6相控制器调试说明(精)
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
ADD-32 FIELD SERVICE POWER UP AND START UP PROCEDURES CUSTOMER NAME - LOCATION:
MACHINE NAME:
SECTION NAME:
MOTOR CHECKOUT
2. Check motor for obstructions and loose connections.
3. Verify interior of motor is clean and dry.
4. Disconnect motor field and armature wiring at the ADDvantage-32TM.
5. Check motor field and armature for open circuits by placing an ohmmeter across each set of wires.
Record the measured field ohms.
Field Ohms Measured = _________ Ohms
1. Lock out all power to the ADDvantage-3
2.
********************************************************************** *
C A U T I O N
Damage to the ADDvantage-32 will occur if the motor is not disconnected from the drive during the megger testing.
********************************************************************** *
6. Use a high voltage Meg Ohm Meter (Megger) to check for motor field-to-ground faults and motor
armature-to-ground faults. In addition, megger between the motor field and armature windings.
7. Reconnect motor wiring to the drive.
8. Record the motor nameplate data:
Armature Volts
Armature Amps
Field Amps
Field Volts
Field Ohms
Base Speed
Max Speed _____________Vdc _____________Amps ______/_______Amps
_____________Vdc _____________Ohms _____________RPM _____________RPM Horsepower
TRW
Rev: 01/31/06 ____________HP 1
DRIVE CHECKOUT
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer 1. Lock out all power to the ADDvantage-32TM including power sources which may originate from outside of the drive cabinet.
2. Inspect the drive for physical damage, loose connections, loose parts and any metal shavings left from
the installation.
3. Using an ohmmeter and clip lead, ohm out all external drive wiring.
4. Set jumpers on control transformer T1 to the correct incoming AC line voltage (240/480 VAC). Refer to
Figure 1 below.
Figure 1: Control XFMR T1 Jumper Configuration
5. Verify there are not any short circuits on primary or secondary of the isolation transformer supplying
power to the drive. For Delta/Wye transformers, the neutral of the wye secondary must be connected to a good plant earth ground.
6. Verify that a good plant earth ground is connected to GND stud on outside of drive base assembly.
7. With the drive circuit breaker off, measure the incoming power at the top of the breaker for the proper voltage and phase to phase balance.
Phase A-B
Phase B-C
Phase A-C
Phase A-GND
Phase B-GND
Phase C-GND = = = = = = __________VAC __________VAC __________VAC
__________VAC __________VAC __________VAC
TRW
Rev: 01/31/06 2
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
8. Verify power is off and locked out. Connect Switch Box. Terminate E-STOP wires marked 19 and 20 to
TB1 (19) and (20) or in series with other E-Stop pushbuttons already wired. Connect Switch Box Reset wires marked 17 and 18 to TB1 (17) and (18).
9. Have a millwright lock the motor rotor. Uncouple motor only if there are felts or machinery sensitive to
backward motion.
POWER UP DRIVE
1. Remove the power lockout and apply power to drive. Drive will show USR FAULT 6 indicating drive is
loaded with default parameters. Go to the DRIVE CONFIGURE menu and set parameter Y030:USR FAULT 6 to D087:ZERO BIT. Reset drive via Access Codes menu or by power cycle. Verify that drive display shows OPERATE and not a fault message. Verify there is not any red fault LED’s illuminated.
2. Go to the ACCESS CODES submenu, E00//7:SWR VERSION and confirm the displayed software part /0
number and version is what you desire to use.
If the displayed software P/N and/or version are not correct, use Flashzap or Hyper Terminal to download the correct application software P/N and version.
Software P/N _____________ VER ____________
3. Default drive via Access Codes menu. Go to the ACCESS CODES menu and set ACCESS CAL,
ACCESS CON, ACCESS UNTS and ACCESS TBLS to YES-NONVOLATILE.
4. Go to DRIVE CALIBRA TE menu and manually enter the drive’s IP Address, IP Mask Address and IP
Gateway Address settings.
