U P S空开线缆对应表 GE GROUP system office room 【GEIHUA16H-GEIHUA GEIHUA8Q8-UPS空开、线缆、对应表一、UPS空开、电缆配置1、高频UPS1-1、输入、输出、电池电流计算方法1-1-1、输入电流计算方法UPS标称功率(VA)×输出功率因数输入电流(A)=输入临界电压(V)×整机效率×输入功率因数×SS:三相UPS=3,单相UPS=1例1:已知: UPS功率:100KVA,输入临界电压:176V,输入功率因数:0.99(高频机都可以近似取1),整机效率:0.95,S=3,输出功率因数:0.8计算结果如下:100000×0.8输入电流(A)= =160176×0.95×3例2:已知: UPS功率:6KVA,输入临界电压:176V,输入功率因数:0.99(高频机都可以近似取1),整机效率:0.90,S=1,输出功率因数:0.7计算结果如下:6000×0.8输入电流(A)= =30176×0.9×11-1-2、输出电流计算方法UPS标称功率输出电流(A)=输出电压×SS:三相UPS=3,单相UPS=1例1:已知: UPS功率:100KVA,输出电压:220V,S=3。
计算结果如下:100000输出电流(A)= =152220×3例2:已知: UPS功率:6KVA,输出电压:220V,S=1计算结果如下:6000输出电流(A)= =27220×11-1-3、电池逆变电流计算方法UPS标称功率(VA)×输出功率因数电池逆变电流(A)=电池临界电压(V)×逆变效率例1:已知: UPS功率:100KVA,输出功率因数:0.8,电池临界电压:420V,逆变效率:0.95计算结果如下:100000×0.8电池逆变电流(A)= = 200420×0.951-1-4、电缆大小计算方法交流电流一般按3-5A计算,直流电流一般按2-4A计算;例1: 100KVA 输入电流:160A,输出电流:152A,电池电流200A。
艾登5SC UPS产品说明书

Eaton 5SC1500IEaton 5SC UPS, 1500 VA, 1050 W, Input: C14, Outputs: (8) C13,TowerGeneral specificationsEaton 5SC UPS5SC1500I743172045171150 mm210 mm410 mm15.2 kg 2 yearCE Marked TUV IEC/EN 62040-1 UL 1778IEC/EN 62040-2 CEEACcTUVusProduct Name Catalog Number UPC Product Length/Depth Product Height Product Width Product Weight Warranty Compliances Certifications60 HzSine wave1050 W0.7TowerBlackNoC14184 V240 V50 HzEaton Intelligent Power ProtectorUser replaceableLead-acid maintenance-free (replaceable) 97Eaton UPS and battery servicesEaton 5SC UPS - 500/3000VA - DatasheetEaton UPS Services Quick Guide 2021EU DoC Eaton 5SCEaton 5SC UPS - 500i/750i/1000i/1500i - Installation and user manual (multiple languages)Secondary frequency - max Output waveformWattageOutput power factorForm factorEnclosureIncludes network card Input connectionInput voltage - minOutput voltage - max Secondary frequency - min Software compatibility Battery replacement Battery typeEfficiencySpecial features BrochuresCompliance information Manuals and user guidesAutomatic Voltage Regulation (AVR) Delivers clean sinewave outputLCD display for real-timestatus and measurementsReliable and affordable UPSfor tower servers,networking and storageSaves space with a compacttower designFully integrates with EatonIntelligent Power Managersoftware1 USB port + 1 serial port1 USB port + 1 serial portAdvanced BatteryManagement (ABM)technology to increasebattery lifetimeConstruction typeFree standing modelOutput voltage - min220 VColorBlackExtended battery capabilityNoOutput voltage range230 V (+6%/-10%)TopologyLine-interactiveBTU RatingOnline: 211Runtime at half load13 minInput nominal voltage230V default (220/230/240V)Input frequency range45-55 Hz (50 Hz system), 55-65 Hz (60 Hz system)Input voltage - max276 VVoltage typeACBattery managementABM or constant voltage charging method (user selectable), automatic battery test, deep discharge protectionAuto shutdown functionYesNumber of Outputs C138VA rating1500 VAPotential free switch contactNoReceptacle(8) C13Phase (input)1Package contentsUSB cableSerial cable(2) IEC-IEC cablesQuickstart guideSafety instructionsNoise level<40 dB at 1 meterFeed type1Runtime graphView runtime graphUser interfaceLCD DisplayBattery quantity3Voltage230VTemperature range0-90% non-condensingCommunicationUSB port (HID compliant) Serial port (RS232)Relative humidity0-90% non-condensingRack mounting kitNoOutput frequency50/60 HzRuntime at full load5 minType of interfaceOtherPrimary frequency - min45 HzBattery rating12 V / 9 AhTypeUPSOutput nominal voltage230V default (220/230/240V)Expansion slotsNoInput voltage range184-276 VNominal frequency50-60 HzPrimary frequency - max65 HzAltitude2000 mEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. All rights reserved. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmedia。
UPS说明书

U P S 不断电电源供给器智能在线网络保护不断电系统3KVA/6KVA/10KVA/12KVA/15KVA/20KVA/30KVA■产品使用手册■1. 导论------------------------------------------------------------------------------------------------22. 重要安全指示-----------------------------------------------------------------------------------23. UPS介绍------------------------------------------------------------------------------------------34. 产品介绍------------------------------------------------------------------------------------------55. 安装------------------------------------------------------------------------------------------------66. 操作说明-----------------------------------------------------------------------------------------87. 监控软件选配及计算机接口端口--------------------------------------------------------98. 保养及保存方法------------------------------------------------------------------------------109. 异常状况排除---------------------------------------------------------------------------------1110. 附录A 规格---------------------------------------------------------------------------------15在线式不断电系统电源供应器(UPS)提供一个连续且稳定的电源给需要保护的设备使用,使您的设备免于遭受下列电源的困扰。
科瑞爱特 CT55500KVVA 系列三相工频电力专用 UPS 电源 使用手册说明书

