•All installations should comply with local regulations•For detectors approved to UL268refer to NFPA72for installation guidance.In such installations,it is advised that the maximum distance of Detector and Reflector from the ceiling must be 10%of the distance between floor and ceiling•For installations covering less than 18m,the Short Range Mask must be used•Position beam as high as possible,but with a minimum distance of 0.5m from Detector and Reflector to ceiling.•Mount Detector and Reflector directly opposite each other•Do NOT position Detector where personnel or objects can enter the beam path •Do NOT position 2Detectors facing each other •Detector LED indicator must face downward•Do NOT install the Detector or Reflector in environments where condensation or icing are likely tooccur18—50m =150—100m =48—18m =1Use Short RangeMaskEnsure clear line ofsight from Detector to ReflectorMount on solid surfaces (structural wall or girder)1.General Information2.Fitting the ProductClip PCB intobaseInsert DetectorcableLED indicator must face downward3.Wiring DiagramsWiring two Detectors onto two Zones:To Detector 1To Detector 2EOL EOLDET 1DET 2N/OCOMN/CN/OCOMN/CN/OCOMN/CN/OCOMN/C14V -36V DC123123123Con C Zone 1-Zone 1+Zone 2+Zone 2-Supply +Ext Reset Supply -Con A Con B see note 1see note 1ExtReset123Con D •Note 1:This component is the fire resistor.Its value is specified by the Fire Control Panel manufacturer.For U.S.installations it is typically a short circuit •ALWAYS use a separate 2-core cable for each Detector head•CAUTION:For system monitoring -Do not use looped wire under any terminals.Break wire run to provide monitoring of connections •Components not supplied:•End Of Line ('EOL')component -supplied by Fire Control Panel manufacturer •Fire Resistor•After installation,check operation of Fire and Fault connection on Fire Panel•Apply a voltage of 5V to 40V to ‘Ext Reset’contact for at least 2seconds to clear a latched fire conditionFireFaultFire Fault3.Wiring Diagrams (continued)Relay connections for wiring the two Detectors of one Controller onto one Zone:For wiring to other types of Fire Control Panel,or to wire multiple Controllers onto one Zone,refer to additional installation instructions supplied with the productEOLN/O COM N/C N/O COM N/CN/OCOMN/CN/OCOMN/C123123123Con C Zone 1-Zone 1+Con A Con B see note 1123Con D Fire Fault FireFault5seconds5secondsNOTE:One System Controller can be used to control and monitor up to two Detector heads.The ‘#’symbol in this guide is used to represent the number of the Detector currently selected (1or 2).4.Apply power•Commissioned system:•Detectors have been found but the selected Detector is not aligned:•Detector is connected butnot ‘Found’(normal on uncommissionedsystem):•Communications fault,or no Detector connected:Pressfor Pass Codescreen:•Default PassCode:1234•Change digit •Move between digits •Accept•An incorrect Pass Code will return the display to the Pass Code entry screen•Three incorrect attempts will lock access for three minutes5.Enter Pass Code to Access Engineering Menu6.Find Detectors•Press to enable ‘Found’Detectors at any point during 60s countdown•Any unused Detector channels are switched off •Press to re-scan if number is incorrect•‘Find’is automatically displayed the first time this process is run.‘Find’can also be accessed in the System Controller settings menu.Find must be performed when adding or removing a detector to an already ‘Found’system.•In‘Hi A’mode(default),during normal operation the system will take5.5mA if one Detector is connected or8mA if two Detectors are connected. During Laser targeting,Auto, Hand and Home functions,the system will take36mA.•In‘Lo A’mode(selected via the System Controller settings menu),the system will take 5.5mA or8mA in ALL modes of operation.The Detector will move more slowly during Align, Laser targeting and Home,so it is recommended to leave the system set to‘Hi A’if the current isavailable.7.Select Power Mode8.Select Detector•Select Detector to be accessed•All Detectors need to be aligned separately•Steps9to129.Select Distance between Detector and Reflector •Select8-50m(default)or100m(Set for eachDetector)SER TargetingThe system will signal Fault while in this modeThe LASER is used to align the Detector with the Reflector.It is an approximate alignment tool only.After Auto-Align the LASERwill not necessarily be pointing on the Reflector •Use to move the LASER as close to the Reflector as possible •One press of an arrow key results in one movement of the Detector head •Press or to turn off the LASER and return to the Settings menu•Refer to Additional Detector Information for troubleshooting if LASER is not visible11.‘Auto’Alignment•Select ‘Auto’to automatically align the infrared beam •Signal Strength will be shown during Alignment•If the LASER is turned on it will not necessarily be pointing on the Reflector after ‘Auto’is run -this is normal•If ‘Auto’ends with an error code ‘E-’,refer to troubleshootingHiA:2minutes LoA:25minutes•When ‘Set’is displayed press whilst the Reflector is still uncovered•When ‘S-00’is displayed,cover the Reflector with a non-reflective material and leave covered,then press•When ‘S-01’is displayed,uncover the Reflector and leave uncovered,then press •Repeat Steps 8to 12for any other Detectors found during the ‘Find’process12.‘Set’0/100(Calibrate)13.System is Aligned•Green LED on Detector will flash every 10seconds,and Signal Strength should be between 99%and 101%•Default values:35%Fire Threshold,10second delay to Fire and Fault,Non-Latching mode14.Manual Fire and Fault TestsAfter installation or cleaning,it is recommended that a manual Fire and Fault test is performed:Fire Test:Cover the Reflector slowly so that it takes longer than 5seconds to cover.The System Controller will signal Fire to the Fire Control Panel after the delay to fire has expired (10s default)Fault Test:Cover the Reflector completely within 2seconds.The System Controller will signal Fault back to the Fire Control Panel after the delay to fault has expired (10s default)Detector Fire LED Test Detector will signal Fire,System Controller will stay Normal.Press to exitwithout performing the testRelay/Controller Wiring Test System Controller signals ‘Fire’to Fire Control Panel Press or to exitIt is possible to perform a Fire Test from the System Controller,to test the wiring to the Fire Control PanelNOTE:The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine Maintenance per UL268-515.Remote Fire TestThis setting is the threshold at which the Detector will detect a fire Default factorysetting=35%(Set for each Detector)16.Fire ThresholdComplies with EN54-12for sensitivity levels between 25%and 35%with a maximum delay to fire of 20seconds•Sensitivity can be adjusted in 1%steps by pressing up or down keys •Press to accept setting EN Approved Sensitivity Ranges:to move between icons in theDetector Menu,shownDelay 1(Fire)These settings are the delays that the System Controller uses before signalling a FIRE or FAULT condition respectively to the Fire Control Panel.Default factory setting=10seconds Delay 2(Fault)In Latching Mode the system will stay in Fire condition after the fire clears.In Non-Latching Mode the system will automatically return to normal condition after the fire clears(Set for each Detector)17.Fire/Fault Delaytching/Non-Latching ModeTo clear a latched fire,apply 5-40V to the External Reset terminal,enter the passcode,or power cycle for 20s(Set for each Detector)19.Cleaning the SystemThe system will automatically compensate for dust build-up by changing the Compensation Level.However,it is recommended that the Detector lenses and the Reflector are cleaned periodically with a soft lint-free cloth.If the Compensation Level for a particular Detector remains above130for several days,this indicates that cleaning should take place on that Detector.The system should be isolated from the Fire Control Panel before cleaning takes place.After cleaning,verify that the system is operating normally:If the Signal Strength is between92%and108%-leave the system to compensate back to100%(this should take no more than12hours)If the Signal Strength is above108%-reduce Compensation Level until Signal Strength is92—108%,and wait for system to compensate back to100%If the Signal Strength is below92%-perform LASER Targeting,Auto-Align,and Set.How to change Compensation Level:20.Troubleshooting21.1.Multiple Zone WiringWhen using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP),it is important to choose the correct method of wiring.Incorrect wiring may result in a Controller isolating subsequent devices on that zone if it enters a Fault condition,and may prevent these subsequent devices signalling a Fire condition back to the FCP .If the FCP monitors for point detector removal,it is possible to use the following wiring diagrams which use diodes to provide zone continuity in the event of a Fault state on any Controller.Two Detectors connected to Controller:Single Detector connected to Controller on “Det 1”:Note 1–This component is the Fire Resistor.Its value is specified by the FCP manufacturer,and is not supplied with the System Controller.For U.S.installations it is typically a short circuit.Note 2–Recommended diode type:Schottky,60Volt,1Amp;must be UL listed for installations meeting NFPA72.Con C Fire Con D FaultFire Con A Fault Con BCon C Fire Con D FaultFire Con A Fault Con B1.Multiple Zone Wiring(continued)If the FCP does not monitor for detector removal,it is recommended that the following wiring diagram be used.For installations conforming to UL268and NFPA72,the following diagram MUST be used when wiring multiple Controllers onto one zone.Note1–This component is the Fire Resistor.Its value is specified by the FCP manufacturer, and is not supplied with the System Controller.For U.S.installations it is typically a short circuit.EOL–End of Line component.This is supplied with the FCP,and not supplied with the System Controller.Do NOT wire to any unused relay pairs.Con A and Con B are the relay outputs for Detector1;Con C and Con D are the relay outputs for Detector2.2.Event LoggerThe System Controller contains a logging function which will store information for the most recent 50events on each Detector.For each Fire or Fault activation,the controller will store:If there have been power-cycle events on the controller,all timing information will be lost for those events that occurred prior to the most recent of the power-cycles.To erase and restart the event logger,press and hold ‘left’and ‘right’keys together when displaying any of the event log entries.Press ‘tick’when prompted by ‘SurE’.To access the event log,press tick on the Event Logger icon when the relevant detector is highlighted:Event Number01is the most recent event 02is the event before 0103is the event before 02,and so on•The event code –This is the same as the error code (E-__)that would be displayed during the Fault,or one of the following:•99-Log erased •98-Power cycle •97-Fire Detected•96-Remote Fire Test initiated •95-AUTO initiated •94-LASER activated •93-‘Home’initiated•The elapsed time since the event occurred •The duration of the event•The signal strength when the event occurred (if applicable)•The AGC value when the event occurred (if applicable)2.Event Logger(continued)Press left to access olderevents,and right to accessnewer events.When therelevant event is selected,press down to accessfurther information about theevent.Time elapsed since eventstarted.‘—‘will be displayedif the event occurred prior tothe most recent power cycle.Duration of event.‘—‘will bedisplayed if the event is stilloccurring,or if a power cycleoccurred while the eventwas in progress,or if thereis no duration associatedwith the event type(e.g.power-on)Signal strength when theevent occurred.If the signalstrength could not be readduring the event‘—‘will bedisplayed.AGC value when the eventoccurred.If the AGC valuecould not be read during theevent‘—‘will be displayed.3.Troubleshooting-LASER not visibleIf it is not possible to see the LASER because of the installation environment(for example,if you cannot see the Reflector from the System Controller or there is high ambient light)then use‘Hand’Alignment.This option displays the signal strength value returned by the Detector, and allows the user to move the beam1.Start‘Auto’Alignment and press after two seconds to exit.(this will maximise infrared power)2.Select‘Hand’alignmente to steer the beam until the signal strength is above800.There is no auto-repeat function on any key.To move the motor in any given direction more than once, press the key multiple times4.Cover the Reflector.If the Signal Strength does not drop by more than half,the beam is not aligned to the Reflector,so repeat Step35.Perform‘Auto’alignment,followed by‘Set’4.Troubleshooting-HOMEIf it is not known where the beam is pointing,use Home Position to automatically steer the infrared beam to approximately the centre of its range of movement.•Press or to exit this function•This will take up to3minutes to complete•When complete the display will return to the Engineering Menu5.Display and Indicators -LCD Icon LayoutD e g r e e s F i r e T r a n s m S i g n a l R e c e i v S i g n a l %/VS y s t e F i r e L A S E R S e t B a r G r a p hS y s t e m L o c k e d /U n l o c k e dW a r n i n gB u s yM e t r e s6.Display and Indicators -Detector and System ControllerStatus Indicators123•PressinthismenutoenterthePassCode•PresstoputthesystemintoSleep ControllerStatusSystemControllerSoftwareVersionDetectorSoftwareVersionDetectorStatus8—5mor5—1m8.Menu Layout -Engineering Menu•T h e P a s s C o d e m u s t b e e n t e r e d t o a c c e s s t h e E n g i n e e r i n g M e n u •T h e m e n u i s n a v i g a t e d b y u s i n g k e y s t o m o v e t h e c u r s o r .•I t e m s a r e s e l e c t e d b y u s i n g •P r e s s i n g e x i t s t h i s m e n u a n d r e t u r n s t h e s y s t e m t o a ‘l o c k e d ’s t a t eS e t t i n g s E v e n t L o g F i r e T e s t D e l a y9.**Gain**1% SetDetector10.System Controller SettingsCodePower Mode•Change Pass Code Use to access each digit Use to change the digit Press to save the new Pass Code and return to the settings menu Press to cancel the change and return to the Engineering menuDetectors。

