3RW30 31 电子式软起动器 用户指导手册
西门子 3RW44软启动器 说明书
2.1.3 SIRIUS 软起动器培训课程 ..............................................................................................................2-2 2.2 一般负载或重载起动 .................................................................................................................................2-3 2.2.1 2.2.2 正常起动(脱扣等级 10)的应用示例 ............................................................................................2-3 重载起动(脱扣等级 20)的应用示例 ............................................................................................2-3
2.2.3 超重载起动(脱扣等级 30)的应用示例.........................................................................................2-4 2.3 接通持续时间与通断频率 ...........................................................................................................................2-5 2.4 安装海拔高度与环境温度 ...........................................................................................................................2-6 2.5 3 3.1 出厂基本设置 ............................................................................................................................................2-7 软起动器的安装 ........................................................................................................................................3-2 3.1.1 3.1.2 拆包 ..............................................................................................................................................3-2 安装位置 .......................................................................................................................................3-2 安装、连接与回路结构 .......................................................................................................................... 3-1
3RW40说明书
软起动器 3RW4060947-4-2EN/IEC使用说明书订货号:3ZX1012-0RW40-1AA1在安装、操作或维护本设备之前请阅读并掌握这些操作说明。
危险危险电压。
可能造成人员伤亡。
在操作设备之前须切断电源。
只有使用合格部件才能保证本设备的可靠性能。
危险危险电压可能造成人员伤亡。
为避免触电或被电烧伤,在软起动器带电时不能接触软起动器的接线端。
即使软起动器处于“OFF”状态时,输出端仍然带有电压。
GWA 4NEB 535 2193-10 1复位/测试旁通出厂设定中文x I e 电流极限值 5t Ron 加速时间7 sU s 起动电压50 %t Roff 惰转时间0I e 额定电机电流最大值CLASS 等级10RESET MODE 复位模式手动2GWA 4NEB 535 2193-10对“ON/RUN ”输出13/14进行编程(出厂设定为:ON )RESET / TEST 1)RESET MODE 2)DEVICE 3) STATEBYPASSED 4) FAILURE 5) AUTO按压按钮以便保存按压按钮以便转换英文中文1) RESET / TEST 复位/测试2) RESET MODE 复位模式3) DEVICE设备4) STATE BYPASSED 状态旁通5) FAILURE 故障6)AUTO运行OFFON闪烁闪光警告不要在应用之中使用自动复位模式,因为电机的意外自动重启可能对人员或设备造成伤害。
GWA 4NEB 535 2193-10 3L1/L2/L3, T1/T2/T3:电源电路1. A1, A2, 2/-, 3/+, 1 / IN1, 13, 14/24, 23, 95, 96,98:控制电路/辅助电路2. GWA 4NEB 535 2193-104注意软起动器 3RW40 设计用于A类设备。
在民用环境中使用此类产品可能造成无线电干扰。
注意!切断电压!GWA 4NEB 535 2193-10 53RU1900-2A 远程复位3RU1900-2A 远程复位6GWA 4NEB 535 2193-10GWA 4NEB 535 2193-10 73RW40 5: M6 ... 10 Nm3RW40 7: M8 ... 15 Nma b c d e f g h i k l m n o3RW40 5 180 120 37 17 167 100 223 250 180 148 6,5 153 7 1983RW40 7 210 160 48 25 190 140 240 278 205 166 10 166 9 230注意保留足够的自由空间,以便确保用于冷却所需的空气能够从设备底部流通到顶部。
软启动器
32
- 7.5 15 - 27
- 7.5 7.5 20 - S2
3RW30 34-1AB ☐4 1 1 件 131 0.794
38
- 11 18.5 - 32
- 10 10 25 - S2
3RW30 35-1AB ☐4 1 1 件 131 0.779
45
- 15 22 - 38
- 10 15 30 - S2
5.5 ... 250 - -25 ... +60
√ √ 40 ... 100 0 ... 20 - - - -
√ √ √ √ √ √ - - - - - - - - - - - - - - - 1 - 2 个控制相位 √ √ √ √ -
29 ... 1214 200 ... 690
15 ... 710 22 ... 1200 0 ... +60
A
额定工作电压
V
400 V 时的电机额定值
• 标准接线方式
kW
• 内三角接线方式
kW
温度范围
ºC
软起动 / 软停止 电压斜坡
起动 / 停止电压
%
起动 / 停止时间
s
转矩控制
起动 / 停止转矩
%
转矩极限值
%
斜坡时间
s
内置旁路接触器
设备自保护
电机过载保护
电机热敏电阻保护
集成远程复位
可调电流限流功能
内三角接线方式
有关详细信息,请浏览: /sanftstarter
1/194
概述
提供有各种 SIRUS 3RW 30/31 软起动器型号: ● 标准型,用于定频三相电机,规格 S0、S00、S2 和 S3 ● 定速三相电机型,22.5mm 外壳 ● 3RW1 专用型,用于 Dahlander 电机,仅规格 S0 ● 软起动单相电机型,规格 S0、S2 和 S3
软启动器解析
软启动器交流电机全压直接起动将产生过高的电动转矩与起动电流:(1)起初时电流可达5-7倍的额定电流,造成电动机绕组因过流引起过温,从而加速绝缘老化,严重时电机可能烧毁。
(2)造成供电网络电压降过大,影响到电网内其他电气设备的运转。
当电压≤0.85额定电压时,可能引起电动机本身的起动无法正常完成,尤其是欠压保护要动作。
(3)起动时能量损失过大,尤其当频繁起停时。
(4)对设备造成大的冲击力、使机械传动部件非正常磨损、加速老化,缩短寿命,尤其是过高的起动冲击转矩将引起一系列的机械问题,如连接件损坏、电动机机座变形、传送带撕裂,齿轮或齿轮箱损坏等。
全压起动的电动机容量愈大,供电变压器容量愈小时,这种影响愈显著。
通常认为电动机容量大于动力变压器容量的30%时,不允许经常全压起动。
解决此类问题的常用方法为:适当降低电动机的端电压,从而减少电动机的起动电流及过大的起动冲击转矩。
交流电机传统的起动方法有:自耦变压器起动、星-三角起动、串电抗器起动、串电阻起动等,这些起动方式都属于有级减压起动,存在明显缺点,即起动过程中出现二次冲击电流。
软起动器(Soft Starter):主要构成是串接于电源与被控电机之间的三相反并联晶闸管及其电子控制电路。
通过控制三相反并联闸管的导通角,使电机输入电压从零以预设函数关系逐渐上升,即为软起动,在软起动过程中电机起动转矩逐渐增加,转速也逐渐增加,直至起动结束后再赋予电机全电压。
软起动器和变频器是两种完全不同用途的产品。
变频器是用于需要调速的地方,其输出不但改变电压而且同时改变频率;软起动器实际上是个调压器,输出只改变电压并没有改变频率。
变频器具备所有软起动器功能,但它比软起动器贵得多,结构也复杂得多。
软起动器特别适用于各种泵类负载或风机类负载,需要软起动与软停车的场合。
同样对于变负载工况、电动机长期处于轻载运行,只有短时或瞬间处于重载场合,应用软起动器(不带旁路接触器)也具有轻载节能的效果软起动一般有下面几种起动方式。
软启动3RW3003-1CB54
