空气压差传感器安装调试指引
Series MSX Pro Magnesense 差压传感器安装与操作指南说明书
Series MSX Pro Magnesense ® Differential Pressure TransmitterSpecifications - Installation and Operating InstructionsBulletin P-MSXP-AThe Series MSX Pro Magnesense ® Differential Pressure Transmitter is the professional differential pressure transmitter meeting stringent industry standards with innovative global product design. The device has exceptional stability for use in critical building performance applications with the popular versatility of our original Series MS2 Magnesense ® II transmitter. The MSX Pro simplifies the ordering process to deliver the desired configuration, which reduces product setup time. Pressure ranges of Pa, mm w.c., and in w.c. are available per device. All pressure ranges can be configured in unidirectional or bidirectional modes providing a total of 32 ranges. The MSX Pro transmitter can provide a linear pressure output or a linear velocity output with the square root extraction from the transmitter. Additional parameters have been included to expand the square root capability to calculate flow. Dual voltage and milliamp output signals can be used to provide control and equipment output signal verification.INSTALLATION Surface Mounting:Mount the transmitter on a vertical surface. The pressure sensor measurement is unaffected by orientation, but it is recommended the unit be mounted with the connections facing down to prevent moisture from entering either the pressure ports or the electrical cable entry. Attach the mounting flange to a flat surface using #8 x 1/2˝ pan head sheet metal screws. Do not over tighten.Duct Mounting (Universal model required):Mount the transmitter away from fans, corners, heating and cooling coils and other equipment that will affect the measurement of the pressure.1. To mount the transmitter, drill a .562˝ (12.70 mm) diameter hole into the duct. 2. Screw duct probe into back of housing. Insert transmitter probe into the duct.3. Mark location of mounting holes on duct using mounting flange as template. Drill holes.4. Attach mounting flange to duct with #8 x 1/2˝ pan head sheet metal screws. Do not over tighten screws.5. Place the included cap on the exterior positive pressure port.The Universal model can also be used as a standard wall mount transmitter. In this mode, do not use the duct probe and plug the port on the backside of the transmitterwith the included plug.1-29/32[48.43]1-29/32[48.43]ELECTRICALThe MSX Pro transmitter utilizes a 2-wire 4-20 mA Current Output , or a 3-wire 0-5 V / 0-10 V Voltage Output . It is also capable of Simultaneous Current and Voltage Output . The power and signals interconnect via a removable European-style four conductor terminal block, or optionally, via the included tooless terminal block. 2-Wire 4-20 mA Current OutputThe connections to the transmitter are made through terminals VDC and COM on the terminal block as shown in Figure 1. The terminal block is removable and each of the terminals are labeled next to the terminal block on the circuit board. Polarity is indicated by VDC and COM. See Figure 1.The maximum receiver load resistance (RL) for a given power supply voltage (Vps) is defined by the formula: Shielded 2-wire cable is recommended for control loop wiring. Ground the shield at the power supply end only.The receiver may be connected to either the negative or positive side of the loop, whichever is most convenient. Should polarity