Cirrus Pro User Manual Issue 3.1 14-02-06-中文版

Cirrus Pro User Manual Issue 3.1 14-02-06-中文版

CIRRUS PRO火灾侦测器使用者手册目录1.0简介 (2)1.1型号和设备 (3)1.2UL及ULC信息Pro100, 200, 200+, 200D, 200D+, 200DSC及200DSC+ (4)1.3Pro X4之UL及ULC信息 (6)2.0 定期检修 (8)2.1 定期检查 (8)2.1.1 每天检查 (8)2.1.2 三个月检查 (8)2.1.3 年度检查 (9)3.0 使用者指引 (9)3.1 面板指示和控制 (9)3.2 面板显示 (9)3.2.1 主功能选单 (11)3.2.2 实时图形表示 (12)3.2.3 单位/管显示 (12)3.2.4 事件讯息 (12)3.2.5 历史图形 (13)3.2.6 密码 (13)3.2.7 维修讯息 (14)4.0 侦错 (15)4.1 错误讯息列表 (15)4.2 侦测单元上的错误码 (15)5.0 侦测器规格 (15)1.0简介本手册详述Cirrus Pro Series Aspirating Fire Detectors的安装,测试及服务使用方法。

背景当材料过热时会产生比可见光波长还小的粒子已是众所皆知的事,而且其数量远远超过在正常环境下存的粒子数。

Cirrus Pro侦测器利用Wilson的云雾室理论来侦测火的早期及其它各阶段所产生的次微粒子。

经过过滤的空气样本经由离心风扇传送到侦测器,其中一部份被送入一个增湿器中。

在接近100%的相对湿度下,空气样本被吸入云雾室。

因为真空样本迅速的膨胀、降温,并使水气凝结在小粒子表面而造成”云雾”。

因此,这些由温度变化产生的粒子造成了许多小水滴而形成云,这些小水滴会被云雾室的测量系统侦测。

云的密度会以相称的粒子数量来表现。

侦测的结果是一个连续的讯号,其相对应于粒子的浓度,且此讯号用来提供有4个顺序的警报。

Cirrus Pro侦测器有自我管理系统,会持续的监视其正常的操作。

任何问题会立即有面板灯号、蜂鸣器及失误继电器发出警告。

火焰探测器设计手册.doc

火焰探测器设计手册.doc

火焰探测器设计手册(设计院)一、产品概述防爆红外、红紫外复合火焰探测器(以下简称探测器)属于智能型火灾探测设备,它运用了先进的多红外传感技术(MIR)和复合探测技术,采用多通道火焰传感器设计。