旨在为客户带去更多便利:SIRIUS低压控制产品不仅提供有全线产品系 列,包括负载馈电器开关设备、配电设备、控制和信号设备以及成套电控 柜系列;而且就操控简便性而言,也是树立了行业新标杆。例如,通过采 用创新技术的连接方式或不断缩小产品尺寸,来保证产品能够简便、快速 地安装,并使得其运行绝对可靠。将产品标准化,产品使用寿命更长。此 外采用先进的无缝集成理念 ( 例如全集成能源管理、集成安全功能和 ECOFAST系统),源自西门子的产品线还能够加以优化,进行系统集成。即 使遇到一些问题,西门子遍布全球的快速物流系统也能够使问题得到快 速解决。采用西门子SIRIUS低压控制产品,客户不但可以“心怡”工作, 而且还能够使其产品“前瞻”未来。
6|7
一些基本信息
软起动器的基本原理? 软起动器可以限制起动电流 和起动转矩,有效防止机械 冲击以及电网电压降。通过 相位控制降低电机电压,并 能够在可调起动时间内将电 机电压增加到电网电压。软 起动和软停车可以保证连 接设备上的应力最小化,确保生产运营平 稳。 可以使用软起动器装备负载馈电器吗? 绝对可以。结合使用电机起动保护器,例 如SIRUIS 3RV,可以很容易地装备小型非 熔断器保护的负载馈电装置。此外结合使 用过载继电器,还可快速实施节省空间的 熔断器保护的负载馈电装置。
US
能否进行通讯? 当然。西门子软起动器具有通讯功能。对于
电压斜坡软起动和限流软起动
是否所有三相都需要控制? 不是。如果采用西门子标准软起动器,只 需控制两相,即可实现电机平稳起动。不 仅如此,西门子解决方案还可以显著降低 成本,节省在电控柜中的空间占用。但是, 如果必须采用内三角接线方式,则还必须 控制第三相。
2|3
我们的太阳系卓尔不群 — 颇富灵性,运行稳定...
SIRIUS 3RW5074-6AB14软启动器产品说明书
● of standard HMI module usable ● of high feature HMI module usable ● of communication module PROFINET standard usable ● of communication module PROFIBUS usable ● of communication module Modbus TCP usable ● of communication module Modbus RTU usable ● of communication module Ethernet/IP ● of circuit breaker usable at 400 V ● of circuit breaker usable at 500 V ● of the gG fuse usable up to 690 V ● of full range R fuse link for semiconductor protection usable up to 690 V ● of back-up R fuse link for semiconductor protection usable up to 690 V ● of line contactor usable up to 480 V ● of line contactor usable up to 690 V General technical data starting voltage [%] stopping voltage [%] start-up ramp time of soft starter ramp-down time of soft starter current limiting value [%] adjustable accuracy class acc. to IEC 61557-12 certificate of suitability ● CE marking ● UL approval ● CSA approval product component ● HMI-High Feature ● is supported HMI-Standard ● is supported HMI-High Feature product feature integrated bypass contact system number of controlled phases
三岵Siemens SIRUS 3RW30 31软启动器说明书
Siemens LV 1 · 20066■OverviewVarious versions of the SIRUS 3RW30/31 soft starters are available:•Standard version for fixed frequency three-phase motors, sizes S00, S0, S2 and S3•Version for fixed-speed three-phase motors in a 22.5mm enclosure•Special-purpose version 3RW31 for Dahlander motors only in size S0•Version for soft starting single-phase motors of sizes S0, S2 and S3.SIRIUS 3RW30/31 for three-phase motorsSoft starters rated up to 55kW (at 400V) for standard applica-tions in three-phase networks. Extremely small sizes, low power losses and simple commissioning are just a few of the many ad-vantages of this soft starter. The special feature of the 3RW31 series is that it allows independent definition of two separate acceleration ramps (Dahlander motors).SIRIUS 3RW30 for single-phase motorsThe additional version for standard applications in single-phase networks. Its voltage edge function reduces the motor's inrush current and effectively lowers the torque at the point of starting up. The load and the supplying network are thus protected.■ApplicationThe SIRIUS 3RW30/31 solid-state soft starters are suitable for soft starting and stopping of three-phase asynchronous ma-chines.Due to two-phase control, the current is kept at minimum values in all three phases throughout the entire starting time. Due to continuous voltage influencing, current and torque peaks, which are unavoidable in the case of wye-delta starters, for instance, do not occur.Application areas •Fans •Pumps•Building/construction machines •Presses •Escalators•Transport systems•Air conditioning systems •Ventilators•Assembly lines•Compressors and coolers •Operating mechanisms6■Selection and ordering dataSelection of the soft starter depends on the motor’s ratedcurrent.3RW30 03-2CB543RW30 25-1AB14*You can order this quantity or a multiple thereof.6/6Siemens LV 1 · 2006Siemens LV 1 · 200661)Rated control supply voltage U s 110 ... 