5. Verify your laptop’s Internet Protocol (TCP/IP) settings under Local Area Connection properties are
configured for the drive’s network. Connect laptop to network Switch or to the Copper port (Crossover Cable required) on drive’s ESBX board.
6. Use Addapt 2000 to download all engineered drive parameters from a disk file.
Y031:USR FAULT 7 to
D087:ZERO BIT.
8. Use Addapt 2000 to set/verify the following parameters:
X000: I/O V-REF = (Measured on Micro Board)
X001: MOTOR IARM = ___________%
X002: MOTOR IFLD = ___________%
X050: FLD RESIST = ___________ ohms (Set to the nameplate value)
X053: Z-C Correct = (60Hz vs 50Hz power)
X057: IARM R-LIM =
Y000: DRIVE PN = _____________ (Set to the nameplate P/N) stY001: BRG SELFTST =
TRW
Rev: 01/31/06 3
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
Y002: 4Q OPERATE =
9. Reset drive in ACCESS CODES menu or by a drive power cycle.
If this drive is not an AFM, proceed to the Armature Current Loop Self Tune section of procedures.
AVTRON FIRING MODULE (AFM) CHECKOUT
If drive is an Avtron Firing Module (AFM), the following must be done to verify proper CT Scaling and
firing of all 6 SCR’s for each bridge:
1. Verify the correct part number and polarity of all current transformer assemblies. CT P/N =
2. Set the following AFM parameters:
X005: RBRDG RATIO = _____________
X061: BRIDGE SIZE = _____________ Amps (Set to amp rating of Forward SCR Bridges)
X062: ARM CT OUT = CT Primary Turns x Burden Resistor
3. Verify that CT’s are correctly wired to Avtron’s feedback board as shown in the 2- CT Phasing method
below. Burden resistors should be sized so that 2 volts feedback = 300% motor current. TRW
Rev: 01/31/06 4
ADDvantage-32
AC to DC Power Converter
Software Part Number 694012.V15 and Up
Optimized for Blueprint Room Printer
4. Configure the drive as an open loop voltage regulator by setting the following parameters:
X001: MOTOR Iarm = Leave at engineered value as scaled for motor _____________ X044: Iarm Contin = 100 _____________ X049: ARM Resist = 1 _____________
X057: IARM R-LIM = 15 _____________
Y000: DRIVE PN Y001: BRG SELFTST Y002: 4Q OPERATE Y004: FIELD CNTL Y0017: RUN INPUT Y020: IARM PI CTL Y021: IARM FFWD
= AFM = Disabled = Enable = Disable = D096: LOC BIT 1 = Disable = Enable
_____________ _____________ _____________ _____________ _____________
_____________ _____________
C033: POS CUR LMT = +10 C034: NEG CUR LMT = +10 C037: ALT TRQ STP = 0.0
_____________ _____________ _____________
P028: ALT TRQ IN = C037:ALT TRQ STP _____________ P141: SPD LP EN =
D087:ZERO BIT _____________ P142: ALT TRQ EN = D086:ONE BIT
_____________
5. RESET AFM.
6. Power down and disconnect ALL gate firing modules.
7. Install oscilloscope across “IARM” and “ACOM” on Micro board. Install a DVM across A1 and A2
armature bridge outputs. Install a DVM across armature shunt if available or install Clamp
On
TRW
Rev: 01/31/06
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
Ampmeter on one of the armature cables.
8. Confirm that rotor of motor is locked or that brakes are set. Determine if any PLC / Relay logic needs
forced or jumpered to allow picking up the Motor Contactor, picking up any DB Contactor or keeping the brakes set.
********************************************************************** *
C A U T I O N
Do not keep a significant amount of armature current on a stalled motor for longer than 5 seconds.
********************************************************************** *
9. Create an Addapt Realtime Screen to monitor A023:IARM SETPT, A003:I ARM PCNT and
A016:ARM ALPHA. Using Realtime Screen, turn on LOC BIT 1 (Run) and slowly increase parameter C037: ALT TRQ STP (Ref) in the positive direction. Monitor parameter A016: ARM ALPHA and observe that firing angle as the ALT TRQ STP value increases. It may be necessary to increase the current limits. You should have a full control range from 120 degrees to 30 degrees firing angle.