科瑞爱特CreateU s e r M a n u a lC T50K V A系列三相工频电力专用U P S电源声明本资料著作权属科瑞爱特科技开发有限公司所有。
未经著作权人书面许可,任何单位或个人不得以任何方式摘录、复制或翻译。
侵权必究。
是科瑞爱特科技开发有限公司的注册商标。
科瑞爱特产品的名称和标志是科瑞爱特的专有标志或注册商标。
在未经科瑞爱特或第三方商标或商名所有者事先书面同意的情况下,本手册不以任何方式授予阅读者任何使用本手册上出现的任何标记的许可或权利。
本产品符合关于环境保护和人身安全方面的设计要求,产品的存放、使用和弃置应遵照产品手册、相关合同或相关国家法律、法规的要求进行。
由于产品和技术的不断更新、完善,本资料中的内容可能与实际产品不完全相符,敬请谅解。
如需查询产品的更新情况,请联系那个地办事处。
若需了解最新的资料信息,请访问网站:感谢您选择三相工频电力专用UPS电源!尊敬的用户:首先感谢您选用我们的产品,从现在开始我们将成为朋友!我们非常高兴向您提供这一系列电源产品,希望它在未来的岁月里为您提供方便、可靠的服务,保证您的设备安全运作。
为了您的安全和更好的使用该系列电源,请您在安装使用前务必仔细阅读此使用手册!如果您对本手册的内容有疑问或不明确之处,请您在使用逆变电源产品前与我们联系。
警告:不要拆卸电力U P S电源上的任何外壳或器件。
设备内部零件带有致命性的电压或存有高能量的危险!目录第一章 序言 (5)1.1 注意事项 (5)1.2 开箱检查 (6)1.3 储存环境 (6)1.4 搬运 (6)第二章 产品简介 (7)2.1 产品外观 (7)2.2 工作原理 (9)2.3 主要技术参数 (10)2.4 保护功能 (11)2.5 工作环境 (11)第三章 安装运行 (12)3.1 安装准备 (12)3.2 安装位置 (12)3.3 安装接线 (12)3.4 前面板操作和显示示意图及说明 (13)3.5 UPS电源试运行 (14)3.6 UPS电源的正常启动、关闭操作步骤 (15)第四章 显示异常信息和报警信号 (15)4.1 常见故障的原因及处理方法 (15)第五章 维护保养和售后服务 (16)5.1 维护保养 (16)5.2 售后服务 (16)第一章 序言三相工频电力专用UPS电源是为了电力保障,专为电力、通信系统设计,是一种将市电及电池的电能转化为净化的交流电能的变换装置,用以给计算机和其他电气设备提供可使用的连续交流电源,以备市电的不稳定及断电。
UPS执行价(大正恒业)

主机(柜) PXP1040-400/220-EN DIW1040-380/220 PIW1040 A30 12FIT90 / A812 输出配电柜
主机(柜) PXP1050-400/220-EN DIW1050-380/220 PIW1050 A30 12FIT130 / A812 输出配电柜
主机(柜) PXP1060-400/220-EN DIW1060-380/220 PIW1060 A30 12FIT150 / A812 输出配电柜
(Ah)
10小时放电 容量 C10 1.80V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
非凡 进口品牌原装进口 FIT 非凡 进口品牌原装进口 FIT 非凡 进口品牌原装进口 FIT 非凡 进口品牌原装进口 FIT 非凡 进口品牌原装进口 FIT 非凡
进口品牌原装进口 FIT
主机(柜) PXP3015-400/380-EN DIW3015-380/380 / A30 12FIT40 / A812 输出配电柜
主机(柜) PXP3020-400/380-EN DIW3020-380/380 / A31 12FIT40 / A812 输出配电柜
主机(柜) PXP3030-400/380-EN DIW3030-380/380 / A31 12FIT60 / A812 输出配电柜
31--40 51--60 71--80 91--100 121-130 141--150 171--180 20--30 41-50 51--60 61--70 91--100 111--120 141--150 191--200
非凡 进口品牌原装进口 FIT 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP 非凡 进口品牌国内生产 SP
艾默生Hipulse U系列160~400kVA UPS用户手册

该警告标识代表所有人身安全指示。
目录
第一章 概述 ........................................................................................................................................................................ 1
1.1 特点.........................................................................................................................................................................................1 1.2 设计思想.................................................................................................................................................................................1
设备的安装应遵照以上要求并使用厂家指定附件。
警告
大对地漏电流:在接入输入电源前(包括交流市电和电池),请务必可靠接地。 设备的接地必须符合当地电气规程。
UPS 系统前级配电保护设备的选择必须符合当地电气规程。
UPS相关的计算及配置

目录一、空开的选择与配置 (2)空开的类型: (2)输入工作电流: (2)输出工作电流: (2)空开的选择: (3)二、常用电缆的配置选择 (3)UPS常用电缆类型和规格 (3)电缆常用的截面积: (3)电缆的选择:4---3---2---1.5 (3)三、UPS的容量计算与选择 (5)经济型算法: (5)扩容型算法: (5)四、UPS的电池计算与选择 (6)恒功率模式计算公式 (6)一、空开的选择与配置空开的类型:工作电流的计算方法:输入工作电流:开关容量=2*UPS容量或 =2.5*UPS容量2为工频机----开关容量输入电流的速算系数,2.5为高频机---开关容量输入电流的速算系数例:120KVA的UPS的输入工作电流是:2*120=240A ,所以选250A的空开特例: UL33输入电压范围宽,需考虑满载最低工作电压(额定电源的75%):60KVA的ups输入开关=(60*2)/0.75=160A,所以选160A的空开输出工作电流:开关容量=1.5*UPS容量1.5为----开关容量输入工作电流速算系数例:400KVA的UPS的输出工作电流是:1.5*400=600A,所以选630A的空开空开的选择:开关大小:由大-----小的原则,开关数量:UPS输入2个/ UPS输出1个UPS用的基本都是3P开关,用4P开关的情况如下:外置维修旁路或有ATS系统图:Visio 软件平面摆放:CAD二、常用电缆的配置选择UPS常用电缆类型和规格电缆常用的截面积:10/16/25/35/50/70/95/120/150/185/240/300/400/500/630电缆的选择:4---3---2---1.5输入空开及电缆:输入电流:2*120=240A,输入空开选:250A,电缆选240/2=120方输出空开及电缆:输出电流:1.5*120=180A,输出空开选:180A,电缆选180/2≈95方例:APM 90KVA输入空开及电缆:输入电流:2*90=180A,输入空开选:200A,电缆选180/3≈70方输出空开及电缆:输出电流:1.5*90=135A,输出空开选:160A,电缆选135/3≈50方三、UPS的容量计算与选择经济型算法:因为用户的负载清单中,每一设备的容量均为最大幅值容量,所以UPS的容量按照最大容量取整即可UPS容量=最大的负载容量(容量取整)扩容型算法:UPS容量=负载容量 * 1.3(容量取整),负载在UPS的60-80%例:若机房各设备总负载的371000W,如下表:经济型算法:UPS的容量为=371000w=371 kw ≈ 400 kva(容量取整)扩容型算法:UPS的容量为=371000w * 1.3 =482.3 KW≈500 kva(容量取整)四、UPS的电池计算与选择恒功率模式计算公式W/cell =P L/N*6*ŋW/cell----每个电池各上的功率 WP L--------负载功率 W(用ups容量计算时需考虑ups功率因素)C---------蓄电池容量 AHVe-------蓄电池组上的额定电压 VT---------备用时间Hŋ---------UPS的电池逆变效率N= Ve/12, 6是指12V电池内部有6个2V单元格,6V为3,2V为1 注意:1、N可以调节 Ve相同,不任是2V/6V/12V,注意W/cell与W/block 例:NXr 160kva, ŋ=0.94, n=30节,满载时后备15分钟什么配置电池W/cell =P L/N*6*ŋ=(160*1000*0.9)/(30*6*0.94)=851w/cell。
UPS说明书技术参数