230 V AC/DC.Selection of the soft starter depends on the motor’s rated current.The SIRIUS 3RW3 solid-state soft starters are designed for easy starting conditions. J Load < 10 x J Motor . In the event of deviating conditions or increased switching frequency, it may be neces-sary to choose a larger device. Siemens recommends the use of the selection and simulation program Win-Soft Starter.See LV 1 T for information about rated currents for ambient temperatures >40 °C.Ambient temperature 40 °C Ambient temperature 50 °CSize DT Order No.Price per PUPU (UNIT, SET, M)PS*PG Weightper PU approx.Rated opera-tional current I e Rated output of three-phase induction motors for rated operational voltage U e Rated opera-tional currentI e Rated output of three-phase induction motors for rated operational voltage U e115 V 230 V 400 V 500 V 115 V 200 V 230 V 460 V 575 V AkWkWkWkWAhphphphphpkg12.5--3 5.5--11--337.5--S0 B 3RW31 24-1CB141 1 unit 1310.46816--47.5--14--3310--S0 B 3RW31 25-1CB141 1 unit 1310.47525-- 5.511--21--5515--S0B3RW31 26-1CB141 1 unit 1310.46412.5------7.511------7.510S0 B 3RW31 24-1CB151 1 unit 1310.46716------1114------1010S0 B 3RW31 25-1CB151 1 unit 1310.47625------1521------1520S0B3RW31 26-1CB151 1 unit 1310.47525 2.24----21 1.533----S0 A 3RW30 26-1AA121 1 unit 1310.439383 5.5----32255----S2 B 3RW30 35-1AA121 1 unit 1310.689755.511----6451010----S3B3RW30 45-1AA121 1 unit 1311.393*You can order this quantity or a multiple thereof.6Accessories1)With internal soft starter power supply.Forsoft startersSize Version DT Order No.Priceper PUPU(UNIT,SET, M)PS*PG Weightper PUapprox.Type kg3RW39 26-8A3RW39 36-8A3RW3 . 2.S0To increase switching frequencyand for device mounting in posi-tions different from the normal posi-tion.The fan is snapped into the enclo-sure from below.During operation, (control signalinput "IN" at potential A1), the fan isrunning. After a stop, the fan contin-ues to run for about another 60 min-utes.}3RW39 26-8A1 1 unit1310.008 3RW30 3.and3RW30 4.S2S3}3RW39 36-8A1 1 unit1310.030CoversTerminal covers for box terminals3RT19 36-4EA23RW30 3.S2Additional touch protection to befitted at the box terminals(2 units required per device)}3RT19 36-4EA21 1 unit1010.016 3RW30 4.S3}3RT19 46-4EA21 1 unit1010.023Terminal covers for cable lugs and bar connections3RT19 46-4EA13RW30 4.S3For complying with the phaseclearances and as touch protec-tion if box terminal is removed(2 units required per contactor)}3RT19 46-4EA11 1 unit1010.037Version FunctionalityFunctionsUse DT Order No.Priceper PUPU(UNIT,SET, M)PS*PG Weightper PUapprox.kg Sealable caps Forsecuringagainstunauthorized adjust-ment of setting knobsFor deviceswith 1 or2 COcontacts}3RP1 9021 5 units1010.004Push-in lugsfor screw mountingFor deviceswith 1 or2 COcontacts}3RP1 903110 units1010.002*You can order this quantity or a multiple thereof.6/8Siemens LV 1 · 20066/9Siemens LV 1 · 20066Note:The covers and connection modules listed here are also used for load feeders (3RV motor starter protector + 3RT contactor). For further technical specifications see Controls –> Contactors and Contactor Assemblies.For fuseless load feeders with size S00 soft starter, the link module has an integrated conductor routing.1)Computer labeling system for individual labeling of device labeling platesavailable from:murrplastik Systemtechnik GmbHFor soft starters Size Version DT Order No.Price per PUPU (UNIT, SET, M)PS*PGWeight per PU approx.Typekg3RA19 11-1A3RA19 21-1A3RA19 31-1AElectrical and mechanical linkbetween motor starter protector and soft starter.Single unit packaging 3RW30 1..S00 }3RA19 11-1AA001 1 unit 1010.0273RW30 2..S0 }3RA19 21-1AA001 1 unit 1010.0373RW30 3..S2 }3RA19 31-1AA001 1 unit 1010.0423RW30 4..S3 }3RA19 41-1AA001 1 unit 1010.090Multi-packs 3RW30 1..S00 }3RA19 11-1A 110 units 1010.0193RW30 2..S0 }3RA19 21-1A 110 units 1010.0283RW30 3..S2 }3RA19 31-1A 1 5 units 1010.0333RW30 4..S3}3RA19 41-1A15 units1010.072*You can order this quantity or a multiple thereof.6/10Siemens LV 1 · 200661)Without connectors for data and auxiliary power (yellow and black).2)With one connector each for data and auxiliary power (yellow and red).For busbar accessories, see SIVACON Switchgear,Distribution Systems and Cabinets –> 8US Busbar Systems.For soft starters Version DT Order No.Price per PUPU (UNIT, SET, M)PS*PGWeight per PU approx.Typekg3RK14 00-1KG01-0AA13RK14 00-1MG01-0AA1AS-Interface load feeder modulesFor standard rail mounting sizes S00 and S0. For mounting onto 40 mm or 60 mm busbar systems and SIRIUS stan-dard mounting rail adapters the matching support is required (see 3RK1 901-3GA00); the AS-Interface connectors for the data and auxiliary power cable (yellow and black) must be ordered separately (see 3RK1 901-0.A00)Rated opera-tional voltage U e2 inputs / 1 output 24 V DC 1)}3RK1 400-1KG01-0AA11 1 unit 1210.0974 inputs / 2 outputs A 3RK1 400-1MG01-0AA11 1 unit 1210.1002 inputs / 1 relay output 120/230 V AC 2)C3RK1 402-3KG02-0AA11 1 unit 1210.1243 inputs / 2 relay outputsB3RK1 402-3LG02-0AA111 unit 1210.143Manuals for AS-Interface load feeder modules German, English }3RK1 701-2GB00-0AA01 1 unit 1920.197French, ItalianA 3RK1 701-2HB00-0AA01 1 unit 1920.196Supports for AS-Interface load feeder modulesWidthFor mounting onto 3RA19 22-1A SIRIUS standard mounting rail adapter45 mmB3RK1 901-3GA0011 unit 1210.048Support with mounted power connector couplingPower connector sets 5-pole, 2.5 mm 2(1 package = 5 connec-tors and 5 couplings)C 3RK1 901-0EA001 5 sets 1210.1113RK19 01-0NA003RK19 01-0PA00AS-Interface connectors for data and auxiliary supply cablesColorWith insulation displace-ment terminals for 2 x (0.5 to 0.75 mm 2) flexible leadYellow C 3RK1 901-0NA001 5 units 1210.015BlackC3RK1 901-0PA001 5 units 1210.0153RA19 223RW30 1.Standard mounting railadapter for mechanical mounting of motor starter protector and contactor; can be snapped onto standard mounting rail or for screw mounting, suit-able for size S00}3RA19 22-1A1 5 units 1010.095Surge suppressors3TX7 462-3.RC elementsRated opera-tional voltage U eFor lateral snapping onto auxiliary switch or 35 mm standard mounting rail127 ... 240 V AC A 3TX7 462-3T 1 1 unit 1010.081*You can order this quantity or a multiple thereof.6/11Siemens LV 1 · 20066■More informationConfigurationThe 3RW solid-state motor controllers are designed for easy starting conditions. In the event of deviating conditions or in-creased switching frequency, it may be necessary to choose a larger device. For accurate dimensioning, use the Win-Soft Starter selection and simulation program.If necessary, an overload relay for heavy-starting must be se-lected where long starting times are involved. PTC sensors are recommended. This also applies for the smooth ramp-down be-cause during the ramp-down time an additional current loading applies in contrast to free ramp-down.In the motor feeder between the SIRIUS 3RW soft starter and the motor, no capacitive elements are permitted (e.g.no reactive-power compensation equipment). In addition, neither static sys-tems for reactive-power compensation nor dynamic PFC (Power Factor Correction) must be operated in parallel during starting and ramp-down of the soft starter. This is important to prevent faults arising on the compensation equipment and/or the soft starter.All elements of the main circuit (such as fuses, controls and over-load relays) should be dimensioned for direct starting, following the local short-circuit conditions. Fuses, switching devices and overload relays must be ordered separately. Please observe the maximum switching frequencies specified in the technical specifications.Power electronics circuit diagram 1)Status graphs1)Circuit diagram applies to sizes S0 and S2;for size S00, phase L3 is bridged;for size S3, phase L2 is bridged.Control with a PLCWhen a 3RW30 is operated with a triac output or thyristor output, the leakage current at the PLC output should be <1mA be-cause otherwise the 3RW30 will interpret the resultant voltage drop at the input as an "On command". As a corrective measure for PLC outputs with a higher leakage current, an RC element with >100nF and 220W can be connected in series between "IN1" and terminal "A2" of the 3RW30 (Order No.: 3TX7 462-3T see Selection and Ordering Data).Win-Soft Starter selection and simulation programWith this software, you can simulate and select all Siemens soft starters, taking into account various parameters such as mains properties, motor and load data, and special application requirements.The software is a valuable tool, which makes complicated, lengthy manual calculations for determining the required soft starters superfluous.You can order the CD-ROM under the following order number:Order No.: E20001-D1020-P302-V2-7400.You can find more information on the Internet at:/sanftstarter3RW31。
3RW22用户指导手册
4 SIKOSTART 3RW22系列电动机软起动器的功能 .................................... 4/1 4.1 起动和停车控制功能 ....................................................................... 4/1 4.2 欠负载情况下的节能运行 ................................................................ 4/7 4.3 恒速连续运行方式 ........................................................................... 4/8 4.4 保护与控制 ...................................................................................... 4/9
起动电流峰值的减小,可以使总的电费降低。总之, SIKOSTART® 电动机电子控制器有助于你在各种使用 情况下节省费用。
避免高起动转矩和起动电流峰值的办法,可以通过降低 电动机起动时加在其定子上端电压的措施达到。
SIKOSTART 3RW22电动机电子控制器就是一种利用微 处理器技术的电动机电压三相可控硅相位控制装置。
1/1
SIKOSTART
应用典型示例
2 应用典型示例
皮带输送机、升降机、电动扶梯类工作机械:
2
负载特征:M=常数
在整个速度范围内,负载力矩为恒定不变(见图2.1 ~ 2. 3)。另外,要求有一个起动转矩推力。属于这类负载物 征的工作机械.