10. Change parameter C037: ALT TRQ STP to –10.0 and repeat step 9. Results must be the same as
obtained in step 9. Change C037: ALT TRQ STP to 0.0.
11. Connect SCR gate leads for one Forward Bridge, leave other Bridges disconnected. Note this will not be
possible if using the Bush SCR Firing Adaptor board.
12. Power up the AFM and Bridges. With C037: ALT TRQ STP (Ref) = 0.0, turn on LOC BIT 1 and
slowly increase the value of C037: ALT TRQ STP until you observe pulses on scope. You should span as shown below. As reference is increased, amplitude of pulses will increase. Note there is a 5x gain between the CT burden resistor and the IARM test point.
If 2 pulses are of greater magnitude than the other four, check CT wiring into feedback board as CT’s should be connected in parallel, not series.
If oscilloscope were connected across one of the burden resistors, the waveform should look like the
TRW
Rev: 01/31/06 6
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
13. If all pulses observed on scope are negative instead of positive as shown above, reverse all CT polarities.
If the CT leads are difficult to reach, switch the wires for all CTs at J1 of the SCR Firing Adapter.
14. If the voltage waveform observed on scope has some positive segments and some negative segments as
shown in Figure below, verify that all CT’s have their dot facing in the same direction with respect to current flow. Check CT wiring at Feedback board.
15. Increase parameter C037: ALT TRQ STP to 30.0. Verify A023:IARM SETPT = 30.0. Document DVM
reading across armature shunt or on Clamp On Ampmeter. Verify that A003:I ARM PCNT = 30.0. Verify that measured current across armature shunt or Clamp On Ammeter equals 30% of the motors nameplate rating.
16. Turn LOC BIT 1 off and set C037: ALT TRQ STP = 0.0. Power down AFM and all bridges. Disconnect
the SCR Gate leads for the Forward Bridge and connect SCR Gate leads for the Reverse Bridge if applicable.
17. Repeat steps 12 thru 15 above but now adjust C037: ALT TRQ STP using a negative value. You should
18. Set all parameters changed in step 4 above back to their original values.
TRW
Rev: 01/31/06 7
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
ARMATURE CURRENT LOOP SELF TUNE
Motors containing series fields should have the series field disconnected or bypassed. Series fields are not typically used with regenerative drives and may
cause self tuning failure if connected. Bypassing the series field should only result
in a 2-5% increase in armature current to make up for the lost torque.
1. Test the Switchbox E-STOP and E-STOP RESET pushbuttons. Verify EMERG STOP OK and DRIVE
READY LEDS on drive are illuminated. Verify parameter D017:ABC ROTATE = ONE BIT. Reverse incoming phase A and C if D017:ABC ROTATE = ZERO BIT. 2. Verify rotor of motor is locked or brake is set. Go to the ACCESS CODES submenu, E006 SELF
TUNE, and press the right arrow key. While someone is watching the motor, use an Addapt Realtime Screen to turn on RUN (LOC BIT 1). The DC contactor should pick up and self tuning of the armature current loop begins.
3. When Self Tune test is complete, drive will fault and display shows “Tune Pass”. Turn off LOC BIT 1
(RUN). Clear the drive fault and FIFO. If Tune Fail is displayed, adjust X049: ARM RESIST or X053: Z-C CORRECT = -1000.0 to be closer to actual values. If ICONT > ILIM faults occur on AFM’s or Panel Drives during self tune test, swap the polarity of Iarm feedback at the BIB and / or verify the CT's are installed (dot) and wired with the same polarity. Repeat step 2.
4. Record the following tuning parameters. Verify parameters have changed from their default values. X044: IARM CONTIN = _______________ (30.0)
X049: ARM RESIST = _______________ (0.01)
X053: Z-C CORRECT = _______________ (-600.0)
X054: IARM PGAIN = _______________ (0.20)
X055: IARM IGAIN = _______________ (0.20)
FIELD LOOP SCALING & TUNING
1. Install a clamp on DC ammeter on one of the motor field wires at the drive TB1 (1)
or (2) for 510 ADC
drives and below or at TB1 (-) or (+) for 540 ADC drives and above. Note ammeter polarity requirements.