本探测器能够对日光、闪电、电焊、人工光源、环境(人等)、热辐射、电磁干扰、机械振动等干扰有很好的抑制,从而实现了对火焰信号的快速响应和准确识别。

本探测器采用非接触式探测,灵敏度现场可调,提供无源接点、标准电流输出和总线接口与火灾报警系统相连接。

本探测器适用于无烟液体和气体火灾、产生烟的明火以及产生爆燃的场所。

例如:航天工业、飞机库、飞机修理场、化学工业、公路隧道、弹药和爆炸品仓库、油漆工厂、石油化工企业、制药企业、发电站、印刷企业、易燃材料仓库等可燃物含碳物质的其他场合。

本探测器根据GB3836.1-2000《爆炸性气体环境用电气设备第1部分:通用要求》、GB3836.2-2000《爆炸性气体环境用电气设备第2部分:隔爆型“d”》的规定,制成隔爆型结构,其防爆标志:ExdⅡCT6。

适用于工厂具有ⅡA、ⅡB、ⅡC级,引燃温度组别为T1~T6组的1区、2区可燃性气体或蒸气与空气形成的爆炸性混合物的场所。

二、产品系列介绍三、火焰探测器型号注释JTGB ―□□―□□ □□□(□□)―□□/□□□产品类别组特征代号传感器特征及传输方式代号厂家代号产品代号Ex 防爆标志IR 红外火焰探测器UV 紫外火焰探测器UV/IR 红紫外复合火焰探测器IR2双波段红外火焰探测器IR3三波段红外火焰探测器四、产品资料※JTGB-UH-YC103-IR2 隔爆双波段红外火焰探测器 ●产品简介防爆多波段红外火焰探测器(以下简称探测器)属于智能型火灾探测设备,它运用了先进的多红外传感技术(MIR ),使用两只具有窄带滤波的不同波长的红外传感器,其中一只传感器工作在反映火焰信息的中心波长,另外一只传感器监视环境中的其他红外辐射,结合火焰的闪烁特征,通过高性能的微处理器和先进的数学算法模型进行运算分析,使得只有符合火焰特征的辐射频谱才会被确认为火警,而其他的干扰因素形成的假火警信号则会被排除。

火灾探测器用户手册说明书

火灾探测器用户手册说明书

OVERVIEWThis detector model samples the air and the environmental temperature in the protected area. An alarm condition is raised when the detected environmental smoke quantity, the temperature level or the thermal variation rate exceeds the alarm threshold.COMPATIBILITYThis detector is compatible only with wireless systems based on the Sagittarius protocol.For more specific information concerning compatibility refer to your fire security system supplier.INSTALLATION - IMPORTANT NOTESFor detector spacing, placement and special applications refer to your specific national standards.Mount the detector as far as possiblefrom metal objects,metal doors, metal window openings, etc. as well as cable conductors, cables (especially from computers), otherwise the operating distance may greatly drop. The detector must NOT be installed near electronic devices and computer equipment that can interfere with its wireless link quality.This detector must be installed according precisely to the procedures described in this manual.Test this detector after installation.BEFORE INSTALLING THE DETECTOR1) Extract the batteries cover from the back of the detector.2) Power -up the detector removing the isolating tab in the battery housing. LED indicators signal “Power up ”.3) Link the detector to the Sagittarius wireless system (LINKING ). 4) Check the WIRELESS LINK QUALITY .5) SELECT A GOOD LOCATION FOR THE DETECTOR . 6) Tag device ’s loop and address data (IDENTIFICATION ).7) Fix the detector supporting base to the wall (BASE INSTALLATION ).LED INDICATORSPicture 1: provide visual indication for functional conditions and battery levels as indicated in table 1.HFW -MA -05BI -DIRECTIONAL WIRELESS ADDRESSABLE MULTICRITERIADETECTOR WITH VARIABLE SENSITIVITYLED INDICATORS Picture 1928m/02LINKINGrefer to the translator ’s or the Wirelex configuration software ’s literature):1) Move the link switch ’call it BLANK, since it carries no indication). LED indicators signal “system ” (picture 2).Linking is successful when: a) the translator indicates so (check translator ’s literature)ORb) the Wirelex software indicates so (check the Wirelex ’s literature).If linking is unsuccessful:2) Check if evident mistakes were made.3) Perform the LINKING RECOVERY .LINKING RECOVERY1) Take out both batteries from their holders2) Move alternatively the link switch to ON / BLANK five times (picture 2) 3) Move the link switch to ON4) Reinsert both batteries into their holders, oriented as per polarity marks5) Perform the LINKING procedure.DETECTOR SENSITIVITY SETTINGSDuring installation using the Wirelex software it ’s possible to set the smoke sensitivity and the heat class of the detector (see tables 4 and 5). Otherwise if the installation is performed manually through the translator keyboard, default setting will be applied.WIRELESS LINK QUALITYIt is possible to check wireless link quality between the detector and its linked -to translator or expander in this way:1) Move the link switch to the ON position.2) LED indicators will start blinking according to the following table:3) NOTE: Ensure the link switch is returned to the "BLANK" (operational) position on completion of testing.SELECT A GOOD LOCATION FOR THE DETECTORChoose for the detector a placement position that:- compliances with your specific standards- is reached by a strong wireless signal from its linked -to translator or expander module- is not interfered by environmental factors.IDENTIFICATIONFor identification purposes, analogue loop number and device ’address can be recorded on the plastic tag supplied with base (picture 3).base.**********************.ukL20-LMCXX -1400 (vA.2)Picture 3Assessment Device ’s indicationDuring the linking phase, the detector must be positionedclose to the aerial (within a few centimeters) of the translator or expander to which it is being linked. Picture 2 Link switchBASE INSTALLATIONFix the base to the wall with the provided screws (picture 4).DETECTOR PLACEMENT1)Install the batteries cover.2)Position the detector centrally on the baseensuring it is level.3)Rotate clockwise applying gentle pressure.The detector will drop into its keyed location.4)Continue to rotate clockwise a few degreesuntil the detector has fully engaged in thebase.5)When the detector is firmly engaged, checkthe alignment of the raised reference markson the detector and on the base (picture 5).DETECTOR LOCKINGTo lock the detector to the base, screw in the provided security screw; screw entry is locat-ed on the side of the detector’s base (picture 6).TAMPER DETECTIONWhen the detector is detached from the base a tamper message event is sent to the control panel.TESTINGTest this detector after installation.After each test reset the fire security system from the control panel, as per your control panel in-structions.TEST MODESTest modes make the HFW-MA-05 more reactive to aerosol stimulus; two test mode types are provided:Type 1 Test Mode -almost instantaneously alarm agent reactive.Type 2 Test Mode -makes the detector as reactive to smoke as an optical smoke detector, simulating it.TEST 1 - MAGNET TEST1) Hold a suitable magnet in correspondence of the indicated area (picture 7)2) LED indicator will signal “Type 1 Test Mode”3) Apply again the magnet in correspondence of the indicated area (picture 7)4) LED indicator will signal “Alarm”TEST 2 - AEROSOL TESTUse only suitable aerosol testers supplied by approved manufacturers.1) Hold a suitable magnet in correspondence of the indicated area (picture 7)2) LED indicator will signal “Type 1 Test Mode”3) By following its specific instructions, apply the aerosol test device to the detector4) Wait a few seconds5) LED indicator will signal “Alarm”TEST 3 - AEROSOL TESTUse only suitable aerosol testers supplied by approved manufacturers.1) Remotely activate the detector’s green LED from the Wirelex program2) LED indicator will signal “Type 2 Test Mode”3) By following its specific instructions, apply the aerosol test device to the detector4) Wait a few seconds5) LED indicator will signal “Alarm”TEST 4 - HEAT TESTUse only suitable heat test devices from approved manufacturers.1) By following its specific instructions, apply the heat test device to the detector.2) Wait a few seconds.3) LED indicator will signal “Alarm”.Picture 5Dust covers DO NOT providecomplete protection againstcontamination: detectorsshould be removed before construc-tion, major re-decoration or other dustproducing work is started.Dust covers MUST be removed beforethe system can be made operational.Picture 4Picture 6Picture 7MAINTENANCE - CLEANING1) Remove the detector from its base.2) Smoke entry areas and thermistor area: use asoft bristle brush to dislodge any obvious such as insects, spider webs, hairs, etc.3) Smoke entry areas and thermistor area: use a blow any remaining small particles away.4) damp, lint -free cloth to remove any surface film that later attract airborne contaminants.5) Install the detector onto its base again.6) Test the detector. MAINTENANCE - BATTERY REPLACEMENTWhen a low battery condition is indicated, both batteries must be changed altogether.During this procedure the linking switch must NOT be touched at all !1) Detach the detector from its base.2) Extract the batteries cover.3) Extract the batteries.4) Insert the new batteries into their holders, oriented as per polarity marks.5) Reinstall the batteries cover.6) Reinstall the detector onto its base.7) Test the detector.**********************.ukL20-LMCXX -1400 (vA.2)Table 3Table 4Table 5* When a low battery condition is indicated, both batteries must be changed for new cells. Lifespan of batteries indicated is subject to standard environmental conditions, default monitor settings and excellent link quality.** Check latest version of document TDS -LMCXX for further data, obtainable from your supplier.。