不间断电源u n i n t e r r u p t i b l e p o w e rs u p p l yU P S(6···250)K V A产品使用说明书目录1.产品介绍---------------------------------------------2 2.操作要求---------------------------------------------2 3.注意事项---------------------------------------------2 4.工作原理---------------------------------------------3 5.前板介绍---------------------------------------------7 6.安装---------------------------------------------------87. 主要技术指标---------------------------------------118. 告警说明---------------------------------------------159. UPS启动程序-------------------------------------17 10.UPS维修关机程序------------------------------17 11. 紧急关机程序--------------------------------------17 12.前显示板说明-------------------------------------18 13.并机系统启动操作步骤-------------------------21 14.并机系统关机步骤---------- --------------------2215. 并机系统紧急关机步骤--------------------------2216. 附页—开机注意事项----------------------------- 241.产品介绍三三系列三进三出全数字化UPS,是采用先进的微电子、电力电子、数字控制技术,集数字化、信息化、网络化为一体的高智能型产品,具有强大的信息采集系统、信号处理系统、监测系统和完善的保护系统。
160KVA UPS

1.8.1160KVA UPS1)技术性能:机房系统IT设备采用UPS 供电,配电容量为160kVA,三相输入,三相输出,后备时间30分钟。
在失电情况下,UPS 提供后备电源,并进行必要的隔离和滤波,防止外部电压波动对设备运行的干扰。
UPS电源装置的主要技术性能指标应满足以下要求:Ø可根据负载大小自动调节放电,延长电池寿命。
Ø在线式双变换技术。
采用双转换技术的UPS始终再生一个洁净的电压输出,完全隔离主交流电源的扰动,UPS必须采用整流器和谐波滤波器。
Ø应采用智能化控制系统进行控制信息处理,对蓄电池进行有效地管理。
Ø具备易看和易操作的大屏幕图形化液晶显示屏,借助于人-机对话型的菜单操作随机记录UPS运行状态,提供可靠的原始数据,便于分析故障原因。
同时具备标准内置SNMP网络适配器、标准内置RS232接口、环境输入节点(监控烟雾、湿度、温度等)、继电器干接点、EPO接口。
要求UPS设备和后台监控都必须为中文界面。
Ø UPS内置输出隔离变压器,保证UPS输出侧与市电的完全隔离。
UPS输出隔离变压器必须采用H级的Z-Z绕组的隔离变压器以抵消负载谐波电流的干扰,实现带100%三相不平衡负载的功能。
Ø逆变器侧和旁路侧必须使用能够带满负载工作的SCR静态旁路开关,不得使用交流接触器加小容量的SCR来实现旁路功能。
Ø应设置静态旁路,静态旁路开关须自动地把UPS负载无间断地切换到逆变器电源或旁路供电电源。
UPS电源装置须可以承受静态旁路开关无间断地与旁路电源并联时产生的瞬间能量或故障能量。
Ø内置手动维修旁路,保证实现不停电维护,使负载与UPS电源系统隔离。
Ø为满足将来发展需求,UPS可在线扩容。
Ø标配有“三位”电池保护开关。
Ø投标方需提供UPS设备的具体发热量指标。
2)基本参数:Ø输入电压: 380V+10%(可调);380V-15%(可调);Ø输入频率: 50Hz±5%(可调);Ø频率跟踪率≤4Hz/s(可调);Ø输入功率因数:≥0.85,具有功率因数补偿功能;Ø输入电流谐波成分≤25%(3~39次THDi);Ø输出电压:三相(380V)五线制交流电源Ø输出电压稳压精度:±1%Ø输出电压不平衡:≤3%Ø输出频率:50 Hz±0.1 Hz(电池逆变工作)Ø输出波形失真度:≤3%Ø市电电池切换时间:0msØ旁路逆变切换时间:<1 ms(逆变器故障时)Ø瞬变响应恢复时间:≤20 ms(电池逆变工作)Ø整机效率:≥92%Ø输出功率因数≥0.8Ø UPS: 应带有内置输出隔离变压器;Ø防雷要求:具备机房工程防雷性能,满足信息产业部D级防雷标准Ø过载能力:在正常工作方式下,UPS过载125%工作时间不小于10分钟,静态开关过载120%工作时间不少于3分钟Ø并机能力:支持4台以上并机运行。
艾森5SC UPS 产品说明说明书

Eaton 5SC1000IEaton 5SC UPS, 1000 VA, 700 W, Input: C14, Outputs: (8) C13,TowerGeneral specificationsEaton 5SC UPS5SC1000I150 mm210 mm340 mm11.1 kg2 year CE MarkedTUVIEC/EN 62040-1 UL 1778IEC/EN 62040-2 CEEACcTUVus Eaton 5SC 1000iProduct Name Catalog Number Product Length/Depth Product Height Product Width Product Weight Warranty Compliances Certifications Model CodeLead-acid maintenance-free (replaceable)View runtime graphUser replaceable2ABM or constant voltage charging method (user selectable), automatic battery test, deep discharge protection12 V / 9 AhNo (8) C13230V700 W0.7230 V (+6%/-10%)Sine wave230V default (220/230/240V) 1Line-interactive1000 VAC14230V default (220/230/240V)50-60 Hz184-276 V45-55 Hz (50 Hz system), 55-65 Hz (60 Hz system)NoNoLCD Display NoBattery typeRuntime graphBattery replacement Battery quantityBattery management Battery ratingExtended battery capability ReceptacleVoltageWattageOutput power factor Output voltage range Output waveform Output nominal voltage Feed typeTopologyVA ratingInput connection Input nominal voltage Nominal frequency Input voltage range Input frequency range Includes network card CommunicationEthernet interfaceUser interfacePotential free switch contact Expansion slotsUSB port (HID compliant) Serial port (RS232)NoEaton Intelligent Power ProtectorOther2000 m<40 dB at 1 meter0-90% non-condensing0-90% non-condensingFree standing model Black1YesBlack96No1Eaton 5SC UPS - 500i/750i/1000i/1500i - Installation and user manual (multiple languages)EU DoC Eaton 5SCSoftware compatibilityType of interfaceAltitudeNoise levelTemperature rangeRelative humidityConstruction type EnclosurePackage contentsPhase (output)Auto shutdown function ColorEfficiencyRack mounting kit Phase (input)Brugervejledninger Compliance informationUSB cableSerial cable(2) IEC-IEC cables Quickstart guide Safety instructionsEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. Alle rettigheder forbeholdes. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmedia。
美国Eaton 5P UPS系列产品的说明书