软起动器操作手册
软起动器操作手册软起动器操作手册一、设备介绍软起动器是一种集电机软起动、软停车、轻载节能和多种保护功能于一体的新型电机控制装置。
其操作使用需要一定的专业知识和技能,为了确保软起动器的正常运行和延长设备寿命,建议用户严格按照操作手册进行操作。
二、操作步骤1、打开软起动器的外壳保护门,将电机及传动部分正确安装并连接好。
2、连接输入电源,将电源线接入软起动器的输入端子。
注意三相电源需要保持平衡,不能出现缺相的情况。
3、连接输出电源,将电动机线接入软起动器的输出端子,注意线的颜色要与电机接线盒的颜色一致。
4、打开软起动器电源开关,此时电源指示灯应显示为亮。
5、调整电机的起动参数,包括初始电压、全电压和加速时间等。
这些参数可以根据电机的具体需求进行调整。
6、关闭外壳保护门,确保其紧密关闭。
7、在起动前应检查电源是否正常,手动检查软起动器的操作是否顺畅。
8、起动电机,观察电机的运行状态和软起动器的显示面板信息。
9、在电机运行过程中,要定期进行维护和检查,确保设备的正常运行。
三、注意事项1、操作过程中应切断电源,防止意外触电。
2、在调整电机参数时,应遵循厂家提供的建议范围,不得随意修改。
3、在安装和维修过程中,应使用厂家指定的工具和备件,不得使用其他替代品。
4、定期清理软起动器内的灰尘和杂物,保持设备清洁。
5、若出现故障,应立即切断电源,并联系专业人员进行维修。
四、常见故障及排除方法1、电机不能起动:检查电源是否正常,检查软起动器输入电源是否缺相,检查电机参数是否设置正确。
2、软起动器显示故障:查看故障代码,根据故障代码查找故障原因,并采取相应措施排除故障。
3、电机运行过程中出现异常声音:检查电机是否负载过大,检查电机参数是否设置正确,检查电机轴承是否损坏。
4、软起动器外壳发热:检查散热是否良好,检查内部元件是否损坏。
五、维护与保养1、定期检查软起动器的外壳保护门是否紧闭,以确保良好的散热性能。
2、定期清理软起动器内部的灰尘和杂物,防止对设备运行产生不良影响。
用于 SIRIUS 3RW44 软起动器的 PROFINET 通信模块 设备手册说明书
工业开关技术SIRIUS用于SIRIUS 3RW44 软起动器的PROFINET 通信模块设备手册Siemens AGSmart Infrastructure Control ProductsWerner-von-Siemens-Str. 48-50 3ZX1012-0RW40-0AK0Ⓟ 02/2020 本公司保留更改的权利Copyright © Siemens AG 2013. 保留所有权利法律资讯警告提示系统为了您的人身安全以及避免财产损失,必须注意本手册中的提示。
人身安全的提示用一个警告三角表示,仅与财产损失有关的提示不带警告三角。
警告提示根据危险等级由高到低如下表示。
危险表示如果不采取相应的小心措施,将会导致死亡或者严重的人身伤害。
警告表示如果不采取相应的小心措施,可能导致死亡或者严重的人身伤害。
小心表示如果不采取相应的小心措施,可能导致轻微的人身伤害。
注意表示如果不采取相应的小心措施,可能导致财产损失。
当出现多个危险等级的情况下,每次总是使用最高等级的警告提示。
如果在某个警告提示中带有警告可能导致人身伤害的警告三角,则可能在该警告提示中另外还附带有可能导致财产损失的警告。
合格的专业人员本文件所属的产品/系统只允许由符合各项工作要求的合格人员进行操作。
其操作必须遵照各自附带的文件说明,特别是其中的安全及警告提示。
由于具备相关培训及经验,合格人员可以察觉本产品/系统的风险,并避免可能的危险。
按规定使用 Siemens 产品请注意下列说明:警告Siemens 产品只允许用于目录和相关技术文件中规定的使用情况。
如果要使用其他公司的产品和组件,必须得到 Siemens 推荐和允许。
正确的运输、储存、组装、装配、安装、调试、操作和维护是产品安全、正常运行的前提。
必须保证允许的环境条件。
必须注意相关文件中的提示。
商标所有带有标记符号 ® 的都是 Siemens AG 的注册商标。
软启动操作使用说明
A-B软启动器操作使用说明一.软启动器的起动方式选择┅┅┅┅┅ 2 二.软启动器的参数查看方法┅┅┅┅┅ 3 三.参数修改┅┅┅┅┅ 5 四.常见故障信息及消除方法┅┅┅┅┅ 5 五.常见故障说明┅┅┅┅┅7 六.常用参数及说明┅┅┅┅┅8 七.软启动器的初次调试┅┅┅┅┅11软启动器使用操作说明一.软启动器的起动方式选择:软启动器的起动方式常用的有以下几种:1.软起动:该方式是最常用的起动方式,电动机可根据参数设定的初始转矩进行起动。
起动加速时间在0—30S之间,由用户自行调节。
起动斜坡加速期间,输出至电机的电压不断上升,当软启动器的控制器检测到电动机已达到额定转速状态,则输出电压将自动切换到全电压。
(若设定的起动时间为30S,在20S的时候如果电动机已达到额定转速,电机端电压已达到全电压,则不必等到30S)2.限流起动:限流起动顾名思义,限制电机的起动电流,该方式为电动机提供一固定电压的降压起动。
限流水平可由用户在电机满载电流的500-600%间调节,限流起动时间0—20S由用户设定。
在起动过程中,当软起动器的控制器检测到电机的额定转速时,输出电压将自动切换成全压输出,这点与软起动方式有些区别:软起动过程电压是无级不断增加的;而限流起动是始终以一固定电压起动的。
3.全压起动:该方式同一般设备的启动相同,一般来说,既然选用了软启动器就不太会选用该方式进行起动。
4.可选择的突跳起动:该起动功能一般是附加于软起动方式或限流起动方式之中,为电动机起动提供一个大提升转矩以克服负载惯性,突跳时间可由用户在0.0—2.0S之间设定。
我厂采用的软起动方式主要有以下两种:1.限流加突跳起动方式:该方式主要用于PVC的水环压缩机、抽风机、鼓风机和排渣泵等设备,因为这些设备的电机容量较大,起动电流较大,其供电线路也较长,采用限流起动,可减少对配电室母线电压的影响,以免造成当大设备启动时,母线压降大,使照明及其他设备失电跳闸的情况发生。
3RW软启动器