特殊检测 Cerberus PRO 高级防火探测器说明书

特殊检测 Cerberus PRO 高级防火探测器说明书

Detector FDA241
Order no.: S54333-F17-A1
Multi-criteria fire detector OH921
Order no.: S54320-F6-A2
Thermal (heat) detector HI921
Order no.: S54320-F5-A2
Compatible with bases below
Audible base ABHW-4B
Order no.: S54320-F13-A1
Audible base ABHW-4S, (520Hz)
Order no.: S54320-F14-A1
Ceiling mount remote lamp RL-HC
Order no.: 500-033230
Wall mount remote lamp RL-HW
– Complies with UL 268 7th edition requirements.
Multi-criteria fire detector OOH941
Order no.: S54320-F7-A2
Multi-criteria fire/CO detector OOHC941
Order no.: S54320-F8-A2
– Complies with UL 268 7th edition requirements.
Cerberus PRO standard detectors
– Solution for standard applications with average risk and moderate potential for deceptive phenomena

诺帝菲尔消防主机操作说明 ppt课件

诺帝菲尔消防主机操作说明  ppt课件

• 广播线:双绞线
• 电话线:屏蔽双绞线
ppt课件
系统特性-抗雷击特性
在抗雷击措施方面,NOTIFIER产品的 性能同样出色。雷电所产生的高压放电 主要是通过外部线路窜入控制器内部, 这里所说的外部线路主要是指220V交流 供电线路。对于该线路,在NOTIFIER 消防报警系统的电源中采用了MOV(金 属氧化物压敏元件)和GT(空气管)等 元件对窜入的高压瞬变信号(雷击)进 行限制和隔离。具体的原理如右图所示 :
• 可作为NFN网络中的指令中心 • 图形化显示楼层平面及设备 • 显示或控制所有网络节点 • 显示所有网络事件
• 确认、消音和复位基本功能外,还可以屏蔽或解除屏蔽探 测器、模块和区域;激活或关闭控制模块;查询和修改各 个控制器系统设置等。
• Notifier美国工厂开发的标准产品,并通过UL认证。 • Windows软件环境,Notifier专用软件,中文界面,清晰友

ppt课件
远 程 联 网
AM2020
AFP-400
NCA
NFN网络
Onyx Works
TC/PIP 网络线
NFS-3030 NFS-640
ppt课件
Honeywell Fire & Security Systems (Shanghai) Co., LTD.
霍尼韦尔消防安防系统(上海)有限公司
2nd Floor, Building 1 3215 Jinxiu Road, Pudong New Area Shanghai China 200125
工业自动化
Honeywell
楼宇自动化
消防系统
……
ppt课件
Notifier控制器
全进口系列

IFD火灾探测器安装及调试说明

IFD火灾探测器安装及调试说明

真空泵引管 接口
云雾室
压强传感器 接口
云雾室
水位传感器 接口
水位传感器
云雾室
空气样品 过滤器
清洁空气 过滤器
云雾室
进水管
云雾室
LED光源 产生器 电源接口
LED光源 产生器
云雾室
内容

外观 内部结构 主板 云雾室 抽气泵 真空泵 水瓶 分解程序 一般故障发现与处理
机器数据储存
打开网络Байду номын сангаас项框,当选择‘发送 送设定讯息到单机上’ (Set detector network number)时
会出现一个 确认对话询 问你程序已 经重置,是 否确认要改 变设置,按 下【OK】即 可传送设置 信息到前端 设备。
在更改设置的后,数据需储存于机器中。
任何机器设定的更改必须下载至机器中,这必须从机器的选单中手动 完成,但如果关掉联机时,修改尚未储存会出现提醒讯息。 再有任何要关闭电脑程序动作时,如果有修改数据,显示屏幕会出现 提示(本设备设置已经改变,如果不把新设置发送到前端设备,修改 数据将会丢失,是否放弃修改):
主板
LED光电接收 器接口
主板
LED光源 發生器接口 水位传感器 接口
内容

外观 内部结构 主板 云雾室 抽气泵 真空泵 水瓶 分解程序 一般故障发现与处理
云雾室
固定螺丝
固定螺丝
云雾室
LED光电组件 接收器
注意:连接的时候一定要小心引脚
云雾室
电磁阀
云雾室
搜索连接于网络里的所有设备
2. 分配计算机端口位置
点击网 络 (Netw ork)
选择相 应的接 口 (CO M Port)

极早期火灾报警器数据中心解决方案

极早期火灾报警器数据中心解决方案

Cirrus Pro IFD 云雾室极早期火灾报警系统计算机数据中心解决方案展径贸易(上海)有限公司目录一.计算机数据中心极早期火灾防范的重要性二.计算机数据中心极早期火灾防范特点三.传统点式烟雾探测设备的局限性四.Cirrus Pro IFD云雾室极早期火灾报警器`的工作原理五.Cirrus Pro IFD在计算机数据中心的应用优势六.CirrusPro IFD网络结构七.云雾室型与激光型探测器性能比较八.IFD探测器主要技术指标和参数一.计算机数据中心极早期火灾防范的重要性随着社会的发展和进步,以及现代科技及信息产业的飞速发展,人们对书籍、资料和数据(印刷版本、电子版本、电脑数据库等)的兴趣和需求越来越强烈,已经成为我们日常工作和生活当中的重要组成部分,为我们提供了知识和乐趣、资料和数据以及信息等服务。