of the transmitter or receiver be inadvertently reversed, the loop will not function properly but no damage will be done to the transmitter.The maximum length of connecting wire between the transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 feet), it is desirable to select receivers with lower resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 feet, you can use a connecting lead wire as small as No. 22 ga.Selection of using a DC or AC power supply is made via the terminal block. See Figure 2 for DC Wiring. See Figure 3 for AC Wiring.The terminal block is removable and each of the terminals are labeled next to the terminal block on the circuit board. Positive polarity is indicatedby VOUT. AC/DC selection is made via the terminal block. If the polarity of the transmitter is inadvertently reversed, the unit will not function properly, but no damage will be done to the transmitter.The minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gage, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%.The output across VOUT and COM will be either 0-5 V, 0-10 V depending on the DIP switch setting. See DIP Switch Settings Section for more information.DC POWER SUPPLY 10-36 VDCV A CV D CC O MV O U TCURRENT RECEIVER+--+DC POWER SUPPLY 17-36 VDCVOLTAGE RECEIVER-++-V A CV D CC O MV O U T AC POWER SUPPLY 21.6-33 VACVOLTAGE RECEIVERV A CV D CC O MV O U T -+DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILLRESULT. SIMULTANEOUS OUTPUTS ARE NOT DESIGNED FOR AC VOLTAGE OPERATION.DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILLRESULT.Figure 1Figure 2: DC wiringFigure 3: AC wiringR L =V ps - 10.020 mA DC If equipped, the LCD must be removed before wiring. Pull the LCD directly away from the product to remove. Reinstall the LCD afterwiring is completed.Simultaneous Current and Voltage OutputThe terminal block is removable and each of the terminals is labeled underneath the terminal block on the circuit board. Positive polarity is indicated by VOUT. The VDC terminal and a DC power supply must be used for Simultaneous Current and Voltage Output. The voltage output and the power supply must have separate wire leads that are only joined at terminal 2 of the transmitter. Additional error may occur for the voltage output if a single wire is used or if the wires are joined at the power supply or receiver.For the current output, the maximum allowable loop resistance (wiring + receiver resistance) is dependent on the power supply. The maximum loop voltage drop must not reduce the transmitter voltage below 17 V. The maximum loop resistance (R MAX ) for a given power supply voltage (V PS ) can be calculated using the following equation:The equation uses 17.0 instead of 10.0 as seen in the equation earlier with Figure 1. This represents the minimum voltage supply which is higher on the simultaneous output configuration due to the requirements of the voltage outputs.Shielded 4-wire cable is recommended for control loop wiring. Ground the shield at the power supply end only. Should the polarity of the transmitter or receiver be inadvertently reversed, the unit will not function properly, but no damage will be done to the transmitter.For voltage outputs, the minimum receiver load is 1 kΩ. The resistance due to the wire should be low compared to the receiver load resistance. While the voltage at the terminal block remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to the receiver. For a 