无功补偿功率因数查询表
功率因数对照表[1]
功率因数对照表[1]预览说明:预览图片所展示的格式为文档的源格式展示,下载源文件没有水印,内容可编辑和复制(附表:)功率因数调整电费表表一:以0.90为标准值的功率因数调整电费表减收电费实际功率因数0.900.910.920.930.940.95-1.00 月电费减少%0.00.150.300.450.600.75增收电费实际功率因数0.890.880.870.860.850.840.830.820.810.800.790.780.770.760.750 .740.730.720.710.700.690.680.670.660.65月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.64及以下,每降低0.01电费增加2%表二:以0.85为标准值的功率因数调整电费表减收电费实际功率因数0.850.860.870.880.890.900.910.920.930.94-1.00 月电费减少%0.00.10.20.30.40.50.650.800.950.75增收电费实际功率因数0.840.830.820.810.800.790.780.770.760.750.740.730.720.710.700 .690.680.670.660.650.640.630.620.610.60月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.59及以下,每降低0.01电费增加2%表三:以0.80为标准值的功率因数调整电费表减收电费实际功率因数0.800.810.820.830.840.850.860.870.880.890.900.910.92-1.00 月电费减少%0.00.10.20.30.40.50.60.70.80.9 1.0 1.15 1.30 增收电费实际功率因数0.790.780.770.760.750.740.730.720.710.700.690.680.670.660.650 .640.630.620.610.600.590.580.570.560.55月电费增加%0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.57.07.58.08.59.09.510.011.012.013.014.015.0功率因数自0.54及以下,每降低0.01电费增加2%功率无功/有功电费增减功率无功/有功电费增减功率因无功/有功电费增减0.80 0.85 0.90 0.80 0.85 0.90 0.80 0.85 0.90 100 0.000-0.105 -1.30 -1.10 -0.75 75 0.869-0.895 +2.5 +5.0 +7.5 50 1.710-1.755 +25.0 +35.0 +45.0 99 0.106-0.176 -1.30 -1.10 -0.75 74 0.896-0.922 +3.0 +5.5 +8.0 49 1.756-1.802 +27.0 +37.0 +47.0 98 0.177-0.227 -1.30 -1.10 -0.75 73 0.923-0.950 +3.5 +6.0 +8.5 48 1.803-1.852 +29.0 +39.0 +49.0 97 0.228-0.272 -1.30 -1.10 -0.75 72 0.951-0.977 +4.0 +6.5 +9.0 47 1.853-1.903 +31.0 +41.0 +51.0 960.273-0.311 -1.30 -1.10 -0.75 71 0.978-1.006 +4.5 +7.0 +9.5 461.904-1.956 +33.0 +43.0 +53.0 95 0.312-0.347 -1.30 -1.10 -0.75 70 1.007-1.034 +5.0 +7.5 +10.0 45 1.957-2.012 +35.0 +45.0 +55.0 94 0.348-0.379 -1.30 -1.10 -0.60 69 1.035-1.063 +5.5 +8.0 +11.0 44 2.013-2.069 +37.0 +47.0 +57.0 93 0.380-0.411 -1.30 -0.95 -0.45 68 1.064-1.093 +6.0 +8.5 +12.0 43 2.070-2.129 +39.0 +49.0 +59.0 92 0.412-0.439 -1.30 -0.80 -0.30 67 1.094-1.122 +6.5 +9.0 +13.0 42 2.130-2.178 +41.0 +51.0 +61.0 91 0.440-0.468 -1.15 -0.65 -0.15 66 1.123-1.153 +7.0 +9.5 +14.0 41 