我们对其的依赖也变得日趋强烈。

与过去的情况相比,计算机数据中心的设施越来越先进,功能越来越完备,造价也变得越来越昂贵,所以这些场所内部设施的一次很小的火灾都将造成非常严重的灾害。

其中不但包括建筑物及设施本身的损失,而由此引发的包括珍贵的文史图书、资料和数据的损毁以及信息服务中断所带来的损失将是不可估量的。

因此,计算机数据中心的安全,特别是火灾防范,已经变成保障此类场所中有形及无形资产安全,确保服务正常进行的首要问题。

但是,传统形式的火灾报警设备已经远远不能达到计算机数据中心这一类物品价值高、设施精密,有些部门还不能间断服务的场合的防护需求,为了计算机数据中心火灾防范问题,必须要有一种比现有设备更加先进,更加灵敏,更加稳定无误报,能够较好的适应这些场所特殊环境的新一代极早期火灾报警探测系统。

二. 计算机数据中心极早期火灾防范特点相对一般意义的火灾防范,计算机数据中心有着自身的特点,主要表现在以下几个方面: 1.易燃物品种类繁多--与过去相比,现代化的计算机数据中心内安置有大量计算机、电源及功能完备、价格昂贵的仪器设备、电线电缆及各种存储介质,其中设备内部的元器件,电缆绝缘外套多采用石碳酸纤维,聚氯乙烯等易燃材料,极易燃烧造成灾难性后果。

IFD极早期火灾探测器数据中心解决专业技术方案

IFD极早期火灾探测器数据中心解决专业技术方案

Cirrus Pro IFD云雾室极早期火灾探测系统计算机数据中心解决方案展径贸易(上海)有限公司目录一.计算机数据中心极早期火灾防范的重要性二.计算机数据中心极早期火灾防范特点三.传统点式烟雾探测设备的局限性四.Cirrus Pro IFD云雾室极早期火灾探测器`的工作原理五.Cirrus Pro IFD在计算机数据中心的应用优势六.Cirrus Pro IFD网络结构七.云雾室型与激光型探测器性能比较八.IFD探测器主要技术指标和参数一.计算机数据中心极早期火灾防范的重要性随着社会的发展和进步,以及现代科技及信息产业的飞速发展,人们对书籍、资料和数据(印刷版本、电子版本、电脑数据库等)的兴趣和需求越来越强烈,已经成为我们日常工作和生活当中的重要组成部分,为我们提供了知识和乐趣、资料和数据以及信息等服务。

我们对其的依赖也变得日趋强烈。

与过去的情况相比,计算机数据中心的设施越来越先进,功能越来越完备,造价也变得越来越昂贵,所以这些场所内部设施的一次很小的火灾都将造成非常严重的灾害。

其中不但包括建筑物及设施本身的损失,而由此引发的包括珍贵的文史图书、资料和数据的损毁以及信息服务中断所带来的损失将是不可估量的。

因此,计算机数据中心的安全,特别是火灾防范,已经变成保障此类场所中有形及无形资产安全,确保服务正常进行的首要问题。

但是,传统形式的火灾报警设备已经远远不能达到计算机数据中心这一类物品价值高、设施精密,有些部门还不能间断服务的场合的防护需求,为了计算机数据中心火灾防范问题,必须要有一种比现有设备更加先进,更加灵敏,更加稳定无误报,能够较好的适应这些场所特殊环境的新一代极早期火灾报警探测系统。

二.计算机数据中心极早期火灾防范特点相对一般意义的火灾防范,计算机数据中心有着自身的特点,主要表现在以下几个方面:1.易燃物品种类繁多--与过去相比,现代化的计算机数据中心内安置有大量计算机、电源及功能完备、价格昂贵的仪器设备、电线电缆及各种存储介质,其中设备内部的元器件,电缆绝缘外套多采用石碳酸纤维,聚氯乙烯等易燃材料,极易燃烧造成灾难性后果。

极早期空气采样式探测使用说明书

极早期空气采样式探测使用说明书

极早期空气采样烟雾探测器JB-BK06安装使用说明书目录一:概述-------------------------------------------------------- 2二:特点-------------------------------------------------------- 2三:技术特性---------------------------------------------------- 2四:结构介绍---------------------------------------------------- 3五:面板说明---------------------------------------------------- 4六:探测器编程-------------------------------------------------- 8 1:时间设置-------------------------------------------------- 8 2:工作模式等设置------------------------------------------ 10 3:灵敏度设置------------------------------------------ 104:环境自学习---------------------------------------------- 12七:维护------------------------------------------------------- 12过滤器更换―――――――――――――――――――――12八:常见问题与解决--------------------------------------------- 12九:注意事项--------------------------------------------------- 13一:概述:极早期空气采样烟雾探测器(以下简称探测器)是基于先进的激光光学空气监测技术和微处理器控制技术的烟雾采样探测装置。

Cerberus PRO 火警控制面板操作接口单元数据表说明书

Cerberus PRO 火警控制面板操作接口单元数据表说明书

ARCHITECT AND ENGINEER SPECIFICATIONSFCM2018-U3Standard Operating UnitFCM2035-U3Operating Unit with LEDss Cerberus® PRONOT I CE ─ The information contained in this data-sheet document is intended onlyas a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information.Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer.I nformation contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer.Siemens ─ Canada, Limited1577 North Service Road East • E. Oakville, Ontario L6H 0H6 / CanadaTel: (905) 799-9937 • Fax: (905) 799-9858 Web: /Cerberus-PROBuilding Technologies Division S CL ─ Fire SafetyMay 2017 ─ Supersedes sheet dated 8/2013(Rev. 4)Specifications – (continued)Models FC I 2016-U1 and FC I 2017-U1 provide connection for power and communication of the periphery boards.With the use of the custom-configuration tool, Models FCM2018-U3 and FCM2035-U3 can provide global functionality by annunciation and control of multiple Cerberus PRO systems. Moreover, the programming software is held in flash electrically erasable programmable read-only memory (EEPROM).The display screen for each interface module categorizes events by type, providing a separate event tab for Fire Alarm , Gas Alarm , Supervisory , Trouble and Test events.Each event can have a custom message of up to 40 characters describing the event’s location. In addition to the text message, the system displays the category of the active event: (e.g. – Automatic Alarm , Water Flow , Manual , etc) – the category means more to responding officials than model numbers.Up to eight (8) events can be displayed at a time. When more than eight (8) events are present, the four-way navigation-menu buttons allow the end-user to scroll up and down the list of events.A progress meter on the right side of the list indicates the size of the list of events and the location in the list. New, ‘unacknowledged’ events are indicated by a flashing exclamation point ('!'). Once ‘acknowledged’, the exclamation point changes to a non-flashing check mark (‘√ ’).A Maintenance Menu contains options for adjusting the contrast and brightness for the LCD screen, as well as supplying options for diagnostics and system-configuration programming.Once beyond the password-protected initial screen in ‘Menu’ view, system-configuration functions allow the end-user to enable, disable, or test alarms; activate / deactivate switches; report, control and maintain data. The soft-key buttons allow the end user to scroll down, allowing for further information to be displayed on a given event. This data can be vital to an authority-having-jurisdiction (AHJ), or any fire official responding to an Alarm system command.Models FCM2018-U3 and FCM2035-U3 also provide a complete menu for generating system-status reports. Each operating interface unit provides the user with seven (7) extra programmable buttons that can be programmed for a variety of usages. Models FCM2018-U3 and FCM2035-U3 mount to the inner door of the enclosure (Model FHD2004-U1).The operating interface units also support the following optional modules:▪ SafeDL I NK / Cnet network module for ‘peer-to-peer’networking of Cerberus PRO FACPs▪ RS −485 module (Model FCA2016-U1) forconnection to remote-display terminals (RDTs) and / or remote peripheral modules (RPMs) for printersTemperature and Humidity RangeOperating I nterface Units areULC Listed for indoor dry locations within a temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% a temperature of 90 +/-3°F (32+/-2°C).Details for OrderingModelPart NumberDescriptionF C M2018-U3 S 54400-C 40-A2Operating I nterface Unit for the Cerberus PRO FACPF C M2035-U3 S 54400-C 140-A1Siemens − Canada Operating I nterface Unit [w/ LED module]for the fire-only Cerberus PRO FACPs, and I ntelligent Voice (I VC) systems。