3. Reset the drive in ACCESS CODES or by a drive power cycle.
4. Verify that A005: I FLD PCNT = 100.0%. If it is not equal to 100.0, adjust X003: MFLD % SCALE in
DRIVE CALIBRATE as required. Reference ADD-32 Manual Appendix for
MFLD %SCALE adjustment.
TRW
Rev: 01/31/06 8
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
5. Adjust X002: MOTOR IFLD so the ammeter is equal to the motor field nameplate value if the field
windings are connected in series and double the nameplate value if connected in parallel.
6. Observe A006: I FLD AMP and adjust X004: MFLD ASCALE in DRIVE CALIBRATE if required so
that displayed I FLD AMP matches the ammeter. Reference ADD-32 Manual Appendix for MFLD ASCALE adjustment. Document the following scaling parameters:
X002: MOTOR IFLD
X003: MFLD %SCALE
X004: MFLD ASCALE = _______________ = _______________ = _______________ 7. Observe A017:FLD ALPHA from the OPERATE submenu DRIVE ANALOG. If the value is less than
40 degrees, try changing transformer tap to increase Line Volts into Field Supply. You may be able to get a minimal increase in Field Alpha by swapping the incoming 3-phase power at L1 and L3 on drive. Verify that the FLD ALPHA value has increased by some amount.
Vdc = 0.9*Vac*cos(field alpha)
A017:FIELD ALPHA at 100% IFLD PCNT = ___________ Deg
8. Check scaling of any Analog meters for Field Current and / or Field Voltage.
9. If this drive’s motor is to be field weakened, it will be necessary to tune the Field Loop. It is normal to
only tune X066:IFLD PGAIN, leaving X067:IFLD IGAIN at default. PGAIN values of 5.0 or 7.0 are typical. If ADD-32 Field Supply is used along with an external Field Supply (for parallel motor applications), it is important that ADD-32 Field Loop response be tuned to match response of external Field Supply.
Use Addapt Realtime Screen and setup Signal Analyzer to monitor / record A021:IFLD CMD. A005:I FLD PCNT and A013:FLD VOLTS. Setup Signal Analyzer for Analog trigger using Rate = 1 or 1.5. Step change can be achieved by toggling C038:FLD MAX LMT from 75 to 100. Adjust X066:IFLD PGAIN for best response with no overshoot and no instability at steady state.
X066:IFLD PGAIN = _____________
X067:IFLD IGAIN = _____________
TRW
Rev: 01/31/06 9
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
X057: IARM R-LIM Y001: BRG SELFTST
Y017: RUN INPUT
P024: MAX LIM REF
P025: MIN LIM REF
P030: MAX I LIMIT
P031: MIN I LIMIT C033: POS CUR LMT
C034: NEG CUR LMT
C038:FLD MAX LMT 10 Use the ADDAPT 2000 or drive keypad/display to set the following parameters back to their engineered state and/or default value if changed in earlier steps:
11. Upload all drive parameters and save to a disk file. Record the file name for future reference.
File Name = _____________ PC Name =
12. Remove drive power and lock out. Have a millwright unlock the rotor and couple the motor if there are
no felts or machinery sensitive to backward motion.
MOTOR ROTATION AND SPEED FEEDBACK CHECKS
1. Remove power lockout and apply drive power.
2. Use ADDAPT 2000 PC on line edit mode to set up the following drive parameters for running motor in
CEMF control.
C004:RUN SPEED
TRW
Rev: 01/31/06
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
C006: SPD DWN RATE C007: SPD UP RATE C013: MAX SPEED C015: STOP RATE C017: ANLG SCALE C031: SPD I GAIN C033: POS CUR LMT C034: NEG CUR LMT C042: BREAK SPD P001: RUN INP P131: SPD FDBK SE Y017: RUN INPUT = ________ = ________ = ________ = ________ Base Armature Volts x G.R.