13RW软起动器产品目录• 20103RW软起动器Answers for industry.34产品概览5 3RW30 标准型软起动器5 概述6 订货资料8技术参数14 3RW40 标准型软起动器14 概述16 订货资料20技术参数30 3RW44 高性能软起动器30 概述31 订货资料42 技术参数56 选型配置说明59 外形尺寸图63接线示意图SIRIUS 软起动器概览SIRIUS 3RW30SIRIUS 3RW40SIRIUS 3RW44额定电流,40 ºC 时A 3.6 ~ 10612.5 ~ 43229 ~ 1214额定电压V200 ~ 480200 ~ 600200 ~ 690电机功率(400 V,标准接线方式)kW1.1 ~ 55 5.5 ~ 25015 ~ 710电机功率(400 V,内三角接线方式)kW--22 ~ 1200工作温度ºC-25 ~ 60-25 ~ 600 ~ 60软起动/软停止x1)x x电压斜坡x x x起动/停止电压%40 ~ 10040 ~ 10020 ~ 100起动/停止时间S0 ~ 201)0 ~ 200 ~ 360转矩控制--x起动/停止转矩%--10 ~ 100转矩限制%--20 ~ 100斜坡时间s--0 ~ 360内置旁路接触器x x x设备自保护-x x电机过载保护-x x电机热敏电阻保护-x2)x集成远程复位-x3)x可调电流限流功能-x x内三角接线方式--x突跳脉冲--x双向慢速爬行--x泵停止--x4)直流制动--x4) 5)组合制动--x4) 5)电机加热--x通讯--配 PROFIBUS DP(选项)外部显示和操作面板--(选项)状态/测量值显示屏--x故障日志--x事件列表--x零位指示器--x曲线跟踪功能--x6)可自定义的控制输入和输出接点--x参数组数量113参数设置软件(Soft Starter ES)--x晶闸管(可控硅)两相控制两相控制三相控制螺钉型端子x x x弹簧型端子x x xUL/CSA x x xCE 标识x x x重载起动--x4)选型支持Win-Soft Starter,电子选型工具,技术支持:40081042881) 3RW30,仅软起动2)只到 S3(软起动外型尺寸号)规格3)对于 3RW40 2. ~ 3RW40 4.;3RW40 5. ~ 3RW40 7.,为可选4)需要选用更大电流等级的软起动器5)不能在内三角接线方式中使用6) Soft Starter ES 软件的跟踪功能x 提供该功能-无该功能4SIRIUS 3RW30 软起动器通过相角控制来降低电机端电压,平滑地将电压从起动电压软起动升到到电源电压。
SIRIUS软启动器 3RW30,40,44 产品折页
0 1
3RW40 55-■BB 4 3RW40 56-■BB 4 3RW40 73-■BB 4 3RW40 74-■BB 4 3RW40 75-■BB 4 3RW40 76-■BB 4
6 2
3 4
3RW40 2. 45 x 125 x 154 45 x 150 x 154
3RW40 3. 55 x 144 x 170 55 x 144 x 170
软起动器应用选型帮助
应用,常规起动 (Class 10) 泵 热力泵 液压泵 冲床 带式输送机 辊式输送机 螺旋式输送机 自动扶梯 活塞式压缩机 螺杆式压缩机 小型风机 离心式鼓风机 船首推进器
推荐型号
可使用型号
SIRIUS 3RW30
SIRIUS 3RW40
用于高性能应用的软起动器 SIRIUS 3RW44
优点
+ 初始投资相对较低 + 电机起动器中的功率损耗较低 + 具有电气隔离功能,适用于安全应用 + 起动时具有极高转矩,起动速度快
+ 功率损耗相对较低
+ 可避免电流峰值,电网承受的压力较低
+ 起动时的电流和转矩峰值较低
+ 机械起动和降速转矩低,机械磨损小
+ 具有固定的低起动转矩,大多适合软起动 + 起动和停止期间的所有条件均可自由调节
1200 kW(内三角接线方式)的驱动装置 采取创新的转矩控制,并具有可调的限流 功能 • 具有设备过载保护功能 • 无需额外的电机过载继电器,节省空间, 并将接线量降到最低 • 可用 PROFINET 或 PROFIBUS DP 模块进行 改装,实现通信功能 • 通过集成的旁路触点,热损耗大大降低
高机械应力
软启动器说明书
软启动器说明书1 软启动工作原理软启动器电动机的应用 1 软启动器工作原理与主电路软启动器采用三相反并联晶闸管作为调压器,将其接入电源和电动机定子之间。
这种电路如三相全控桥式整流电路,主电路图见图1。
使用软启动器启动电动机时,晶闸管的输出电压逐渐增加,电动机逐渐加速,直到晶闸管全导通,电动机工作在额定电压的机械特性上,实现平滑启动,降低启动电流,避免启动过流跳闸。
待电机达到额定转数时,启动过程结束,软启动器自动用旁路接触器取代已完成任务的晶闸管,为电动机正常运转提供额定电压,以降低晶闸管的热损耗,延长软启动器的使用寿命,提高其工作效率,又使电网避免了谐波污染。
软启动器同时还提供软停车功能,软停车与软启动过程相反,电压逐渐降低,转数逐渐下降到零,避免自由停车引起的转矩冲击。
软启动与软停车的电压曲线见2 软启动器的选用(1)选型:目前市场上常见的软启动器有旁路型、无旁路型、节能型等。
根据负载性质选择不同型号的软启动器。
旁路型:在电动机达到额定转数时,用旁路接触器取代已完成任务的软启动器,降低晶闸管的热损耗,提高其工作效率。
也可以用一台软启动器去启动多台电动机。
无旁路型:晶闸管处于全导通状态,电动机工作于全压方式,忽略电压谐波分量,经常用于短时重复工作的电动机。
节能型:当电动机负荷较轻时,软启动器自动降低施加于电动机定子上的电压,减少电动机电流励磁分量,提高电动机功率因数。
(2)选规格:根据电动机的标称功率,电流负载性质选择启动器,一般软启动器容量稍大于电动机工作电流,还应考虑保护功能是否完备,例如:缺相保护、短路保护、过载保护、逆序保护、过压保护、欠压保护等。
3 Alt48软启动器的特点Alt48软启动器启动时采用专利技术的转矩控制。
转矩斜坡上升更快速,损耗更低。
具有电动机和软启动器综合保护功能,能全时连续检测电机电流,提供电机可靠和完整保护,这种保护功能在启动结束旁路后仍能起作用,这是其它软启动器都不具备的。
西门子 3RW34 电子式软起动器 用户说明书
用户指导手册
1
危险
危险电压 危害生命和重伤身体 或损坏财产 在进行维修工作之前,必须彻底而全部地断开软起动器并将其 接地。在安装、投运或维修软起动器之前,必须阅读和理解这 本使用手册。只允许具有职业资格的人员进行维修工作。在维 修软起动器时使用不允许的零部件或者让无职业资格的人员去 检修软起动器就有可能导致人员死亡、重伤、损坏软起动器或 财产损失。 必须遵守本手册中所述的安全守则以及有关的标准。