吸气式感烟火灾探测器系统操作手册

吸气式感烟火灾探测器系统操作手册

IFD Cirrus Pro极早期火警预警系统操作手册目录第一章一般操作 (1)第二章异常操作 (6)第三章查询 (9)第一節事件检视 (9)第二節历史曲线图 (11)第三節数据库查询 (12)第四節历史数据查询 (13)第五節图面打印 (14)第四章CirrusPro控制器操作 (15)第一節组件选项 (15)第二節灵敏度设定 (16)第三節编辑文字 (16)第四節输入输出设定 (17)第五節管之进气流 (18)第六節保修信息 (18)第七節制造信息 (19)第八節清除事件线图 (20)第九節展示模式 (20)第五章数据设定 (21)第一節树状窗口操作 (21)第一項监控计算机 (22)第二項F-NET (25)第三項区域 (30)第四項CPD(CirrusPro控制器) (33)第二節图片窗口操作 (36)第一項新增 (36)第二項删除 (36)第三項更改属性 (37)第四項CPD位置调整 (37)第六章登入 (39)第七章使用者管理 (40)第一節使用者权限 (40)第二節新增使用者 (41)第三節修改使用者 (41)第四節删除使用者 (42)第一章一般操作进入极早期火警预警系统, 屏幕显示如下:窗口说明:树状窗口极早期火警预警系统之数据为树状结构,以监控计算机图标开始,第二层为区域侦测网络(F-NET) ,每一个区域侦测网络包含区域(第三层),每一个区域包含极早期火警预警控制器(CPD) (最后一层)。

树状显示窗口如下: 图控树状窗口 图片窗口讯息窗口 CPD 状态窗口图示说明:监控计算机区域侦测网络(F-NET)区域极早期火警预警控制器(CPD)讯息窗口依CPD的状态显示该异常CPD之相关讯息。

图片窗口显示目前选定区域图片。

在树状窗口节点上按下鼠标左键, 即可快速切换至该区域或极早期火警预警控制器图片。

鼠标光标图标说明:鼠标游标在图面上移动时之图示。

当鼠标游标在图面时按下鼠标左键时之图标,此时移动鼠标可拖曳图面。

奥瑞那设计手册第二部火灾报警及消防联动控制系统产品设计应用手册

奥瑞那设计手册第二部火灾报警及消防联动控制系统产品设计应用手册

1.3 火灾探测器1.3.1 OT502智能光电感烟火灾探测器概述OT502探测器采用红外散射原理设计,内置先进的MCU微处理器,具有强大的现场数据采集和分析判断能力。

完善的火灾判定智能模型和漂移自动补偿技术,有效确保了探测器报警的准确性和工作的稳定性。

外形尺寸性能特点; 美国Microchip微处理器,内含Flash存储器,功能强大,性能可靠。

; 德国Siemens红外光电管,内含日光滤波器,有效滤除环境光线干扰。

;特殊的光学迷宫结构,响应快,一致性好。

; 先进的自动编址功能,无需电子编码器人工编址,节约工程施工时间。

; 环境自动补偿,独特的自诊断技术,对环境变化(温度、湿度、灰尘污染)的漂移量具有 自动修正补偿功能,极大地降低了系统的误报率。

; 内含智能软件,与控制器双向分布智能,最大限度地保证了报警的准确性。

; 二总线电流量脉宽数字化信号传输技术,通讯可靠,抗干扰性能强。

; 总线无极性,避免了由于接线不当而引起的系统损坏。

; 具有过流保护功能,可监测其供电电压,并可在控制器上显示出来,方便工程调试。

; 先进的SMT贴片工艺、可靠的屏蔽措施,对电磁环境恶劣场所有很强的抗干扰能力。

; 特殊三防处理,防霉防潮防盐雾,抗潮湿性能强。

;平时绿灯闪亮,报火警时红灯闪亮。

; 可做为编码探测器使用,也可做为普通探测器使用。

; 超薄流线外形,美观大方。

主要技术参数工作电压 标准值DC24V,范围DC20~28V监视电流 典型值200uA,最大值350uA报警电流 20mA(红灯闪亮时)风速 <10 m/s保护面积 60~80m2编码方式 自动编码,范围1~192线制 两总线,无极性适用底座 ODZ5004、ODZ5006、ODZ300C技术标准 GB4715-93安装与接线* 在天花板上预埋86H50型标准或其它孔距为40~85mm的预埋盒。

* 确认探测器类型与底座要求的类型一致。

* 将探测器底座用两个M4的螺丝安装在预埋盒上或直接安装在天花板上。

Cirrus Pro云雾室型极早期火灾探测器设计使用手册

Cirrus Pro云雾室型极早期火灾探测器设计使用手册
7
Cirrus Pro 取样管测试点
取样管测试点指示要作为测试的功能,通常被安装在管路最末端的位置。 N- 37-570-00 25 毫米红 ABS 端塞’测试点’ 1no。 每取样管要求。
N- 37-571-01 2mtrs 完成隐藏式毛细管测试点 c/w T 片,取样管的 10 毫米的 2mtrs 以及隐藏式测试点。
N- 37-555-73 25 毫米红 ABS 45 度弯头. 根据需要,保持到最少。
N- 37-554-72 25 毫米红 ABS 三通管 要求根据需要,保持到最少的分接。
N- 37-553-71 25 毫米红 ABS 端塞 1no。 每取样管末端必须要有。
N- 37-559-77 25 毫米红 ABS 插座 1no。 每取样管要求。
作的参数(取样管,数量和样本的大小洞或者毛细管取样点的长度)可被接受。
Cirrus Pro - 电源单位
9000 / BC 3/10 9000 / BC 3/26
9000 / BC 3/18
S9000 3Amp 电源供应器可以用于 Cirrus Pro 系列侦测器并且同时给电池充 电。
本电源供应器的作用是给侦测器提供电流并给侦测器提供备用电池。 因此, 如果侦测器在警报条件期间需要充分的 3Amp,那么充电器将允许全部的动力 被给到侦测器。 在警戒状况期间当侦测器只是提供数百毫安时,电流的剩余 部分可提供给电池充电。 如果知道在警戒状态还有警报状态所需要的电源供 应及时间,则 PSU 的尺寸就可以加以被确认。
设计前考虑………………………………………………………..………………10 极早期火灾侦测系统的预期……………………………..……………………10 侦测器灵敏性……………………………………………..……………………10 背景粒子等级…………………………………………………………………. 11 需要'性能测试'……………………………………………………………….…11