2.179-2.252 +43.0 +53.0 +63.0 90 0.469-0.498 -1.10 -0.5 0.00 65 1.154-1.184 +7.5 +10.0 +15.0 40 2.253-2.325 +45.0 +55.0 +65.0 89 0.499-0.525 -0.9 -0.4 +0.5 64 1.185-1.216 +8.0 +11.0 +17.0 39 2.326-2.397 +47.0 +57.0 +67.0 88 0.526-0.552 -0.8 -0.3 +1.0 63 1.217-1.249 +8.5 +12.0 +19.0 38 2.398-2.471 +49.0 +59.0 +69.0 87 0.553-0.580 -0.7 -0.2 +1.5 62 1.250-1.282 +9.0 +13.0 +21.0 37 2.472-2.550 +51.0 +61.0 +71.0 86 0.581-0.606 -0.6 -0.1 +2.0 611.283-1.315 +9.5 +14.0 +23.0 362.551-2.632 +53.0 +63.0 +73.0 85 0.607-0.632 -0.5 0.00 +2.5 60 1.316-1.350 +10.0 +15.0 +25.0 35 2.633-2.720 +55.0 +65.0 +75.0 84 0.633-0.658 -0.4 +0.5 +3.0 59 1.351-1.386 +11.0 +17.0 +27.0 34 2.721-2.813 +57.0 +67.0 +77.0 83 0.659-0.685 -0.3 +2.0 +3.5 58 1.387-1.423 +12.0 +19.0 +29.0 33 2.814-2.909 +59.0 +69.0 +79.0 82 0.686-0.710 -0.2 +1.5 +4.0 57 1.424-1.459 +13.0 +21.0 +31.0 32 2.910-3.012 +61.0 +71.0 +81.0 81 0.711-0.737 -0.1 +2.0 +4.5 56 1.460-1.498 +14.0 +23.0 +33.0 31 3.013-3.122 +63.0 +73.0 +83.0 80 0.738-0.762 0.00 +2.5 +5.0 55 1.499-1.537 +15.0 +25.0 +35.0 30 3.123-3.238 +65.0 +75.0 +85.0 79 0.763-0.788 +0.5 +3.0 +5.0 54 1.538-1.579 +17.0 +27.0 +37.0 29 3.239-3.362 +67.0 +77.0 +87.0 78 0.789-0.815 +1.0 +3.5 +6.0 53 1.580-1.620 +19.0 +29.0 +39.0 28 3.363-3.496 +69.0 +79.0 +89.0 77 0.816-0.842 +1.5 +4.0 +6.5 52 1.621-1.664 +21.0 +31.0 +41.0 27 3.497-3.638 +71.0 +81.0 +91.0 76 0.843-0.868 +2.0 +4.5 +7.0 51 1.665-1.709 +23.0 +33.0 +43.0 26 3.639-3.791 +73.0 +83.0 +93.0表四:功率因数及全部电费增减%速见表。
无功补偿计算及补偿容量计算
功率因数和无功补偿容量的计算:
1、功率因数的计算:
(1)功率因数可以从所接电网的功率因数表里直接读取。
(2)若用电用户没有安装功率因数表,功率因数可以从所装的电度表里直接读取有功功
因数。
即:
cosφ=1/SQRT(1+(tanφ)*(tanφ))=P/SQRT(P*P+Q*Q)=1/SQRT(1+(Q/P)*(Q/P))如果记录的某段时间内的有功功率P和无功功率Q可知,即可求出该段时间内的
2、补偿容量的确定:
补偿容量的确定:补偿容量的大小决定于电力负荷的大小、补偿前功率因数的大小和补
Qc=P年*(tanφ1-tanφ2)
Q c--无功补偿容量(kvar)
P年--年平均功率(kW)
tanφ1--补偿前功率因数角的正切值
tanφ2--补偿后功率因数角的正切值
举例说明:
答:此系统呈现感性负载,为提高功率因数,可以采用400V低压就近补偿原
1、若一10/0.4kV电力系统有功负荷100kW,呈感性负责,系统功率因数0.74。
有功功率和无功功率进行计算得出功率
=1/SQRT(1+(Q/P)*(Q/P))
间内的加权平均功率因数:
小和补偿后提高的功率因数的大小
补偿后cos φ2
1kW有功功率所需补偿电容器的补偿容量(kvar)
无
0.74。
若将系统功率因数提到0.98,需要补偿多少无功容量?