1% accurate gage, the resistance of the wires should be less than 0.1% of the value of the receiver load resistance. This will keep the error caused by the current flow below 0.1%.The output across VOUT and COM will be either 0-5 V or 0-10 V depending on the DIP switch setting. See DIP Switch Settings Section for more information.Power SupplyRefer to the following tables for the required supply rating.DIP SWITCH SETTINGSDIP switch settings are marked directly on the PCBA as shown in Figure 5. Switches are factory-set, based on the order configuration. You can also use a small screwdriver or pen to change the position of the switches.Key To DIP Switch SettingsSwitches are numbered 1 to 8 beginning on the left.DIP Switches 1 and 2 - Unit of Measure SelectionDIP Switches 1 and 2 work as a pair to select the unit of measure. V A CV D C C O M V O U T DC POWERSUPPLY 10-36 VDCVOLTAGE RECEIVERCURRENT RECEIVER+-+--+Figure 4: Simultaneous current and voltage output wiringDO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY WILLRESULT. SIMULTANEOUSOUTPUTS ARE NOT DESIGNED FOR AC VOLTAGE OPERATION.Figure 5 is a depiction of a 5 in w.c. pressure board. Other pressure boards, while similar, will vary from the below.There are no hazardous voltages if supplied power is within thespecified range. However, it is a good idea to shut control systemsdown while changing DIP switches to prevent erratic control system behavior.Figure 5: 5 in w.c. pressure boardR MAX =(V PS – 17.0) 20 mA DCDIP Switch 3 - Pressure vs Velocity/Flow Mode of OperationDIP Switch 3 toggles between pressure output vs velocity or flow output.• When the switch is in the OFF or down position, the device is in Pressure Mode.• When the switch is in the ON or up position, the device is in Velocity/Flow Mode. DIP Switch 4 - Voltage Output RangeVoltage output range can be either 0-10 V or 0-5 V depending on the position of DIP Switch 4.• When the switch is in the OFF or down position, the output will be 0-10 V• When the switch is in the ON or up position, the output will be 0-5 V.DIP Switch 5 - Unidirectional vs Bidirectional OutputDIP Switch 5 can be set to measure pressure in one direction (unidirectional) or in both directions (bidirectional).• When the switch is in the OFF or down direction, the transmitter will be set for uni-directional and will be 0 based (i.e. 0 to 5 in w.c.).• When the switch is in the ON or up position, the transmitter will be set forbidirectional and will be ± the maximum of the selected range (i.e. ±5 in w.c.). DIP Switch 6 - Response Time SelectionDIP Switch 6 toggles to select the desired response time.• When the switch is in the OFF or down direction, the transmitter response time will be instantaneous.• When the switch is in the ON or up direction, the response time will be 3 seconds. DIP Switches 7 and 8 - Maximum Range Selection (Pressure)DIP switches 7 and 8 work as a pair to select the maximum range output of the transmitter. Use the tables below to navigate pressure range selection. Alternatively, if using the device for velocity and flow, proceed to the next section.DIP Switches 7 and 8 - Maximum Range Selection (Velocity/Flow)DIP switches 7 and 8 work as a pair to select the maximum range output of the transmitter. Use the tables below to navigate velocity and flow range selection. CALIBRATIONThe transmitter security feature must be unlocked before calibration is accessible. See Section Program Menu-Menu