1 SIKOSTART 3RW34 软起动器的方框接线图 ............ 6 2 3 相交流制的基本波形 .............................................. 6 3 星形接线时的 3 相位置图 ......................................... 7 4 三角形接线时的 3 相位置图 ...................................... 7 5 电动机的连接 ............................................................ 8 6 电动机在降压时的典型转速 / 转矩 - 特性曲线 ............ 8 7 在软起动与自然制动直至停止运转时,以时 间为函数的电压与转速-特性曲线 ........................... 9 8 在软起动与软制动时的电压和转速特性曲线 ............. 9 9 电感性用电设备的去干扰 ......................................... 16 10 SIKOSTART 的电网连接和电动机连接 .................... 17 11 SIKOSTART 的控制器连接 ...................................... 18 12 装在通风型外壳中“标准接线”电动机的 负载连接 (保护开关或熔断器式隔离开关) ............... 22 13 装在通风型外壳中“标准接线”电动机的 控制线路 (保护开关或熔断器式隔离开关) ............... 23 14 “标准接线”单台电动机在带有桥接接触器时 的负载连接 .............................................................. 24 15 装在通风型外壳中“标准接线”电动机的 控制线路 .................................................................. 25
3RW30 31 电子式软起动器 用户指导手册
45 X 97.5 X 93
表 2:3RW3,规格
规格 S0 5.5 - 11kW 12.5 - 25A 宽 X 高 X 深(mm) 45 X 125 X 119
首先,先施加电源电压以便将旁路继电器 设定在确定的开闭状态。
然后,再激活主回路。
如果不按照本程序进行操作,则电动机会 被无意激活从而会造成人身伤害或造成系 统部件的损坏。
! 注意
3RW3...-1,B1软起动器是作为A类电器制 造的。如果在住宅小区里使用本产品,可能 会产生无线电干扰。
2
3RW3 电子式软起动器
3RW30/31的规格
图 1: 3RU11 过载继电器,规格 S00 至 S3
3RW30 软起动器有 S00,S0,S2 和 S3 四种规格。 3RW31 软起动器只有 S0 一个规格。 下表列出了各个规格的功率范围(所有参数均适用于 UN=400V,环境温度 40C):
规格 S00 1.1 - 4kW
4 附件 .......................................................................................................................... 31
5 组装和连接 .................................................................................................................... 33 5.1 组装 ........................................................................................................................ 33 5.2 连接 ........................................................................................................................ 33 5.3 接线图 .................................................................................................................... 34
中压软启动器使用手册
起动过程结束继电器
测试模式: 可以用到的三种测试模式: 1. 1. 2. 3. 在没有中压接入的条件下,软起动在正确的逻 辑操作下的测试。. 触发测试是在只有控制电压没有主电压的情况 下进行的。 测试环境在对一台 400V 的电动机进行测试, 测试其动力和 4 对 dip 开关。
当投入操作电源, RAM 自动装载从 EEPROM 来得数据和 LCD 显示的参数。 2. 参数可以在键盘上修改 (假如起动器是在一种操 作状态并且 软件锁是打开的 – Dip Switch 8 在开的 位置). 3. 起动参数修改可以在起动过程中,并且会立即 影响操作. 例如: 假如电流的限制设置太低并且电机 没有加速到满速,增加电流限制的设置将立刻改变 起动过程,这样就可以选择最佳的起动特性。 4. 完成调整后,参数应该保存在 EEPROM. 通过按 保存键,LCD 上显示“Store Enable”在每个模式页的 后面都可以保存新的参数。
• • • • • •
光纤连接
释放光纤螺母逆时针方向 ½ 圈. 从插孔中拔离光纤头 25mm 确认光纤头的数目 最大限度的插入光纤头(大约 18mm). 向 逐渐紧固光纤,顺时针方转, ½ 圈
光纤板
光纤板前视图. 光纤板微型开关位于光纤插入连接器 #5 的底部.
电子式电压互感器 (EPT)
Note: 确认连接线按标记好的号进行连接 Input: 输入电源有熔丝连接 Input: Directly connected to H.V. bus bars
注意
本产品的设计满足 IEC 947-4-2 标准对 A 类设备的要求,也满足 EN 50178 标准. 详细信息查看技术特性。
警告
当 NC3S 主电路上电后,其内部组件和 P.C.B 电路板就会带电。这种电压特别危险,如果 接触到就会引起死亡或严重损害。 当 NC3S 主电路上电后,即使没有连接控制电压,电机处于停止状态,在起动器的输出端 和电机端子上,主电路电压也会以全压形式出现。 软起动器必须可靠接地以确保可靠操作、安全性和防止意外伤害。 检查功率因数电容器不要接到软起动器的输出端,而要确保其接到母线接触器之后。.