3. Reset the drive in ACCESS CODES or by a drive power cycle. Press the E-STOP RESET pushbutton.
4. Verify the motor, gearbox, and driven rolls are free of loose debris and people. While an operator is
observing motor, turn on LOC BIT 1 (drive run) using Addapt Realtime Screen. Set
C004:RUN SPEED to about 10% of rated base motor speed and observe A065:SPD REF. Verify A000:FIL SPEED = A065:SPD REF. Verify the motor rotation will give the correct roll rotation. Reverse the two motor field wires if motor runs backwards. 5. After verifying motor control, stop motor if running uncoupled. Remove and lock out drive power.
Have millwright couple motor to the roll if it was not coupled in step 12 above.
Apply drive power and run motor again at 10% of rated base motor speed. Verify that A012: ARM VOLTS is correct for the present speed and motor armature volt rating. While motor is running at 10% rated speed, verify that A034: SPEED IN 1 displays a positive polarity and the correct value for the motor speed. Have the machine operator confirm the rolls are turning in the correct direction.
If positive polarity of speed feedback is observed and roll rotation is incorrect, then:
a.
b.
c.
If negative polarity of speed feedback is observed and roll rotation is correct, then:
a.
b. Stop motor. Reverse the tach phase A and B wires at Maxi System board as described in “c”
above. Reverse tach phase A and B wires at the Maxi System board J7 (17) and (20) if tach 1 is used and/or J7 (24) and (27) for tach 2. If tach compliments are used, reverse tach wires between J7 (17) and (20) and also J7 (18) and (21). Reverse the two motor field wires at the drive TB1 (1) and (2) or TB1 (-) and (+). Stop motor. Remove and lock out drive power.
TRW
Rev: 01/31/06 11
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer If negative polarity of speed feedback is observed and roll rotation is incorrect, then:
a.
b.
6. If tach / field wiring changes were made, run motor again at 10% rated speed. Confirm roll rotation is
correct and that A034: SPEED IN 1 displays the correct value as a positive value.
Stop motor. Remove and lock out drive power. Reverse the two motor field wires at the drive TB1 (1) and (2) or TB1 (-) and (+).
SPEED LOOP TUNING
1. Use the ADDAPT PC on line edit mode to set up the drive for running motor in speed control. Set the
following parameters:
C009:AUX SPD ST1 = __________________ (tuning speed step change)
C033: POS CUR LMT C034: NEG CUR LMT P005: AUX SPD IN1 P125: AUX SPD EN1 P131: SPD FDBK SE P136: SPD FIL SEL X008: TACH 1 GRAT =
_____________
X009: TACH 1 RDIA = _____________ (Entered in Process Units Feet, Meters
or .31831)
X010: TACH 1 EPR = _____________
RESET ADD-32
2. Verify that tach alignment meets Avtron’s specifications as documented in Pulse Generator Instruction
Sheets. If tach couplings are used, verify they are the equivalent to Thomas Minature Flexible couplings that are rated for Zero Backlash.
3. Press the E-STOP reset pushbutton. Turn on LOC BIT 1 (RUN) and slowly increase C004:RUN
SPEED to 75% of base process speed as observed in A065: SPD REF and A000: FIL SPEED.
75% Base Process Speed = _______________
4. Use a digital hand tach or strobe gun to determine the actual roll speed. Adjust X009: TACH 1 GRAT so
that A000: FIL SPEED matches the hand tach/strobe.
X009: TACH 1 GRAT = ____________________
5. Adjust C017: ANLG SCALE so that A066: SCALED FDBK matches A000: FIL SPEED.
C017: ANLG SCALE = ____________________
TRW
Rev: 01/31/06 12
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer 6. With motor running, gradually increase
C004:RUN SPEED until rated armature volts is displayed in A012: ARM VOLTS. Document the roll speed displayed in A000: FIL SPEED at base motor speed.