IFD云雾室型吸气式感烟火灾探测器的应用

IFD云雾室型吸气式感烟火灾探测器的应用

机场 - 具有挑战性的项目
• 巨大的开放式空间,烟雾被大大稀释 • 穹顶 • 隐蔽式探测——要求与现代化的设计相协调 • 日常维护要在运营时间内进行
海上平台
IFD优势:
不受灰尘及其他环境污染影响造成误报 较一般点式系统更早反映火灾状况 不受高速气流影响而误报 不受温湿度和冷凝水、含盐空气等极端天气影响而误报
利用毛细管 对机柜进行 保护,对电 缆的热释粒 子高灵敏度 探测,极早 期发现火灾 隐患
电缆隧道及电缆桥架的保护
输煤传送带的保护
高压配电装置的保护
泵站的保护
原 煤 仓的保 护
• 空气中灰尘粒 子含量很高
• 难以进行适当 的探测
外观很重要的场所的保护
• 有些场所内部的形象绝不允许被不雅观的传统探测器所破坏 • 大教堂,教堂 • 古老的和著名的建筑 • 博物馆 • 艺术馆 • 现代化的办公建筑 • 传统建筑
IFD应用
洁净室 • 保护洁净室,最重要的是要避免停工期。 • 洁净室被公认是防火的困难区域 。 • 高大开阔的空间 • 较高的气流速率 • 换气率高 - 最高达到每小时600次。
IFD应用
利用毛细管采样保护银行机柜
毛细管在 机柜内采样
.
感谢下 载
• 洁净室 • 仓库 • 监狱 • 高压配电装置 • 电磁兼容控制区域 • 营业中的剧院
需要足够的时间来控制局面 并安排人员撤离的场所
• 有些场所受环境条件限制,妨碍了人员的迅速撤离 • 洁净室 • 地铁站 • 剧院 • 公共建筑 • 巨大的仓库
大型公共建筑的保护
101金融大楼 电气开关室、高压开 关箱
高灵敏度探测
典型的洁净室
IFD 应 用• 电讯
• 移动通讯基站 • 配电柜 • 交换机房 • 主机室 • 传输室 • 互联网服务提供者 • 小型通讯室 • 动力室 • 备电室 • 无线电发射

IFD图控系统操作说明-SMIC

IFD图控系统操作说明-SMIC

诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
按下控制器下拉式 选单可选择单一IFD 数据显示或全部之 IFD数据显示
选择查询区 域数据
选择查询 IFD数据
诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
诚信、团队、效能、卓越


登入 一般操作 異常操作 查询 IFD (CirrusPro 控制器)操作 资料设定 使用者管理
诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
异常表列窗口
诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
移动鼠标至欲显示之IFD按下鼠标左 键即可切换图片至此IFD所属之图片
以鼠标在此窗口之项目上快击左键二次,可立即切换图片窗 口至该IFD对应之区域图片及讯息窗口至该IFD之相关讯息 未连结之IFD,若 欲忽略该IFD,则 将鼠标移至该未 连结之IFD上,按 下鼠标右键,按 下 “忽略”即可
同步极早期火災预警圖 控系统与IFD之事件资 料,进入此操作时系统 显示与IFD联机窗口:
依目前查询 之条件查询 IFD之事件数 据
诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
按下IFD-NET可选择 IFD联机,每一个联机 支持32台IFD
依目前查询 之条件查询 IFD之事件数 据 同步极早期火災预警圖 控系统与IFD之事件资 料,进入此操作时系统 显示与IFD联机窗口:
希望有机会为您服务 . . .
诚信、团队、效能、卓越
诚信、团队、效能、卓越
领导防灾新潮流,开创安全新希望!
诚信、团队、效能、卓越

空气采样早期烟雾探测系统简明设计安装手册41页PPT

空气采样早期烟雾探测系统简明设计安装手册41页PPT

56、书不仅是生活,而且是现在、过 去和未 来文化 生活的 源泉。 ——库 法耶夫 57、生命不可能有两次,但许多人连一 次也不 善于度 过。— —吕凯 特 58、问渠哪得清如许,为有源头活水来 。—— 朱熹 59、我的努力求学没有得到别的好处, 只不过 是愈来 愈发觉 自己的 无知。 ——笛 卡儿

60、生活的道路一旦选定,就要勇敢地 走到底 ,决不 回头。 ——左
空气采样早期烟雾探测系统简明设计 安装手册
11、用道德的示范来造就一个人,显私的,对谁都一视同仁。在每件事上,她都不徇私情。—— 托马斯
13、公正的法律限制不了好的自由,因为好人不会去做法律不允许的事 情。——弗劳德
14、法律是为了保护无辜而制定的。——爱略特 15、像房子一样,法律和法律都是相互依存的。——伯克

极早期火灾报警器在机场仓库使用说明

极早期火灾报警器在机场仓库使用说明

云雾室型极早期火灾报警器在机场仓库使用报告说明1、项目概述:某长水机场位于某市官渡区长水村附近。

是中国面向东南亚、南亚和连接欧亚的继北京、上海虹桥和广州之后的第四大国家门户枢纽机场。

机场预计货邮吞吐量95万吨、飞机起降30.3万架次,货邮吞吐量230万吨、飞机起降45.6万架次。

被中国民航总局定位为“节约型、环保型、科技型和人性化的现代化绿色机场”,其中设计与应用处处体现了这一理念,如在其东航货运仓库采用的云雾室型极早期火灾侦测器在其中的应用就符合了这一定位。

那么云雾室型极早期火灾侦测系统有哪些优势,它是怎样满足机场物流仓库应用需求的呢?那接下来我们就来了解一下这款来自英国具有世界上第一无二侦测方式,被誉为火灾侦测器中的艺术品的云雾室型极早期火灾报警器。

云雾室型极早期火灾报警器有如下特点:1)探测方式采用了PVC管路采样的方式,无需敷设线路节约了线缆线材。

2)探测器部分集中于现场安装的主机内部,且前端探测部分为无源设备,达到了节能减排的目的。

3)云雾室型吸气式感烟火灾报警采用了世界上最先进的云雾侦测技术,能在烟产生之前就可以发现火灾的倪端,为保证保护区的安全,提供了最多的反应时间,极大的增强了被保护区与的安全性。

并且云雾室型采用的云雾室技术成功的解决了传统光电式侦测器灵敏度高误报率同时升高的难题,使得保护区不但可以在云雾室型运行的高灵敏度之下受到保护,又不用担心灰尘、雾气等不确定的环境因素造成探测器误报。