Eaton 5P850IREaton 5P UPS, 850 VA, 600 W, Input: C14, Outputs: (4) C13,Rack, 1UGeneral specificationsEaton 5P UPS5P850IR743172042910438 mm43.2 mm509 mm13.8 kg 3 year on electronics, 2 year on batteryCE Marked TUV IEC/EN 62040-1 UL 1778IEC/EN 62040-2 CEEACcTUVusProduct Name Catalog Number UPC Product Length/Depth Product Height Product Width Product Weight Warranty Compliances Certifications60 HzSine wave600 W0.7RackBlack/silverNoC14150 V240 V50 HzEaton Intelligent Power Manager, Eaton Intelligent Power ProtectorUser replaceableLead-acid maintenance-free (replaceable)97Eaton UPS and battery servicesEaton UPS Services Quick Guide 2021Eaton 5P UPS Quick Start GuideEaton 5P UPS - Installation and user manual Eaton 5P UPS DatasheetSecondary frequency - max Output waveformWattageOutput power factorForm factorEnclosureIncludes network card Input connectionInput voltage - minOutput voltage - max Secondary frequency - min Software compatibility Battery replacement Battery typeEfficiencySpecial features BrochuresManuals and user guides Technical data sheetsAutomatic Voltage Regulation (AVR)High-density protection fornetworks: 1U onlyEnergy efficient, reduce energy and cooling costs Delivers clean sinewave output1 slot for optional com card (Network management card, Relay card or Network and Industrial card)Compatible with Virtual environments (VMware, Hyper-V, Citrix Xen, Redhat) Fully integrates with Eaton Intelligent Power Manager software1 USB port + 1 serial port Advanced Battery Management (ABM) technology to increase battery lifetimeNext-generation graphical LCD displayHot swappable batteries Remote reboot and runtime optimization thanks to 2 manageable outlet groupsConstruction type482.6 mm (19 inch) deviceOutput voltage - min200 VColorBlack/silverExtended battery capabilityNoOutput voltage range230 V (+6%/-10%)TopologyLine-interactiveBTU RatingOnline: 123Runtime at half load12 minInput nominal voltage230V default (200/208/220/230/240V)Input frequency range47-70 Hz (50 Hz system), 56.5-70 Hz (60 Hz system), 40 Hz in low sensitivity modeInput voltage - max294 VVoltage typeACPhase (output)1Battery managementABM or constant voltage charging method (user selectable), automatic battery test, deep discharge protectionAuto shutdown functionYesNumber of Outputs C134VA rating850 VAPotential free switch contactYesReceptacle(4) C13Phase (input)1Package contentsRack-mounting kitCable locking systemUSB cableSerial cable(2) IEC-IEC cablesQuickstart guideSafety instructionsNoise level<40 dB at 1 meterFeed type1Runtime graphView runtime graphUser interfaceMultilingual graphical LCD displayBattery quantity2Rack size1UVoltage230VTemperature range0-90% non-condensingEthernet interfaceNoCommunicationUSB port (HID compliant) Serial port (RS232)Mini-terminal block forremote On/Off and Remote Power OffDry contacts (2 outputs, optocoupler, RJ)Relative humidity0-90% non-condensingRack mounting kitYesOutput frequency50/60 HzRuntime at full load4 minType of interfaceOtherPrimary frequency - min47 HzBattery rating12 V / 7 AhTypeUPSEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. All rights reserved. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmedia230V default (200/208/220/230/240V)One slot for optional communication card 160-294 V (adjustable to 150 V-294 V)50-60 Hz70 Hz 2000 mOutput nominal voltageExpansion slotsInput voltage rangeNominal frequency Primary frequency - max Altitude。
Eaton 9395 UPS (225-300 kVA) Single-Feed Kit 安装说明说

Eaton 9395 UPS®225–300 kVASingle-Feed Kit Installation InstructionsEaton 9395 UPS (225–300 kVA) Single Feed Kit S 164201722 Rev 2 /powerquality1Eaton 9395 UPS (225–300 kVA) Single-Feed Kit InstallationNOTE Refer to the applicable installation and operation manual supplied with the UPS during installation.Installation should be performed only by qualified personnel.To install the single-feed kit:1.If not already accomplished, remove one top screw and two bottom screwssecuring the UPS left front panel (refer to the applicable Eaton 9395 UPS manual for panel location). Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.2.If not already accomplished,remove the screws securing the internal safetyshield panel and remove the panel to gain access to the rectifier and bypass input terminals. Retain the hardware for later use.3.Using hardware from the single-feed kit (see Table 1), install the single-feed jumper cables from the kit between the rectifier input terminals and the input bypass input terminals (see Figure 1). Tighten the bolts to the torque values listed in Table 2.4.Return to the applicable Eaton 9395 UPS manual to complete the wiring.Table 1. Supplied Terminal HardwarePart Size Quantity Terminals Used On Eaton Part Number Jumper Cable N/A6Rectifier and Bypass Input 152602507(wire kit with 6 cables)Bolt, Grade 5M12 45 mm6Rectifier and Bypass Input 180190078-113Flat Washer M1212Rectifier and Bypass Input 180500036-120Conical Washer M126Rectifier and Bypass Input 180500037-120NutM126Rectifier and Bypass Input180200001-07Table 2. Single-Feed Power Cable TerminationsTerminal FunctionTerminal Function Bus Landing Tightening TorqueNm (lb ft)Bolt Size Rectifier InputE1Phase A 1 – 1 bolt mounting 76 (56)M12E2Phase B 1 – 1 bolt mounting 76 (56)M12E3Phase C 1 – 1 bolt mounting 76 (56)M12Bypass InputE6Phase A 1 – 1 bolt mounting 76 (56)M12E7Phase B 1 – 1 bolt mounting 76 (56)M12E8Phase C1 – 1 bolt mounting76 (56)M12EATON 9395 UPS (225–300 KVA) SINGLE-FEED KIT INSTALLATIONEaton 9395 UPS (225–300 kVA) Single Feed Kit S 164201722 Rev 2 /powerquality 2Single Feed JumpersFigure 1. Eaton 9395 UPS (225–300 kVA) Single Feed Kit*1642017222*164201722 2。
艾特顿93PM UPS 30-500 kVA 产品说明书