A000: FIL SPEED = __________________
7. Have machine operator nip and load the rolls if applicable.
8. Begin speed loop tuning at 75% base process speed. Setup the Addapt Realtime Screen to monitor
various drive parameters. Setup Addapt Signal Analyzer to record A065:SPD REF,
A002:ACT SPEED and A003:I ARM PCNT.
a) Slowly increase C029: SPD P GAIN until instability occurs. Document the P-GAIN value at which
instability first occurs. The FWD BRIDGE ON and REV BRIDGE ON Led’s usually begin to toggle when instability occurs. However, be aware there are times when too much P-GAIN will cause a knee or breakdown on the rising edge of step change long before instability occurs. Decrease the SPD P GAIN until the instability disappears. Turn on LOC BIT 2 to enable step change for about 8 seconds and then turn off. Verify that motor/roll speed increased by the C009:AUX SPD ST1 value, Current Limit Led is off, and that no instability exists. If instability occurs, reduce the SPD P GAIN as required.
Reduce the motor/roll speed to 25% base process speed. Enable the speed step change as above and reduce the SPD P GAIN as required if instability occurs.
b) Return the motor/roll speed to 75% base process speed. Begin increasing the C031: SPD I GAIN by
lowering the value from 8.0 seconds to 7.0 seconds and so on in 1-second increments. Turn on LOC BIT 2 to enable step change after each change to SPD I GAIN and observe the speed response on Signal Analyzer. Adjust the SPD I GAIN as necessary to obtain the quickest speed response with 10% or less overshoot. Check the speed response at 25% and 50% of base process speed. Adjust the SPD I GAIN as required. C029: SPD P GAIN = __________
C031: SPD I GAIN = __________
c) If acceptable speed response cannot be obtained, the problem may be due to a mechanical resonance
frequency limiting the speed loop gains. A notch filter may be required to obtain the desired speed response.
While recording A002: ACT SPEED on Signal Analyzer, increase the C029: SPD P GAIN until the speed goes unstable for 5 seconds and quickly reduce the SPD P GAIN until the motor speed becomes stable. Count the number of speed oscillations (peaks) for a 5-second period of instability. Divide the number of peaks by 5 seconds to compute the notch frequency in HZ. Turn off LOC BIT 1 (Run) and set the following parameters:
C029: SPD P GAIN = C024: NOTCH DEPTH = C025: NOTCH FREQ =
TRW
Rev: 01/31/06 13
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer C026: NOTCH WIDTH = Turn on LOC BIT 1 (run). Repeat steps 8a and 8b above. Adjust the NOTCH DEPTH and NOTCH WIDTH if required to obtain desirable speed response.
d) If acceptable speed response still cannot be achieved, the user may try a LEAD or LAG filter. The
motor should be stopped before entry of either LEAD or LAG values. The LEAD filter can be used when faster speed response is required. To obtain a LEAD filter, the user must make C028: SPEED LEAD smaller than C027: SPEED LAG.
The LAG filter can be used to reduce overshoot at the sacrifice of slower speed response. To obtain a LAG filter, the user must make C027: SPEED LAG smaller than C028: SPEED LEAD. Typical values for a LAG filter is LAG = 20 and LEAD = 80 or 100.
Setting both SPEED LEAD and SPEED LAG = 1.0 prevents the LEAD/LAG filter from affecting the speed loop response. The further the SPEED LEAD and SPEED LAG values are separated from each other, the more effect the filters have on the speed response. Entering LEAD and LAG values will require adjustments to the SPD P GAIN and SPD I GAIN values, so repeat steps 8a and 8b.
Check speed response at 25% and 50% of base process speed.
C028: SPEED LEAD = ___________
C027: SPEED LAG = ___________
e) Inertia compensation (SPD FFWD GN) may be required on machine sections having a large inertia,
such as dryer sections on paper machines. Inertia compensation gives the motor a boost in armature current only during ramping.