补偿原则,采用并联电容器方法补偿,补偿容量经查表可以求得:Qc=100*0.71=71(kvar)。
无功功率补偿容量计算表
无功功率补偿容量计算表
参数名称
视在功率 补偿前功率因数 补偿后功率因数 需要补偿的无功功率容量
参数大小
备注
3200 0.8 0.96 1173.333333
本计算方式适用于知道变压 器的视在功率 、补偿前和 补偿后的功补偿前功率因数 补偿后功率因数 需要补偿的无功功率容量
1600 0.8 0.96 733.3333333
本计算方式适用于知道变压 器的有功功率 、补偿前和 补偿后的功率因数,计算需 要补偿的无功功率
说明:此表为简单计算无功补偿容量的表格,需要输入视在功率/有功功率、补偿前功率因数 和补偿后功率因数,表格会自动生成需要补偿的无功功率。
无功补偿容量计算方法及表
无功补偿容量计算方法及表无功补偿容量的计算主要取决于几个关键因素,包括系统负荷的功率因数、补偿前后功率因数的目标值、以及负荷的电流值。
以下是无功补偿容量计算的基本步骤:第一步,计算负荷的功率因数。
功率因数是有功功率(真实功率)与视在功率(总功率)的比值。
有功功率是指电器在使用中消耗的电量,而视在功率是指电路中存在的总电量。
功率因数可以用以下公式计算:功率因数 = 有功功率 / 视在功率第二步,确定补偿后希望达到的功率因数。
这通常是由电力公司的要求或者由电器设备的规格来决定的。
例如,如果你的电力公司要求所有用户的功率因数至少为0.9,那么这个值就是你的目标功率因数。
第三步,计算需要补偿的无功功率。
无功功率是没有做任何实际工作,但仍然需要供电的能量。
它是由于电感或电容的交变电流与电源的电压之间的相位差而产生的。
无功功率可以用以下公式计算:无功功率 = 视在功率 * (1 - 功率因数的平方)第四步,根据负荷电流值,利用以下公式求得补偿电容器的容量:无功电容容量 = 无功功率 / (2 * π * 频率 * 负荷电流值)以上步骤中的所有数值都应该根据实际情况进行计算。
其中,有功功率可以通过测量设备运行时的电量消耗来得到,视在功率可以通过测量设备运行时的电压和电流的乘积得到,负荷电流值可以通过测量设备的电流有效值得到。
对于无功电容容量的选择,除了以上的计算方法,也可以根据实际需要选择标准的电容容量,例如10k乏、20k乏、50k乏等。
需要注意的是,电容器的容量和电压等级以及电流等级都是有关的,因此需要根据具体情况来选择。
此外,也应当考虑一定的余量以应对负载变化。
对于并联电容器组来说,应选择单个电容器的容量至少为总补偿容量的一半,然后根据实际需要选择电容器的数量。
如果电容器的容量太大,可能会导致电流过大,从而烧坏电容器。
以上就是无功补偿容量的计算方法。
在实际应用中,应当根据实际情况进行适当的调整。
例如,如果负载是电动机等感性负载,应当考虑采用动态无功补偿装置。
无功补偿容量计算方法及表
无功补偿容量计算方法及表无功补偿详细的容量确定计算方法-补偿容量的确定可以根据负荷的最大功率、补偿前的功率因数及要求补偿后达到的功率因数,用下式计算确定:Q =α*P*(tanφ—tanφ) 12式中:Q —所需补偿的总无功功率,kvar;α—平均负荷系数,取0.7~0.8;P —用户最大负荷,kW;tanφ—补偿前平均功率因数角 1tanφ—补偿后平均功率因数角 2或Q =α*P*qq —补偿率,kvar / kW (可从附表中查取)附表:每kW负荷所需无功补偿率值查取表cosφ cosφ 120.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.960.981 1.008 1.035 1.060 1.086 1.117 1.138 1.166 1.192 1.219 1.2461.276 1.305 1.338 1.368 1.404 1.442 0.500.939 0.966 0.933 1.018 1.044 1.070 1.106 1.134 1.160 1.187 1.2141.244 1.273 1.306 1.336 1.372 1.410 0.510.890 0.917 0.945 0.969 0.995 1.021 1.047 1.075 1.101 1.128 1.1551.185 1.217 1.247 1.277 1.313 1.351 0.520.819 0.876 0.903 0.928 0.954 0.980 1.006 1.034 1.060 1.087 1.1141.144 1.173 1.120 1.206 1.236 1.272 0.530.808 0.835 0.862 0.887 0.913 0.939 0.965 0.993 1.019 1.046 1.0751.103 1.133 1.165 1.195 1.231 1.269 0.540.766 0.793 0.820 0.815 0.871 0.8970.8590.923 0.951 0.977 1.0041.031 1.061 1.090 1.123 1.153 1.189 1.227 0.550.728 0.755 0.782 0.807 0.829 0.859 0.885 0.913 0.939 0.966 0.9911.023 1.052 1.085 1.115 1.151 1.189 0.560.691 0.718 0.745 0.770 0.796 0.822 0.846 0.876 0.902 0.929 0.956 0.986 1.015 1.048 1.078 1.114 1.520 