Product brochure Eaton 93PM UPS 30-500 kVAEaton93PMUPSThe performance of Eaton 93PM UPS is proven with installations totaling no less than 500 MVA installed capacity globally. It provides the highest availabilityfor mission critical applications at the lowest TotalCost of Ownership.Eaton 93PM UPS LOWEST TOTAL COST OF OWNERSHIP HIGHEST AVAILABILITY EASE OF MANAGEMENT30-500kVA Can be paralleled up to 2 MVA P O W E R R A T I N GEASE OF DEPLOYMENT60YEARSThe site hostsUPS capacity range30 – 60 kVANumber of power modules1Maximum system size8 UPS in parallelInternal batteries11 to 30 min full load runtime30 – 250 kVA1 (4)8 UPS in parallelUPS capacity range100 – 500 kVANumber of power modules 2 (8)Maximum system size 4 UPS in parallelAll-round valueOur goal is to deliverthe highest availability formission critical applicationsat the Lowest Total Costof Ownership for cost-efficient businesscontinuity.LOWER TCO HIGHER AVAILABILITY S a fe t y Ef fic i e nc y R e s i l i e n c y S c a l a b i l i t yEfficiencyWith market leading efficiency being translated into reduced electrical and cooling losses, the 93PM helps to minimize operational expenditure. Reduced power losses also lead to higher sustainability, through reduced carbon emissions.ResiliencyThe ability of a system toabsorb faults and still remain inits desired operational state isparamount to minimizing costlydowntime. The 93PM includesa number of features to ensurethe highest possible resiliencyfor mission critical applications.SafetyEaton 93PM makes electricalinstallation safety easy forthe end users, planners andcontractors – required safetyequipment come integrated andinbuilt. Did you know that eachUPS installation is required tobe equipped with a backfeedisolation contactor and shortcircuit protective devices?With Eaton UPS, we havepre-designed, pre-tested andpre-installed these equipmentwithin the UPS.ScalabilityScalability helps to optimizecapital expenditure by enablingthe pay-as-you-grow approach.The UPS capacity can beincreased at any time, simplyby adding power modules to theexisting UPS or by adding a newUPS in parallel to the existinginstallation.SAFETYFIRST=157x320020000400006000080000100000120000140000123 45678910160000180000025%75%VMMS ESS96.7%900000 kVA 74% Less Losses Static Switch Inverter ECT TESTING OF SAVING OF 1 UPS PURCHASE PRICE=AC BYPASS SOURCE FUSE STATIC BYPASS SWITCH BACKFEED CONTACTORUNINTERRUPTIBLE POWER MODULES AC SOURCE LOADS T A T I CB Y P A S SFlexibility and availabilityModular structure can ensure the simplest possible configuration tomeet site-specific UPS power and redundancy requirements flexibly.The Uninterruptible Power Modules are able to operate independently,introducing inherent redundancy and maximizing availability of thecritical load.Scalability Eaton 93PM UPS provides several options for scaling and tailoring theoptimal fit for your application. UPS power scaling can be achieved byadding a new UPS in parallel to the existing installation or by increasingthe UPS capacity. Eaton modular UPS support scalability of capacityany time, simply by adding a new power module to the existing UPS.Scalable UPS design that does not compromise selectivity The UPS bypass capacity needs to match the site requirements for selectivity from day one – even in scalable designs. Using non-compatible UPS designs, where bypass capacity changes with scalability, reduces the availability of the critical load resultingin more extensive, costly downtime. Eaton modular UPS enablesdesigning scalable systems with full bypass capacity installed,with no compromises required for selectivity.Mix and match The UPS double conversion capacity and static bypass capacity of the 93PM UPS can be sized separately, to match higher fault currentlevels of the installation. This enables matching of the UPS to siterequirements, without the need to invest in extra UPS capacity incase of high fault current levels.The modular design of the 93PM allows UPS capacity to be increasedat any time, simply by adding power modules to the existing UPS.Capacity can be increased in steps of 50 kVA, whilst still providingfull bypass capacity from day one.availability FLE X I B I L I T YHot SyncHot Sync is a patented load-sharing technology for parallel operation of UPS inverters, without communication or load-share signals. Not relying on communication link or master-control topology, the 93PM UPS provides the highest possible reliability by eliminating the single point of failure in a parallel operating UPS system.Advanced Battery ManagementThe Advanced Battery Management extends the life of valve- regulated lead-acid (VRLA) batteries, through an intelligent charging routine. This prevents unnecessary charging and significantly retards the battery wear rate. ABM technology is widely usedand accepted technology with a 20-year proven track-record.Reliable operation with mains supply and generator Eaton 93PM UPS provides unity input power factor throughoutthe load range – providing cost savings in upstream distribution and excellent compatibility with generators. The wide frequency and voltage range of UPS rectifier ensures that batteries are not worn out even if the mains network quality is poor. Eaton 93PM UPS comes with advanced and configurable rectifier functions, such as rectifier walk-in ramp and step load reduction, On Generator-limits and delayed rectifier start-up, providing reliable operation with mains and generator.Electrical installation safety made easierDesigning safe electrical installations are made easy for the designers and end users of Eaton UPS. The important safety requirements are implemented into the UPS design as standard.The installation fault current levels are determined by the sizeof incoming transformer. The UPS is validated for prospective short circuit current of Icc 100kA, which is suitable for practicallyall installations. Eaton 93PM UPS comes with an integrated Bussmann ultra-rapid fuse in its bypass line. Eaton UPS are guaranteed to be safe and compatible with any installationfault current levels, no conditions apply.The UPS safety standard (IEC/EN 62040 Part 1) also requires backfeed isolation device to be connected in the UPS static bypass path due to human safety under thyristor short circuit condition. Eaton UPS come with backfeed isolation contactor integrated internally in the unit. This also guarantees that a shorted thyristor will have no effect to the double conversion operation of the UPS, removing the single point of failure.Eaton 93PM design ensures ease of deployment, with pre-designed, pre-tested and pre-installed safety componentsintegrated as standard. Eliminating the need to designthem into the upstream panel reduces the total costof installation.The fully front-accessible design allows quick access for service and maintenance. Front access, together with innovative thermal management options of front-to-top or front-to-rear airflow, also enables installation against a wall or back-to-back, in row or inhot/cold aisle configuration – maximizing deployment flexibility. Accessorize your UPSEaton’s range of accessories for 3ph UPS systems provides flexible installation options that expedite deployment and save valuable space. The aesthetically designed accessories enable coordinated solutions that enhance both safety and reliability whilst reducing installation time and total cost.SupercapacitorsA short runtime back-up power solution has traditionally meant high-maintenance batteries or a less efficient mechanical flywheel. The new Eaton XLM Supercapacitor modules can now be integrated with the Eaton 93PM UPS to offer a new back-up power solution that is highly reliable, economical, maintenance free and manufactured from environmentally friendly materials.The solution can tolerate high ambient temperatures and provide extremely fast recharge time. The solution can also tolerate high amount of discharge-charge cycles without significant effect to the supercapacitor health.Eaton ConnectedEaton connected is an all-in-one solution for power distribution and UPS back-up power. By bringing you pre-designed solutions and prefabricated interconnections, Eaton Connected helps you to manage installation risks by simplifying the whole process from sourcing to commissioning.Both Eaton 93PM UPS and Eaton Power Xpert CX L V Switchgear are individually proven products in challenging applications. Now Eaton Connected is also tested and verified as one system, for your ultimate peace of mind.I/P Tap-OffO/P Tap-OffCyberSingle pane of glassUtilising Eaton’s Intelligent Power Software Suite (IntelligentPower Manager IPM and Intelligent Power Protector IPP) the93PM integrates with leading virtualization and storage platforms,and allows users to view, monitor and administer physical andvirtual servers, UPSs, PDUs and other power devices, from asingle pane of glass.Network- and power-related alerts will be provided through thevirtualization management application, and the 93PM will take theresiliency of the system to the next level, by bridging the electricaland IT infrastructures.Simple policy-based integrationIntelligent Power Manager ensures business continuity byenabling simple, policy-based controlled automation – driven bypower and environmental events. In case of power outage, theIPM provides several options to extend runtime for critical applica-tions:• Load shedding: non-critical services can be suspendedor carefully shut down• Critical loads can be consolidated onto fewer host servers• Unused host servers can be shut down• If UPS battery levels dips below a threshold, vmotion can betriggered to move critical Virtual Machines to an unaffected host.Intuitive Eaton 93PM UPS provides easier access to detailed status information through its large, user-friendly LCD touchscreen display . UPS status LED indicators are fitted to the UPS, providing quick and easy detection of the system status and facilitating troubleshootingAt your service everywhereWith three Power Quality manufacturing facilities in the EMEA region, plus a strong local service presence, Eaton will provide your UPS with expert support from day one to the end of its service life.Peace of mindEaton has a service team on call 24/7, to minimize risks through early detection of problems and timely action, before disturbances or downtime result.There are over 120 Eaton field engineers operating across EMEA – all comprehensively trained and continually updated on the latest products and technologies.The dedicated support package they provide will ensure your equipment runs safely, reliably, sustainably and with the utmost energy efficiency, at all times.The proof is in the testingThe quality and reliability of the Eaton 93PM is not something you have to wait to experience, Eaton’s 5 MW state-of-the-art testing facilities in Finland allow you to conduct standard and customized tests to meet your specific needs,and to address your “what if” scenarios.GeneralUPS output power rating30-500 kVAEfficiency in double conversion mode Up to 97%Variable Module Management System (VMMS)double conversionSignificantly increased efficiency at low loading Efficiency in Energy Saver System (ESS)1> 99%Paralleling capability 30-200 kVA: Up to 8 units 250-500 kVA: Up to 4 unitsRectifier and inverter topology Transformer-free 3-level IGBT-converterAudible noise 30-60kVA: <60 dBA 80-200kVA: < 65 dBA 250-500kVA: < 69 dBA ESS mode: < 47 dBAAltitude (max)1000 m without derating (max 2000 m) InputInput wiring3ph + N + PENominal voltage rating220/380V; 230/400V; 240/415V 50Hz/60Hz Input frequency range40 to 72 HzInput power factor0.99Input iTHD 30kVA, 60kVA: < 4.5% 40-500kVA: <3%Soft start capability YesInternal backfeed protection YesOutputOutput wiring3ph + N +PENominal voltage rating220/380V; 230/400V; 240/415V 50Hz/60Hz Load power factor range0.8 lagging – 0.8 leadingBatteryBattery type VRLACharging mode Advanced Battery Management or FloatTemperature compensatedbattery chargingOptionBattery start capability YesAlternative backup power technologies Wet cell batteries NiCd batteriesLi-Ion batteries SupercapacitorsAccessoriesLong life batteriesExternal battery cabinets and supercapacitor cabinetsExternal maintenance bypass switch panels, Integrated manual bypass Battery breaker enclosures for rack batteries ConnectivityNative relay inputs/outputs5 relay inputs and dedicated EPO1 relay outputMore relay contacts available as option. SoftwareEaton Intelligent Power ManagerEaton Intelligent Power ProtectorGigabit Network card(NETWORK-M2)Web/SNMPThird party certified cybersecurityUp to 3 optional sensors (EMPDT1H1C2):Temperature, humidity and two status inputsIndustrial Gateway card(INDGW-M2)Web/SNMP/Modbus RTU and TCPThird party certified cybersecurityUp to 3 optional sensors (EMPDT1H1C2):Temperature, humidity and two status inputs Power Xpert UPS Minislotcard(PXGMSUPS)Web/SNMP/Modbus RTU and TCP/BACnet IPOptional Sensor (EMP001):Temperature, humidity and two status inputs Industrial Relay-MS card(INDRELAY-MS)5 relay outputs / 1 relay input Compliance with standardsSafety IEC 62040-1; CB certifiedEMC IEC 62040-2Performance IEC 62040-3RoHS EU directive 2011/65/EUWEEE EU directive 2012/19/EU1 Additional information on ESS performance, refer to 93PM UPS Technical Specification.Due to continuous product improvement programmes, specifications are subject to change without notice.© 2022 Eaton All other trademarks are property of their respective owners. All Rights Reserved Publication No. BR153069EN December 2022 The 93PM UPS gives you a glimpse into the future of power protection. To see more of the future, visit /eaton93pmnow.Follow us on social media to receive and discuss the latest product and support information.The future of power protection starts here。
爱达顿5P系列无人值守UPS产品说明说明书