Access Security. There is a 3 second delay from the time the zero or span calibration buttons are released until the time that the change in calibration takes place. This delay is used to prevent stress related offsets on the lower ranges.Zero CalibrationThe zero calibration can be set by applying zero pressure to both of the pressure ports and pressing the zero button for 3 seconds. If the LCD display is present, the display will read ZERO and then sequence back to the home display.The span calibration function allows the pressure value to be adjusted so that the currently applied pressure is the maximum configured pressure. This will in turn set the maximum analog output at the set pressure. It is recommended that the ZERO function be applied before performing a span. Apply the maximum desired pressure to the device, press and hold span for 3 seconds. If the LCD display is present, SPAN is displayed. The span function will be processed 3 seconds after the span button is released.For a positive span, apply pressure to the positive “+” port.LCD DISPLAYThe LCD comes with a housing cover, which contains a window. The display plugs into the pins on top of the circuit board. The LCD is 180° rotatable so that it will read properly if the device must be mounted with the connections facing up.The following error messages will appear if an LCD is present and the device is an error state.PROGRAM MENUHome MenuDuring normal operation, the display will be in the Home Menu and will display the current measured pressure and the engineering units.Menu Access SecurityBy default, a PIN code is not required to enter the configuration menus. However, if access to the menus needs to be restricted, follow the steps below.1. While in the Home Menu, press and hold the Zero and Span buttons until “PIN” is displayed.2. Press and hold the Zero and Span buttons until the current PIN setting isdisplayed (default is 0000).3. Use the Zero button to increment the selected digit (denoted by the caron ) orpress the Span button to select the next digit to the right.4. Any value between 0001 and 9999 will result in the requirement to enter the PINeach time the menu is entered. The value 0000 will disable the PIN entryrequirement.5. Press and hold the Span button until the next menu is displayed. PIN security setup is now complete.MAINTENANCE/REPAIRUpon final installation of the Series MSX Pro, no routine maintenance is required. The Series MSX Pro is not field serviceable and should be returned if repair is needed. Field repair should not be attempted and may void warranty.WARRANTY/RETURNRefer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Materials Authorization (RMA) number before shipping the product back for repair. Be sure to include a brief description of theproblem plus any additional application notes.This symbol indicates waste electrical products should not be disposedof with household waste. Please recycle where facilities exist. Check withyour Local Authority or retailer for recycling advice.DISPLAY ALL SEGMENTSHOME SCREEN (MODE = PRESSURE)FIRMWARE VERSION(MAY VARY)PIN MENUK-FACTOR MENUPRESSURE MENU (OUTPUT LOW MENU)PRESSURE MENU (OUTPUT HIGH MENU)PRESSURE MENU (ALARM LOW)PRESSURE MENU (ALARM HIGH)RESET MENUVELOCITY MENU(OUTPUT LOW MENU)VELOCITY MENU(OUTPUT HIGH MENU)RESET MENUMSX PRO FLOW SETTINGS FLOWCHARTFLOW MENU(AREA)FLOW MENU(OUTPUT LOW MENU)FLOW MENU(OUTPUT HIGH MENU)RESET MENUPrinted in U.S.A. 8/20FR# 444576-10©Copyright 2020 Dwyer Instruments, Inc.NOTES__________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________。