If inertia compensation is desired, set up ADDAPT Signal analyzer to record
A002:ACT SPEED and A003: I ARM PCNT. Note the present speed displayed in A000: FIL SPEED and increase C004:RUN SPEED to create a sizable speed increase (ramped). Determine the value for C007: RUN AF RATE.
During the speed change, I ARM PCNT will peak and then drop off when inertia is overcome. The SPD FFWD GN can then be calculated by:
C007: SPD UP RATE
C035: SPD FFWD GN = ______________ Percent
9. Turn off LOC BIT 1 (Run). Document all speed loop gains:
C029: SPD P GAIN
C031: SPD I GAIN = = _____________ _____________
TRW
Rev: 01/31/06 14
=
=
=
=
=
= ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer C024: NOTCH DEPTH C025: NOTCH FREQ C026: NOTCH WIDTH C027: SPEED LAG C028: SPEED LEAD C035: SPD FFWD GN
_____________ _____________ _____________ _____________ _____________
_____________
If operation above base speed is not required, go to step #10 of the CEMF LOOP TUNING AND FIELD TABLE SETUP section.
CEMF LOOP TUNING AND FIELD TABLE SETUP
1. If operating above base motor speed is required, setup Addapt Signal Analyzer to record A005:I FLD
PCNT. Select an analog trigger of A007:MOTOR CEMF with a trigger value of 5 Vdc higher than crossover value.
2. Set the following drive parameters:
C044: CROSS OVR V = P149: CEMF FLD EN = P151: FLD PROT EN = P152: FLD PROT E2 =
RESET DRIVE
3. Make ADDAPT Realtime Screen to monitor A002: ACT SPEED, A005: I FLD PCNT, A006: I FLD
AMP, A007:MOTOR CEMF, A012: ARM VOLTS, C004:RUN SPEED, C044: CROSS OVR V and C048:CEMF MIN LM.
4. Press the E-STOP Reset pushbutton. Set C004:RUN SPEED below base speed and turn on LOC BIT
1(run).
5. While monitoring the ADDAPT Realtime Screen, slowly increase C004:RUN SPEED until A065: SPD
REF equals either the maximum rated motor speed or any desired maximum speed (in the field range). Use caution so that the motor armature voltage does not rise to an unsafe level. It may be necessary to increase C048:CEMF MIN LM to a larger negative value. Note the speed at which the field begins to weaken.
SPEED at Crossover = _______________
6. While running at your desired maximum speed, observe parameter A005: I FLD PCNT. Subtract this
value from 100% and enter result as a negative value for C048:CEMF MIN LM. Verify your actual speed is still at your desired maximum and armature volts is at a safe level. Document the field current percent and amps at maximum speed.
C048: CEMF MIN LM = _____________
A005: I FLD PCNT = _____________ % at maximum speed
A006: I FLD AMP = _____________ AMPS at maximum speed
TRW
Rev: 01/31/06 15
ADDvantage-32 AC to DC Power Converter Software Part Number 694012.V15 and Up Optimized for Blueprint Room Printer
A002: ACT SPEED = _____________ (maximum speed)
7. Decrease C004:RUN SPEED so that ACT SPEED is about in the middle of your field weakened range.
Adjust C045: CEMF P GAIN and C046: CEMF I GAIN for the best response of A005: I FLD PCNT as observed on Addapt Signal Analyzer.
Hot tuning of the CEMF regulator is not usually desirable. The step response can be implemented using the Realtime Screen by increasing C044: CROSS OVR V by 20 VDC and then decrease back to original value. Verify there is not instability when crossing from the armature range to the field range or at any speed in the field range.
C045: CEMF P GAIN = _______________
C046: CEMF I GAIN = _______________
8. For greater CEMF control accuracy, TABLE #O should be set up. The X values will be entered as
speed in process units and Y values entered as I FLD PCNT divided by 100. The X0 value should always be 0.00 (zero speed) and Y0 = 1.00 (100%).
The X1 value should be entered as your speed at crossover and its corresponding Y1 value = 1.0 (100%). Parameter X15 = your maximum speed. The remaining Y values will be entered as the decimal equivalent of the percent field current (I FLD PCNT。