Eaton 5P850GREaton 5P UPS, 1U, 850 VA, 600 W, C14 input, Outputs: (4) C13, 230V, true sine wave, network card optionalGeneral specificationsEaton 5P UPS 5P850GR20 in 1.7 in17.4 in 30.4 lb3 year on electronics, 3 year on batteries with registration CE MarkedRoHS CompliantUL 497ANOMcTUVusUL 1778cULus ListedIEC 62040-2 C1-C2 / EN 55024 /CISPR22 Class B / FCC part 15 Class BProduct Name Catalog NumberProduct Length/Depth Product HeightProduct Width Product WeightWarranty CompliancesCertificationsABM technology (3-stage charging extends battery service life by 50% and provides advance warning for battery replacement)Sine wave850 VA600 W0.7Rack(4) C13Rackmount/wallmountC14<45 dB at 1 meter1View runtime graphEaton Intelligent Power Manager 5-series UPS overview brochureEaton 5P Rackmount UPS brochureEaton 5P850GR 2D drawingEaton 5P UPS visio stencilsEaton 5P UPS 3D drawingsEaton 5P850GR 3D drawingEaton 5P UPS installation and user manualBattery management Output waveformVA ratingWattageOutput power factor Form factorReceptacleStandard factory warrantyMounting MethodInput connectionNoise levelFeed typeRuntime graphSoftware compatibility BrochuresDrawingsManuals and user guides3-YEAR FACTORY WARRANTY w/ REGISTRATION-3 years-Parts, electronics, and batteries coverage-Standard ground shipping -Technical supportUser interfaceLCD graphical displayBattery replacementUser replaceableBattery typeSealed, lead-acidRack size1UVoltage230VTemperature range0° to 35°C (32° to 95°F)CommunicationRS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables includedRelative humidity0-90% non-condensingExtended service plansADVANCED DEPOTEXCHANGE-5-YEAR DEPOT REPAIR:5SW5Y-950UC-Expedited parts coveragefor 5 years-Parts, electronics and UPSbatteries coverage-Next business day shipping-Technical support5-YEAR ON-SITE PLAN:WFLN75XX-2509UC- On-site parts and laborcoverage for years 5- Parts, electronics and UPSbatteries coverage- 24x7 on-site laborcoverage, next-dayresponse- Next-day shipping- Technical supportSpecial featuresROO/RPO: Rear terminal block connector for remote on/off and power offColorBlack/silverExtended battery capabilityNone; See Eaton 5PX UPS for extended runtimes optionsOutput voltage range184-256 VacTopologyLine-interactiveBTU RatingOnline: 82, Battery 389Output frequency50/60 HzTypeUPSOutput nominal voltage230V default (200/208/220/230/240V)Input nominal voltage230V default (200/208/220/230/240V)Input power factor1Expansion slotsOne slot; Gigabit Network Card (Network-M2) is optionalInput voltage range160-294 V (adjustable to 150 V-294 V)Input frequency range47-70 Hz (50 Hz system), 56.5-70 Hz (60 Hz system), 40-70 Hz in low-sensitivity modeNominal frequency50-60 HzAltitudeUp to 10,000 ft (3000m) without de-ratingEaton Corporation plc Eaton House30 Pembroke Road Dublin 4, Ireland © 2023 Eaton. All rights reserved. Eaton is a registered trademark.All other trademarks areproperty of their respectiveowners./socialmedia。
500kVA,模块化UPS技术要求

