir= 3 - 12 A, 24 V DC, DC voltage
Spécifications générales
Eaton Moeller® series MSC-DE DOL
starter
121744
4015081195541
102 mm198 mm
45 mm0.78 kg
VDE 0660
IEC/EN 60947-4-1MSC-DE-12-M12(24VDC)
Product Name Catalog Number
EAN
Product Length/Depth Product Height Product Width Product Weight Certifications Model Code
Short-circuit release
Temperature compensated overload protection Adjustable
Screw terminals
No
1
500 (Class 5) AC-4 cycle operation, Main conducting paths 900 (Class 15) AC-4 cycle operation, Main conducting paths For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
700 (Class 10) AC-4 cycle operation, Main conducting paths Note: Going below the minimum current flow time can cause overheating of the load (motor).
1000 (Class 20) AC-4 cycle operation, Main conducting paths
≤ 500 ms, main conducting paths, AC-4 cycle operation
IP20
NEMA Other
Direct starter
DIN rail
1
3 A
12 A
Fitted with: Functions Class
Connection
Connection to SmartWire-DT
Coordination type
Current flow times - min
Cut-out periods - min
Degree of protection
Model
Mounting method
Number of auxiliary contacts (normally closed contacts) Number of auxiliary contacts (normally open contacts) Overload release current setting - min
Overload release current setting - max
Overvoltage category
III 3
6000 V AC
Also motors with efficiency class IE3 Starter with electronic trip unit
DC Max. 2000 m -25 °C
55 °C
11.3 A
12 A
3 kW
5.5 kW
230 - 415 V AC
45 A, Class J, max. Fuse, SCCR (UL/CSA) 100 kA, Fuse, SCCR (UL/CSA)
186 A 2.6 W 0 V
0 V
0 V
0 V 24 V 24 V
Pollution degree
Rated impulse withstand voltage (Uimp) Suitable for
Type
Voltage type Altitude
Ambient operating temperature - min
Ambient operating temperature - max
Rated operational current (Ie)
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V Rated operational power at AC-3, 220/230 V, 50 Hz
Rated operational power at AC-3, 380/400 V, 50 Hz
Rated operational voltage
Short-circuit current rating (high fault at 600 V) Short-circuit release (Irm) - max Power consumption (sealing) at DC
Rated control supply voltage (Us) at AC, 50 Hz - min Rated control supply voltage (Us) at AC, 50 Hz - max Rated control supply voltage (Us) at AC, 60 Hz - min Rated control supply voltage (Us) at AC, 60 Hz - max Rated control supply voltage (Us) at DC - min
Rated control supply voltage (Us) at DC - max
Equipment heat dissipation, current-dependent Pvid
4.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.5 W
Rated operational current for specified heat dissipation (In)
12 A
Static heat dissipation, non-current-dependent Pvs
2.6 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be
Eaton Corporation plc Eaton House
30 Pembroke Road Dublin 4, Ireland
© 2023 Eaton. Tous droits réservés.
Eaton is a registered trademark.
All other trademarks are property of their respective
owners.
/socialmedia
evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Is the panel builder's responsibility.Is the panel builder's responsibility.Is the panel builder's responsibility.Is the panel builder's responsibility.
Is the panel builder's responsibility.The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Is the panel builder's responsibility. The specifications for the switchgear must be observed.Is the panel builder's responsibility. The specifications for the switchgear must be observed.The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.6 Incorporation of switching devices and components 10.7 Internal electrical circuits and connections 10.8 Connections for external conductors 10.9.2 Power-frequency electric strength 10.9.3 Impulse withstand voltage 10.9.4 Testing of enclosures made of insulating material 10.10 Temperature rise
10.11 Short-circuit rating
10.12 Electromagnetic compatibility
10.13 Mechanical function。