软起动器使用说明书
控制柜具有降低起动电流对电网的冲击,满足电网波动要求,降 低水泵起动冲击转矩,延长电机及水泵的使用寿命,具备电机软停功 能,消除水泵停泵时的水锤现象等特点,是水泵控制的理想产品。
2KM
a)
说明
1 、一台运行,一备用,运行故障,备用台自动投入。 2、故障自复位。 3 、 SR2选主用信号。 4、 SRl 打到自动,一用一备运行(软起动功能码请改为三线
控制): SRl 打到,分散单台键盘控制(软起动功能码请改 为二控制 SRl 打到切除,均拒动,供检修用)。
争 -380V
QE 了
6 结构特点
软起动器具有如下特点: a) 采用十六位单片机全数字自动控制; 的起动转矩电流、电压、时间可按负载不同灵活设定,以取得
最住的电流冲击和最住的转矩控制特性; c) 为电动机提供了平滑渐进的起动过程,减少起动电流对电网
的冲击,降低设备的振动和噪声,延长了机械传动的使用寿 命,并改善了工人的劳动环境;
8.1 概述 YCR1 型消防水泵控制柜(以下简称控制柜)是以先进的智能化数字
式电动机软起动器作为主要控制器件组成的,用于两台消防水泵一台 运行,一台备用的起动控制设备。当运行的消防水泵故障停机后,则 备用消防水泵自动投入运行,保证消防水泵的可靠供水。
控制柜能减少起动电流对电网的冲击,降低电机及水泵的故障 率,延长电机及水泵的使用寿命;具备电机软停车功能,以消除水 泵时的水锤现象,是消防水泵控制理想产品。
表1
Siemens SIRIUS 软启动器3RW50产品说明书
3RW5076-6AB14
SIRIUS soft starter 200-480 V 470 A, 110-250 V AC Screw terminals Analog output
product brand name product category product designation product type designation manufacturer's article number
● of standard HMI module usable ● of high feature HMI module usable ● of communication module PROFINET standard usable ● of communication module PROFIBUS usable ● of communication module Modbus TCP usable ● of communication module Modbus RTU usable ● of communication module Ethernet/IP ● of circuit breaker usable at 400 V ● of circuit breaker usable at 500 V ● of the gG fuse usable up to 690 V ● of full range R fuse link for semiconductor protection usable up to 690 V ● of back-up R fuse link for semiconductor protection usable up to 690 V ● of line contactor usable up to 480 V ● of line contactor usable up to 690 V General technical data starting voltage [%] stopping voltage [%] start-up ramp time of soft starter ramp-down time of soft starter current limiting value [%] adjustable accuracy class acc. to IEC 61557-12 certificate of suitability ● CE marking ● UL approval ● CSA approval product component ● HMI-High Feature ● is supported HMI-Standard ● is supported HMI-High Feature product feature integrated bypass contact system number of controlled phases
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
1
3RW3 电子式软起动器
警告提示
! 警告!
本装置在出厂前已在工厂经过测试,各工 作性能合格。但是,在运输过程中,可能会 发生不属我们造成的各种应力。
出于这种原因,主回路中的旁路继电器可 能会处于非确定开闭状态。
为了整个安全期间,在 SIRIUS 系列软起动 器调试过程中或在对其更换后,请务必按 下列程序进行操作:
6 - 9A 宽 X 高 X 深(mm)
45 X 97.5 X 93
表 2:3RW3,规格
规格 S0 5.5 - 11kW 12.5 - 25A 宽 X 高 X 深(mm) 45 X 125 X 119
“在使用中开断”
3RW3 软起动器可用作于“在使用中开断”的开关。根据 DIN VDE 0100 第 460 部分 规定: 每条电路必须配备一只能在使用中开断的开关,即能独立于其它部件进行开关。用作 在使用中开断的开关无须开断一条电路中的所有带电导体。
“隔 离”
按 DIN VDE0100 第 460 部分和 EN60 947-1 标准规定,软起动器可以不要求满足“隔 离”要求。 但是,每条电路必须能够与电源的带电导体隔离。 对于多组电路,如果操作条件允许,可用一台公共的装置来隔离。带有隔离功能的各 类装置在断开位置时必须有一个相对的隔离间距和一个能够指示动触头位置的指示装 置。
6 外形尺寸图 ....................................................................................................................... 37
7 技术参数 .......................................................................................................................... 38 7.1 控制部分电子元器件的参数 .................................................................................... 38 7.2 电源部分电子元器件参数 ........................................................................................ 39 7.3 安装海拔高度 .......................................................................................................... 40 7.4 IEC参数 .................................................................................................................. 41 7.5 NEMA参数 ............................................................................................................. 42 7.6 短路保护和熔断器协调配合 .................................................................................... 43
3RW30/31 电子式软起动器
用户指导手册
目录
1 规则 / 规范 / 认可 ................................................................................................................ 1
2 装置的描述
SIRIUS 3RW3 软起动器系 SIRIUS 3R 模块系统的部分。 它们均能与 SIRIUS 3R 其它开关装置兼容。可能的组合包含: 3RW3 软起动器 + 3RV 断路器 3RW3 软起动器 + 3RU/3RB 过载继电器 + 3RT 接触器 用于接触器 / 断路器组合的连接模块就可用于本目的(参见 8.3.2 条“装配指南”)。
3 应用与使用 ....................................................................................................................... 15 3.1 应用领域和选用准则 ............................................................................................... 15 3.2 组装规范 ................................................................................................................. 15 3.3 综述表: 补偿系数 ................................................................................................. 18 3.3.1 独立式3RW30/31软起动器 ....................................................................... 18 3.3.2 与3RV1断路器组合的3RW30/31软起动器 ................................................ 19 3.3.3 3RT接触器与3RU1热过载继电器以及3RW3软起动器的组合 .................... 21 3.3.4 3RT接触器与3RB10电子式过载继电器和3RW3软起动器的组合 .............. 23 3.4 举例电路 ................................................................................................................. 26 3.5 调试 ........................................................................................................................ 27 3.6 动作信息及故障诊断 ............................................................................................... 29 3.7 时间图 .................................................................................................................... 30
3RW30/31的规格
图 1: 3RU11 过载继电器,规格 S00 至 S3
3RW30 软起动器有 S00,S0,S2 和 S3 四种规格。 3RW31 软起动器只有 S0 一个规格。 下表列出了各个规格的功率范围(所有参数均适用于 UN=400V,环境温度 40C):
规格 S00 1.1 - 4kW
3RW3 电子式软起动器
1 规则 / 规范 / 认可
3RW3 电子式软起动器已通过 UL 和 CSA 认可。
UL / CSA 外壳防护等级 标准外形导轨 电子式软起动器 冲击危险保护
EMC 一般分辨率 控制器和开关元件 Gost (苏联)
CTic
表 1:标准与认证,3RW3
UL 508 DIN EN DIN EN 50 022 IEC 60947 - 4 - 2 IEC 60947 - 1 和 DIN 40050 IEC 60801 - 4 - 2 (草案) DIN EN 602 69 - 1A1 DIN EN 602 69 - 1A1 按 Gost 标准通过认可 澳大利亚 EMC 合格标志(相当于 CE 标志)
4 附件 .......................................................................................................................... 31
5 组装和连接 .................................................................................................................... 33 5.1 组装 ........................................................................................................................ 33 5.2 连接 ........................................................................................................................ 33 ቤተ መጻሕፍቲ ባይዱ.3 接线图 .................................................................................................................... 34