1、UPS的品牌资质要求1)★UPS生产厂家注册资金大于7000万,必须获得ISO9000系列质量认证、1SO14001环境保护认证环保以及职业健康安全管理体系认证、中国驰名商标、国家火炬计划高新技术企业、市政府质量奖、省创新型企业等;2)★UPS生产厂家必须在本省内设有直属维修服务网点,并提供获得厂家授权证书及服务工程师资格证书。
3)本工程范围内的所有设备和元器件等均由投标人负责组织并供货,所有设备和元器件的选型必须满足相关技术标准。
4)★UPS电源主机、蓄电池具备信息产业部的TLC认证与检验报告;5)★UPS电源主机必须提供节能认证与检验报告;6)★UPS电源主机必须提供抗震认证与检验报告;7)★投标人必须提供UPS电源彩页原件;8)★电池与主机质保期均为三年以上;2、UPS主要技术条件1)★本次UPS电源系统采用模块化结构,容量250KV A,1套;2)★系统功率模块为≥25KV A,必须满足250KV A以上的需求,可根据负载大小灵活配置,单柜系统最大可以扩容到250KVA,为满足后续需求,柜体之间可以在线扩容,UPS系统容量最大可以扩容的500KV A;3)★UPS由UPS系统柜、监控显示模块、充电模块、功率模块组成;UPS所有模块必须满足在热拔插功能,包括充电模块、监控显示模块、功率模块;4)★UPS系统采用独立的充电模块,每个充电模块电流不小于30A,根据系统要求,充电模块可以冗余或扩容,同时充电模块的充电电流可以根据外部配置的电池容量进行设置;5)★为了避免集中旁路存在的单点瓶颈,要求每个UPS模块内部具备独立旁路功能,不接受采用静态旁路模块和接触器组合结构;6)★LCD采用5.7寸触摸屏,同时可通过监控模块LCD屏在线设置进出线方式、输入电压、输入频率范围、输出电压、输入制式、电池均充电压、浮充电压、电池容量、电池充电温度补偿系数等参数;7)★UPS标配RS232、RS485、干接点等通讯功能。
艾顿9395 200-300kVA UPS 技术规格说明说明书