0.570.655 0.682 0.709 0.734 0.760 0.786 0.812 0.840 0.866 0.893 0.920 0.950 0.979 1.012 1.042 1.078 1.116 0.580.618 0.645 0.672 0.697 0.723 0.749 0.775 0.803 0.829 0.856 0.883 0.913 0.942 0.975 1.005 1.041 1.079 0.590.583 0.610 0.637 0.662 0.688 0.714 0.740 0.768 0.794 0.821 0.848 0.878 0.905 0.940 0.970 1.006 1.044 0.600.549 0.576 0.603 0.628 0.654 0.680 0.706 0.734 0.760 0.787 0.841 0.844 0.873 0.906 0.936 0.972 1.010 0.610.515 0.547 0.560 0.594 0.620 0.640 0.672 0.700 0.726 0.753 0.780 0.810 0.839 0.872 0.902 0.938 0.974 0.620.481 0.508 0.535 0.560 0.586 0.612 0.638 0.666 0.692 0.719 0.746 0.776 0.805 0.838 0.868 0.904 0.942 0.630.450 0.477 0.504 0.529 0.555 0.581 0.607 0.635 0.661 0.688 0.715 0.745 0.774 0.807 0.837 0.873 0.911 0.64cosφ cosφ120.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.960.417 0.444 0.471 0.496 0.522 0.548 0.574 0.602 0.628 0.655 0.682 0.712 0.741 0.774 0.804 0.840 0.878 0.650.386 0.415 0.442 0.467 0.493 0.519 0.545 0.573 0.599 0.626 0.654 0.683 0.712 0.745 0.775 0.811 0.849 0.660.357 0.384 0.411 0.436 0.462 0.488 0.514 0.542 0.566 0.595 0.622 0.652 0.681 0.714 0.744 0.780 0.818 0.670.327 0.354 0.381 0.406 0.432 0.458 0.484 0.512 0.538 0.565 0.594 0.622 0.651 0.684 0.717 0.750 0.788 0.680.297 0.324 0.351 0.376 0.402 0.428 0.454 0.482 0.508 0.535 0.562 0.592 0.621 0.654 0.683 0.720 0.758 0.690.270 0.297 0.323 0.349 0.375 0.401 0.427 0.455 0.481 0.508 0.535 0.565 0.594 0.627 0.657 0.693 0.731 0.700.241 0.268 0.295 0.320 0.346 0.372 0.398 0.426 0.452 0.479 0.506 0.536 0.565 0.598 0.628 0.664 0.720 0.710.212 0.239 0.266 0.291 0.317 0.343 0.371 0.397 0.425 0.450 0.477 0.507 0.536 0.569 0.599 0.635 0.673 0.720.185 0.212 0.239 0.264 0.290 0.316 0.342 0.370 0.396 0.423 0.450 0.480 0.509 0.542 0.572 0.608 0.646 0.730.157 0.184 0.211 0.236 0.262 0.288 0.315 0.342 0.368 0.395 0.425 0.4520 0.481 0.514 0.546 0.580 0.618 0.740.131 0.158 0.185 0.210 0.236 0.262 0.288 0.316 0.342 0.369 0.396 0.426 0.455 0.488 0.518 0.554 0.592 0.750.103 0.130 0.157 0.182 0.208 0.234 0.260 0.288 0.316 0.341 0.368 0.398 0.427 0.460 0.492 0.526 0.563 0.760.078 0.105 0.132 0.157 0.183 0.209 0.235 0.263 0.289 0.316 0.343 0.3730 0.402 0.435 0.465 0.501 0.539 0.770.052 0.079 0.106 0.131 0.157 0.183 0.209 0.237 0.263 0.290 0.317 0.347 0.376 0.409 0.439 0.475 0.513 0.780.024 0.051 0.078 0.103 0.129 0.155 0.181 0.209 0.235 0.262 0.289 0.319 0.348 0.381 0.411 