(文档由风行播放器暴风影音:整理)4)云雾室型吸气式感烟火灾报警在使用中为了维保人员后期维护方便,探测设置部分都在维保人员可以方便维护的地方,尤其是对于现场探测部分了维护,无需像传统点式侦测器一样需要接近侦测点进行维护,尤其像机场库房这样的高大空间,尤其像是冷库夹层这样特殊封闭的空间应用,顶棚设备维护的难度与危险性可想而知,而采用了云雾室型吸气式感烟火灾报警,吹扫及维护都可以在地面方便进行,充分体现了其人性化的关怀。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
N- 37-563-73 T 接用于 10 毫米毛细管。
N- 37-564-74 30mtr 线圈红 10 毫米毛细管取样管。
N- 37-565-75 30mtr 线圈不透明的 10 毫米毛细管取样管。
N- 37-566-76 圆锥形的头毛细管取样点。
N- 37-567-77 隐藏式毛细管取样点。
N- 37-568-78 分离的毛细管取样点。
电流的消耗 尺寸
Cirrus Pro200 + 允许侦测的最大区域 取样管的最大的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电源电压 电流的消耗 尺寸
550 mA---警戒 700 mA---警报 W ---440 毫米,H ---385 毫米,D ---144 毫米
2000m 2 或者一个单独防火区划 200m +(须经计算程序) 4 须经计算程序 15 毫米---25 毫米 20 ---29 伏特 DC 450 mA ---警戒 612 mA---警报 W ---440 毫米,H ---385 毫米,D ---144 毫米
3
主要组成部分
Cirrus Pro 侦测器
新 Cirrus Pro 系列提供一个可以解决几乎任何空气取样应用(取样系统工程要求)的形式。从 有最小显示功能的简单的低成本侦测器到有完全功能的液晶显示屏和内置的侦测器网络能 力的多管的扫描侦测器。
Cirrus Pro100 允许侦测的最大的区域 取样管的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电源电压 电流的消耗 尺寸 Cirrus Pro200 允许侦测的最大区域 取样管的最大的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电源电压 电流的消耗 尺寸 Cirrus Pro200D 允许侦测的最大区域 取样管的最大的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电流的消耗 尺寸 Cirrus Pro200DSC 允许侦测的最大区域 取样管的最大的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电源电压
Cirrus Pro 系列利用的是’Wilson 云雾室’的侦测原理,这种独特云雾室技术使 Cirrus Pro 能 够及早的侦测到火灾,而且是目前可提供的最多用途火侦测技术。 另外响亮的云雾室侦测 原理保证 Cirrus Pro 侦测器其误报机率降至最低,无论是对于蒸汽,凝结,湿度,高的气 流还是温度变化都不会影响侦测效果。 云雾室侦测器 - 操作策略 众所周知,当一种材料过热时,可以产生比可见光的波长更小的粒子,并且存在于正常的 周遭的环境之中。 Cirrus Pro 侦测器利用 Wilson 云雾室就可以发现在火灾初始等级产生的 亚微细粒粒子。 当来自被保护的空间的空气的样品透过一台离心鼓风机送到侦测器时,其部分被送进一个 增湿器。 在大约增湿到 100%的相对湿度的时候,这个样品将被导向云雾室,在那里,由 于迅速的真空膨胀导致冷却,水凝结到全部样本粒子上。 从而,热产生的粒子引起很多小水滴形成云雾,然后通过云雾室的测量系统计数。形成的 云雾的密度与粒子的数量成正比。 当达到一定密度之后,一个符合粒子密度的连续的信号 就会发出。 这个信号用来提供 4 阶段警报等级。
N- 37-555-73 25 毫米红 ABS 45 度弯头. 根据需要,保持到最少。
N- 37-554-72 25 毫米红 ABS 三通管 要求根据需要,保持到最少的分接。
N- 37-553-71 25 毫米红 ABS 端塞 1no。 每取样管末端必须要有。
N- 37-559-77 25 毫米红 ABS 插座 1no。 每取样管要求。
2
介绍
Cirrus Pro 侦测系统的定义
Cirrus Pro 侦测系统采用主动的侦测的方式,可以从侦测区域内抽取空气样本,来发现燃烧 所产生的粒子。 取样管通过连续抽气方法来获得含有燃烧粒子的空气样本,借助鉴定在空气中的燃烧粒子 的数量变化,来确定危胁等级,这一讯息将透过侦测器发出警报。 Cirrus Pro 云雾室型侦测器 不同于市面上其他的极早期烟雾侦测系统,利用’光学’的原理必须要有足够的烟雾产生才能 侦测火灾。
极早期火灾侦测系统的种类………………………………..……………………12 主要侦测取样系统………………………………..……………………………12 次要侦测取样系统…………………………………..…………………………13 局限的侦测取样系统…………………………………………………….…….14 风管侦测取样系统……………………………………………………………..15 箱体内的侦测取样系统…………………………..……………………………16
Cirrus Pro200DSC + 允许侦测的最大区域 取样管的最大的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电源电压 电流的消耗 尺寸
2000m 2 或者一个单独防火区划 200 米(须经计算程序) 4(在初始设定定义) 须经计算程序 15 毫米---25 毫米 20 ---29 伏特 DC 585 mA ---警戒 685 mA---警报 W ---440 毫米,H ---385 毫米,D ---144 毫米
2000m 2 或者一个单独防火区划 200 米(须经计算程序) 4 须经计算程序 15 毫米---25 毫米 416 mA ---警戒 585 Ma---警报 W ---360 毫米,H--- 215 毫米,D--- 144 毫米
2000m 2 或者一个单独防火区划 200 米(须经计算程序) 4(在初始设定定义) 须经计算程序 15 毫米---25 毫米 20 29 伏特 DC
7
Cirrus Pro 取样管测试点
取样管测试点指示要作为测试的功能,通常被安装在管路最末端的位置。 N- 37-570-00 25 毫米红 ABS 端塞’测试点’ 1no。 每取样管要求。
N- 37-571-01 2mtrs 完成隐藏式毛细管测试点 c/w T 片,取样管的 10 毫米的 2mtrs 以及隐藏式测试点。
Cirrus Pro Aspirating Fire Detector 通用设计指南
介绍…………………………………………………………………………………3 Cirrus Pro 极早期火灾侦测系统的定义………………………………….……3 Cirrus Pro---云雾室火灾侦测器…………………..…………………….……..3 云雾室侦测器 - 操作策略……………………………………………………….3
2000m 2 或者一个单独防火区划 100 米(须经计算程序) 1 须经计算程序 15 毫米---25 毫米 20 ---29 伏特 DC 295 mA 警戒--450 mA 警报 W ---285 毫米,H--- 215 毫米,D--- 144 毫米
2000m 2 或者一个单独防火区划 200 米(须经计算程序) 4 须经计算程序 15 毫米---25 毫米 20 ---29 伏特 DC 340 mA 警戒---500 mA 警报 W--- 360 毫米,H--- 215 毫米,D--- 144 毫米
6
Cirrus Pro 毛细管取样管和附件
N- 37-560-70 完成圆锥形的头毛细管 c/w T 片取样点, 10 毫米的 2mtrs 取样管和圆锥形的头取样点。
N- 37-561-71 完成隐藏式毛细管 c/w T 片取样点,取样管的 10 毫米的 2mtrs 并且为隐藏式取样点。 N- 37-562-72 完成分离的毛细管 c/w T 片取样点,取样管和分离的头取样点 的 10 毫米的 2mtrs。
5
Cirrus Pro – 取样管及附件
N- 37-550-68 3 米长度 25 毫米 o/d 红 ABS 取样管
N- 37-551-69 25 毫米红 ABS 接合插座 1no。 插座要求结合管每 3mtrs
N- 37-552-70 25 毫米红 ABS 90 度 长半径弯头 90 度弯头要求根据需要,保持到最少。
Cirrus ProRDP 每个网络最大的显示器的 32
数量
每个网络最大的侦测器的 32
数量
电源电压 电流的消耗
20 ---29 伏特 DC 85 mA ---警戒 95 mA---警报
尺寸
W ---215 毫米,H ---215 毫米,D ---47 毫米
注意︰ 所有的 Cirrus Pro 应该再一次以流力计算软件验证,以确认侦测器的类型以及的操
N- 37-558-76 红 ABS 管夹子 1no。 夹子/ 固定需要最大的每 1.2 mtrs。
N- 37-569-79ห้องสมุดไป่ตู้管夹 c/w 支撑
N- 23-039-37 样品洞警告卷标 - 1 卷 100 个标签 1no。 每取样点要求的标签。
N- 37-556-74 溶剂胶(250 ml 每罐具有完整刷子) 1no。每 100 个接合处需要 1 罐。
4
Cirrus Pro200D + 允许侦测的最大区域 取样管的最大的总长度 最大的管的数量 最大的取样口 取样管管径(外) 电源电压 电流的消耗 尺寸
2000m 2 或者一个单独防火区划 200 米(须经计算程序) 4
须经计算程序 15 毫米---25 毫米 20 ---29 伏特 DC 535 mA--- 警戒 707 mA---警报 W ---440 毫米,H ---385 毫米,D ---144 毫米
设计前考虑………………………………………………………..………………10 极早期火灾侦测系统的预期……………………………..……………………10 侦测器灵敏性……………………………………………..……………………10 背景粒子等级…………………………………………………………………. 11 需要'性能测试'……………………………………………………………….…11
主要组成部分………………………………………………………………………4 Cirrus Pro----侦测器……………………………………………….……………4 Cirrus Pro --- 电源单元…………………………………………………………5 Cirrus Pro - --取样管和附件……………………………………………………6 Cirrus Pro---毛细管取样管和附件……………………………..………………7 Cirrus Pro---取样管测试点……………………………………..………………8 应用………………………………………………………………………………9