Eaton 9395 200-300kVA UPS Technical SpecificationCONSTRUCTION 200kVA 225kVA 275kVA 300kVAModel: 9395E-2009395-2259395-2759395-300 Rating @ 400V 200kVA/180kW 225kVA/202kW 275kVA/250kW 300kVA/240kWMTBF 150 000h (MIL217)Classification VFI-SS-111UPS Dimensions: WxDxH (mm) 1350 x 880 x 1880Weight (kg) without batteries810kg 830kgENVIRONMENTAmbient storage temperature Range of -25 to +55°C in the protective packageAmbient service temperature +0 to +40°C (Max 45o C with 7.5% derating)Maximum service altitude 1000m above sea level max. 2000m with 1% derating per +100mRelative humidity 5 to 95%, no condensation allowedDegree of protection IP20 (EN60529)Acoustic noise at 1m (ISO7779) 75 dBAUSER INTERFACEDisplay Graphical LCD with blue backlight, 4x LEDs for notice and alarmStandard Communication Ports Hardware: 1x RS232 for local support, 4 off X-Slot (Empty), 1x Relaycontact, 1x Emergency Power off input, 2x Environmental inputsOptional X-Slot cards: Web/SNMP, Relay, Hot Sync, Power Xpert, ModBusELECTRICAL CHARACTERISTICS – INPUTRated input voltage and voltage tolerance Rectifier: 3 x 230/400Vac nominal (220/380, 230/400, 240/415 Selectable) Tolerance: 195/340–266/460V (-15%, +15%) at 100% load,161/280-266/460V (-30%, +15%), 50% loadBypass: 3 x 230/400V nominal (220/380, 230/400, 240/415 Selectable) Tolerance: 207/360 – 253/438V (-10%, +10% of nominal)Operating Frequency / Tolerance 50 or 60Hz; Tolerance: ±5 HzInput current distortion 3-5% THDi (Linear load condition at rated input current)Input power factor 0.99pf at 30-100% load, 0.95at 10% load 0.99pf at 40-100% load, 0.95at 15% load0.99pf at 30-100% load, 0.95at 10% load0.995pf at 30-100% load, 0.95at 10% loadInrush Current < 100% of rated currentNumber of input phases 3 phases + NeutralRated Rectifier Input Current 3 x 282A rms 3 x 318A rms 3 x 388A rms 3 x 388A rmsMax Rectifier Input Current 3 x 332A rms 3 x 373A rms 3 x 456A rms 3 x 456A rmsBypass input fuse/CB rating 375A 400A 500A 540A ELECTRICAL OUTPUT CHARACTERISTICS – NORMAL MODERated apparent power 200kVA 225kVA 275kVA 300kVARated active power – linear load 180kW 202kW 250kW 240kW Rated active power – 0.9 pf non-linear load180kW 202kW 247kW 240kW Transfer–normal to stored energy No breakRated output voltage 220/380, 230/400, 240/415Vac, three phaseOutput voltage variation ±2V rmsCrest factor Up to 3:1Rated output frequency 50 Hz (default) or 60 HzOutput frequency variation (synchronised if applicable) ±2Hz (default), ±0.5Hz or ±1Hz with slew rate 0.5Hz/sec (default), 2.5Hz/sec or 7.5Hz/secMaximum Phase Error Maximum of 8 degreesTotal voltage distortion 2% (Across a linear load); 5% (Across a reference non-linear load)Short circuit capability 545A, < 300ms 613A, < 300ms 750A, < 300ms 800A, < 300ms Overload capacity without bypass 10min >100-110% load, 30sec >110-125% load, 10sec >125-150% loadOverload capacity with bypass Continuous >100-115% load, 100msec 1000% loadNote: Selected Bypass fuses may limit the overload capabilityEaton 9395 200-300kVA UPS Technical Specification200kVA 225kVA 275kVA 300kVA Load power factor range 0.7 lagging - 0.8 leading without de-ratingNumber of output phases 3 PhaseOutput Voltage dynamic variation 1% during transfer from stored energy to normal mode±3% with 40msec recovery from 10% to 90% load stepMax output freq rate of change 0.5Hz/s (default), or 2.5Hz/sELECTRICAL OUTPUT CHARACTERISTICS – STORED ENERGYRated apparent power 200kVA 225kVA 275kVA 300kVARated active power – linear load180kW 202kW 250kW 240kW Rated active power – 0.9 pf non-linear load180kW 202kW 247kW 240kW Waveform SineWaveTransfer–stored to normal energy No breakRated output voltage 220/380, 230/400, 240/415 Vac three phaseOutput voltage variation ±3V rmsCrest factor Up to 3:1Rated peak output voltage 325V, ±10VRated output frequency 50Hz (default) or 60HzOutput frequency variation ±0.005Hz (single module), ±0.07Hz (Parallel system)Total output voltage distortion 2% (Across a linear load); 5% (Across a reference non-linear load)Short circuit capability 545A, < 300ms 613A, < 300ms 750A, < 300ms 800A, < 300ms Overload capability 10min >100-110% load, 30sec >110-125% load10sec >125-150% load, 300msec >150% loadLoad power factor range 0.7 lagging- 0.8 leading without de-ratingNumber of output phases 3 Phase + NeutralOutput voltage dynamic variation 0% during transfer from stored energy to normal mode±3% with 40msec recovery from 10% to 90% load stepEFFICIENCY (Input/Output)Efficiency at 100/75/50/25%linear load94/94/92/90% 94/94/93/90% 94/94/93/90% 94/94/93/90% Efficiency at 100/75/50/25% non-linear load94/93/92/90% 94/94/93/90% 94/94/93/90% 94/93/92/90%Heat dissipation*Multiply heat output in kW by 3413 to convert to BTU per hour 11.6kW at 100%8.7kW at 75%5.2kW at 50%3.0kW at 25%13.1kW at 100%9.8kW at 75%7.7kW at 50%5.7kW at 25%15.9kW at 100%11.9kW at 75%9.4kW at 50%6.9kW at 25%15.4kW at 100%11.5kW at 75%9.1kW at 50%6.7kW at 25%SYNCHRONISATION (If applicable)Acceptable voltage difference ±25%Range of frequency synch ±3Hz (default), ±0.5Hz, ±1Hz selectable.Slew Rate 1Hz/s (default), 7Hz/s, 3Hz/s, 2Hz/s, 0.5Hz/s selectable Maximum phase error 8 DegreesBATTERYBattery Nominal Voltage 480V (240 Cells)Float Charge Voltage 240 x 2.30V = 552VMaximum Charge Voltage 240 x 2.35V = 564VRestored energy time to 90% Maximum 10 hours recommended (dependant on battery size)Charging Current (at full load) 80ABattery recharge profile Advanced Battery Management (ABM®) = 90% resting,10% floating/charging Battery cut off voltage 1.75 with 2 minute shutdown timer, 1.67 VPC absolute valueBYPASS CHARACTERISTICSType of bypass Automatic Static Bypass, Optional Manual Maintenance BypassTransfer No break。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
Image shown may not reflect actual product.Cat® UPSB 505
On-Line Double Conversion UPS 160 kVA – 500 kVA
(144 kW – 450 kW)
50 Hz, 60 Hz 380-440 Volt 3-phase Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost effectiveness.
FEATURES
PRODUCT FEATURES
• Double conversion topology
• Integrated battery management system • Internal Maintenance Bypass
• Small footprint
• Up to 94.5% total system efficiency • Power factor corrected input
• Transient protection
• High-speed voltage regulation
• Bottom cable entry HIGH AVAILABILITY
The UPS has been designed for continuous operation. Redundant components and cooling are available for increased reliability, and the UPS is fault tolerant with built in 100% rated static bypass switch.
FLEXIBLE AND UPGRADEABLE
Further capacity can be added by paralleling (maximum system output of 2000 kVA). The UPS has an intuitive man/machine interface with a large high definition display and animated mimic display. With the addition of optional communication cards, it can be easily integrated into networking and monitoring systems using common protocols such as Modbus or SNMP.
• Low input current distortion • Simple installation
• Low maintenance
• Quiet operation
• Parallel up to 8 units
RELIABLE POWER PROTECTION FOR CRITICAL APPLICATIONS WORLDWIDE PRODUCT SUPPORT
Cat® dealers provide extensive post sale support including maintenance and repair agreements. Factory qualified technicians are trained to support every aspect of your Cat UPS system.
Cat® double conversion battery UPS systems utilize IGBT based technology to provide clean, stable power to sensitive loads, ensuring critical power protection, optimum performance, and extended life of the protected equipment.
SUPERIOR DESIGN
Superior system design and the use of robust digital components throughout the system yield a reliable and trouble-free UPS system.
FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT
STANDARD EQUIPMENT
OPTIONAL EQUIPMENT
• Front Panel Display
• Network Management Card
SNMP protocol over 10/100MB Ethernet connection, plus web interface and direct email/SMS notification. − Large LCD display − LED mimic diagram
− Event logging with date-time stamping of 5000 events
• Network Management Card w/Modbus
− Audible alarms Provides features of the above listed network management card with the addition of
communication through Modbus via RS-485 connection.
• Emergency Power Off (EPO) Contacts
• Advanced Monitoring provides intelligent battery
management that automatically tests the battery
system and provides life cycle monitoring of remaining battery life expectancy.
• Battery Circuit Breaker
Provides circuit breaker disconnect for battery power source for use with customer supplied batteries
• Relay Card
Four programmable 9VDC input contacts (20mA
consumption) and six programmable 30VDC output
contacts (rated for 1A at 30VDC) for remote
monitoring of UPS operation.
• Top cable entry Provides auxiliary cabinet for top cable entry. • Backfeed protection
Provides disconnect of the UPS from the input source on UPS discharge
• Internal Maintenance Bypass
- Promotes safe UPS maintenance
- Eliminates the need for costly additional external
bypass breakers
• External sync Provides controls to synchronize the outputs of two UPS modules. - Reduces installation costs
* Tolerance range is limited to +5/ -10%
ELEVATION DRAWINGS
(160-400KVA) (500KVA) ONE LINE DRAWING。