0.447 0.485 0.790.026 0.052 0.078 0.104 0.130 0.157 0.183 0.210 0.238 0.266 0.294 0.326 0.355 0.387 0.421 0.458 0.800.026 0.052 0.078 0.104 0.131 0.157 0.180 0.212 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.810.026 0.052 0.078 0.104 0.131 0.158 0.186 0.213 0.242 0.272 0.303 0.335 0.369 0.406 0.820.026 0.052 0.079 0.105 0.132 0.160 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.830.026 0.053 0.079 0.106 0.134 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.840.026 0.053 0.080 0.107 0.135 0.164 0.194 0.225 0.257 0.291 0.328 0.85• • • • • • • • • • • • • • • • • • 【唯美句子】走累的时候,我就到升国旗哪里的一角台阶坐下,双手抚膝,再闭眼,让心灵受到阳光的洗涤。
功率因数与补偿容量查询表
功率因数与补偿容量查询表补偿前功率因数值cosf1补偿后功率因数目标值及每KW负荷所需电容器容量(KVar) 0.700. 800. 820. 840. 86 0. 880.900. 920. 940. 960. 98 1.00.500.710.9821. 034 1. 086 1. 139 1. 192 1. 248 1. 306 1. 369 1. 440 1. 529 1. 3720.510.520.53 0.540.550.670.620.580.54 0.500.9370.8930.8500.8090.769 0.9890.9450.9020.8610.821 1. 0410.9970.9540.9130.873 1.094 1.0501.0070.9660.926 1.147 1.103 1.060 1.0190.979 1. 203 1.187 1.116 1.075 1.035 1.261 1.217 1.174 1.133 1.093 1.324 1.280 1.237 1.16 1.156 1.395 1.351 1.308 1.267 1.227 1.484 1.440 1.397 1.356 1.316 1.687 1.643 1.600 1.559 1.5190.560.570.580.590.7300.6920.6550.6190.5830.782 0.7440.7070.6710.6350.8360.769 0.7590.7230.6870.8870.840.812 0.7760.7400.9400.9020.8650.820.7930.9960.9580.9210.8850.8491.054 1.0160.9790.9430.907 1.117 1.079 1.042 1.0060.970 1.188 1.1500 1.113 1.077 1.041 1.277 1.239 1.202 1.116 1.130 1.480 1.442 1.405 1.36 1.3330.610.620.63 0.640.650.280.250.210.18 0.150.5490.5160.4830.4510.419 0.6010.5680.5350.5030.4710.653 0.6200.5870.5550.5230.7060.673 0.6400.6080.5760.7590.7260.693 0.6610.6290.8150.7820.7490.717 0.6850.8730.8400.8070.7750.743 0.9360.9030.8700.8380.806 1.0070.9740.9410.9090.877 1.096 1.0631.0300.9980.966 1.299 1.266 1.233 1201 1.1690.660.670.680.690.3880.3580.3280.2990.2700.440 0.4100.3800.3510.3220.4920.462 0.4320.4030.3740.5450.5150.485 0.4560.4270.5980.5680.5360.509 0.4800.6540.6240.5940.5650.536 0.7120.6820.6520.6230.5940.775 0.7450.7150.6860.6570.8460.816 0.7860.7570.7280.9350.9050.8750.8460.817 1.138 1.108 1.073 1.0491.0200.710.720.730.740.75 0.2420.2140.1860.1590.1320.294 0.2660.2380.2110.1840.3460.318 0.2900.2630.2360.3990.3710.343 0.3160.2890.4520.4240.360.369 0.3420.5080.4800.4520.4250.398 0.5660.5380.5100.4830.4560.629 0.6010.5730.5460.5190.7000.672 0.6440.6170.5900.7890.7610.733 0.7060.6790.9920.9640.9360.909 0.8820.760.770.780.790.80 0.1050.0790.0520.0260.0000.1570.1310.1040.0780.0520.2090.183 0.1560.1300.1040.2620.2360.209 0.1830.1570.3510.2890.2620.236 0.2100.3710.3450.3180.2920.266 0.4290.4030.3760.3500.3240.492 0.4660.4390.4130.3870.5630.537 0.5100.4840.4580.3520.3260.599 0.5730.5470.8550.8290.8020.776 0.7500.810.820.830.840.85 0.0260.0000.0780.0520.0260.000 0.1310.1050.0790.0530.0270.184 0.1580.1320.1060.0800.2400.214 0.1880.1620.1360.2980.2720.246 0.2200.1940.3610.3350.3090.283 0.2570.4320.4060.3800.3540.328 0.5210.4950.4690.4430.4170.724 0.6980.6720.6460.6200.860.87 0.880.890.90 0.0000.0530.0270.0000.109 0.0830.0560.0280.0000.1670.141 0.1140.0860.0580.2300.2040.177 0.1490.1210.3010.2750.2480.2200.1920.3900.3640.3370.3090.281 0.5390.5670.5400.5120.4840.91 0.920.930.940.95 0.0300.0000.0930.0630.0320.000 0.1640.1340.1030.0710.0370.235 0.2230.1920.1600.1260.4560.426 0.3950.3630.3290.960.970.98 0.99 1.00 0.0000.0890.0480.0000.292 0.2510.2030.1430.000有功功率与视在功率的比值为功率因数:cosf=P/S无功功率的传输加重了电网负荷,使电网损耗增加,系统电压下降。
无功补偿EKG样本最新资料(压缩版)
The required capacitor power is:
Q C = 500 kW 1.13 = 565 Kvar
概Hale Waihona Puke 述际情况,在电气绝缘,防护强度,安全等级等均更适合。
C
P
Blindleistung des erforderlichen Kompensationskondensators active power of the load to be corrected Wirkleistung der zu kompensierenden Last
功率因数查询表
Chart 2_Tabelle 2
original power factor Ausgangsleistungsfaktor
conversion factor F for a target power factor Umrechnungsfaktor für einen Zielleistungsfaktor cos 2 0.70 3.879 2.853 2.160 1.656 1.271 0.964 0.712 0.498 0.313 0.149 0.75 4.017 2.991 2.298 1.795 1.409 1.103 0.85 0.637 0.451 0.287 0.138 0.80 4.149 3.123 2.430 1.926 1.541 1.235 0.982 0.768 0.583 0.419 0.27 0.132 0.85 4.279 3.253 2.560 2.057 1.672 1.365 1.112 0.899 0.714 0.549 0.4 0.262 0.13 0.90 4.415 3.389 2.695 2.192 1.807 1.500 1.248 1.034 0.849 0.685 0.536 0.398 0.266 0.135 0.92 4.473 3.447 2.754 2.250 1.865 1.559 1.306 1.092 0.907 0.743 0.594 0.456 0.324 0.194 0.058 0.94 4.536 3.510 2.817 2.313 1.928 1.622 1.369 1.156 0.97 0.806 0.657 0.519 0.387 0.257 0.121 0.96 4.607 3.581 2.888 2.385 2.000 1.693 1.440 1.227 1.042 0.877 0.729 0.59 0.458 0.328 0.193 0.037 0.98 4.696 3.670 2.977 2.473 2.088 1.781 1.529 1.315 1.130 0.966 0.817 0.679 0.547 0.417 0.281 0.126 1.00 4.899 3.873 3.180 2.676 2.291 1.985 1.732 1.518 1.333 1.169 1.020 0.882 0.75 0.62 0.484 0.329