压力传感器安装调试说明书
压力传感器安装调试说明书一、前言为了确保压力传感器的安装信号稳定,准确监测压力状态并进行数据采集与处理,特编写此安装调试说明书。
本说明书旨在提供正确的操作步骤,以保证压力传感器系统的正常运行和有效性。
二、安装前准备1. 确认压力传感器型号和规格,验证其与所需安装应用的匹配程度。
2. 检查压力传感器的外观,确保无明显损坏和质量问题。
3. 根据安装环境和指示要求,选择适当的安装位置。
确保其与被测压力贴合并紧密连接。
4. 確保安裝位置周围区域整潔無障礙,便于施工人员進行操作。
三、安装步骤1. 按照被测压力管道的特性和要求,选择合适的接头和密封材料。
2. 清洁安装位置,确保无异物和杂质。
如需要,可使用酒精或清洁剂,但请注意不要使用腐蚀性物质。
3. 将压力传感器与被测压力管道连接。
在连接前,确保接头、密封件和传感器本体的清洁度。
4. 完成连接后,用扳手适当拧紧接头,确保密封性能。
四、传感器校验1. 安装完成后,先检查压力传感器与被测压力管道的连接是否牢固。
2. 通过液压或气压系统,逐步增加压力,观察传感器的响应情况。
确保传感器能准确读取压力变化并输出正确的信号。
3. 监测传感器与数据采集系统的连接是否正常。
可通过检验仪器或相应软件进行测试。
五、注意事项1. 安装过程中应确保施工人员操作安全,防止发生人员伤害和设备损坏。
2. 请避免过度拧紧接头,以免损坏传感器或被测压力管道。
3. 定期检查压力传感器,确保其连接可靠,并补充适量的润滑剂以保持正常工作。
4. 避免传感器长时间暴露于易燃、腐蚀性气体或液体环境中,以免影响传感器的性能和寿命。
5. 在使用过程中,如发现任何异常情况或故障,请立即停止使用,并联系售后服务部门进行维修或更换。
六、总结本安装调试说明书详细介绍了压力传感器的安装步骤和注意事项。
在安装过程中,请严格按照本说明书的要求进行操作,以确保安全和可靠性。
如有任何疑问或问题,请联系我们的技术支持部门。
我们将全力为您解决问题,保证压力传感器系统的正常运行。
压差传感器安装方法
压差传感器安装方法
压差传感器的安装方法可以根据具体的应用场景和设备来确定,下面是一般的安装步骤:
1.选择安装位置:根据需要测量的压差范围和实际应用场景,选择一个合适的安装位置。
通常,应选择在管道或容器的侧壁上,以确保正常的流体流动,并避免阻塞或漏损问题。
2.设备准备:按照压差传感器的规格和要求进行设备准备工作。
包括清洁传感器和连接部件,确保其无灰尘、油污或其他杂质。
3.连接传感器:使用适当的连接件将压差传感器安装在所选择的位置上。
根据传感器的设计,可以选择螺纹连接、法兰连接或其他合适的安装方式。
确保连接紧固,以防止泄漏。
4.调整传感器位置:根据需要调整传感器的安装位置,确保其与流体的流动方向垂直,并保持合适的距离。
避免传感器受到外部冲击或振动,以免影响测量结果。
5.连接电源和信号线:根据传感器的电路设计和接线要求,连接电源和信号线。
确保电源稳定和信号线的正确接地,以获得准确的测量结果。
6.测试和校准:在安装完成后,进行测试和校准工作。
使用适当的校准设备和程
序,确保传感器的测量结果与实际压差值相符合。
7.固定传感器:最后,使用适当的固定装置将传感器牢固地固定在安装位置上,防止其松动或移位,以确保长期稳定和可靠的使用。
请注意,在任何安装过程中,都要遵循安全操作规程,并由合格的技术人员进行安装和调试工作。
气压传感器及调压阀的安装(相对位置示意)
调压阀及气压传感器安装说明
一型号及参数
为了测量制动管路气压的动态变化,需要安装气压传感器,采用欧锐特科技生产的ORT-12型气体压力传感器,外形如图1所示,传感器的相关参数如表1所示。
气压传感器的位置在回馈制动调压阀之后,ABS调压阀之前,前后制动管路各有一个,在完成制动系统参数匹配与标定之后,气压传感器可以方便的拆卸,采用相应螺纹的螺栓将气压传感器的安装孔堵住,保证不漏气。
传感器电源及信号接口采用插拔式接头,在控制器附近及传感器附近各有一个接口。
图1
表1 ORT-12型气体压力传感器主要参数
参数名称参数值
量程0~1MPa
输出1~5V
响应时间1ms
工作温度-25℃~70℃
灵敏度温度系数0.01
二安装说明
如下图所示,回收制动的部件的安装位置。
图回收制动的部件在制动气路中的相对安装位置简图
从图中可见,气压传感器需要使用一个三通才能测量气路中的气压。
回馈制动调压阀需要串联在快放阀及继动阀的后面。
快放阀及继动阀原来的两个出口只使用一个,另一个堵住或接刹车灯/倒车灯传感器。
三通已经提供,需要工厂提供垫片,尺寸如附图。
压力传感器的正确连接与校准方法
压力传感器的正确连接与校准方法压力传感器是一种常见的工业测量仪器,通过量化介质的压力变化来输出电信号,用于测量压力。
然而,正确的连接和校准是确保压力传感器准确工作的关键。
本文将介绍压力传感器的正确连接和校准方法。
1. 连接方法压力传感器通常包含两个接口:电源接口和信号接口。
为了正确连接压力传感器,首先需要理解这两个接口。
电源接口通常需要连接到一个恒定的直流电源,以提供所需的电压,通常为3.3V或5V。
在连接电源之前,确保仔细查看压力传感器的规格书,以确定所需电压范围。
信号接口是连接到微控制器或数据采集系统的接口,以传输压力传感器输出的电信号。
常见的信号接口类型有模拟输出和数字输出。
模拟输出通过一个模拟电压信号来表示测量的压力值,通常为0-5V或0-10V。
而数字输出则通过串行通信协议(如I2C或SPI)输出压力值。
根据实际需求,选择适合的信号接口类型,并按照相应的接线方式连接到微控制器或数据采集系统。
在连接时,注意以下几点:1)使用合适的电缆进行连接,电缆的长度和材质应考虑信号传输的性能要求;2)尽量避免电缆与电源线、高压线等干扰源靠近,以减少干扰;3)连接时注意极性,确保电源和信号接口的正负极性正确。
2. 校准方法校准是保证压力传感器准确测量的关键步骤,下面介绍一种简单的校准方法。
首先,需要一台已知精确值的压力测量仪器(如校准泵),以提供参考压力值。
将该仪器连接到压力传感器的测量介质端口上。
接下来,按照以下步骤进行校准:1)将校准泵压力设置为已知值,记录校准泵的读数和压力传感器的输出电信号;2)持续改变校准泵的压力,记录对应的读数和电信号,确保覆盖整个测量范围;3)绘制读数和电信号之间的关系曲线;4)根据曲线拟合出校准方程,将传感器输出的电信号转换为对应的压力值。
校准完成后,可以使用该校准方程来进行实际压力测量。
需注意的是,校准应在实际应用前定期进行,以确保测量准确性。
此外,应根据实际情况选择合适的校准时间间隔,以平衡校准成本和准确性要求。
差压传感器的安装方法
差压传感器的安装方法引言差压传感器是一种广泛应用于工业控制和仪表领域的传感器,可用于测量流体中的压力差。
它具有灵敏度高、响应速度快、稳定性好等特点,在工程应用中得到了广泛的应用。
本文将介绍差压传感器的安装方法。
准备工作在安装差压传感器之前,我们需要准备一些必要的工具和材料:- 差压传感器- 密封垫片或硅脂- 电缆及接头- 合适的螺栓和垫片- 扳手和螺丝刀- 灯具或手电筒(用于光源)安装步骤以下是差压传感器的安装步骤:1. 确定安装位置:首先确定差压传感器的安装位置。
传感器应安装在能够准确反映流体压力的位置,避免安装在有振动、冲击或高温的地方。
2. 清洁安装位置:在安装之前,需将安装位置彻底清洁,确保表面没有灰尘、油污和其他杂物。
可以使用酒精或清洁剂擦拭表面。
3. 安装密封垫片:在传感器表面涂抹密封垫片或硅脂。
这有助于保护传感器,并确保传感器与安装位置之间的密封性。
注意,不要过度涂抹,以免影响传感器的测量精度。
4. 固定传感器:将差压传感器放置在安装位置上,并使用螺栓和垫片固定传感器。
根据情况使用扳手或螺丝刀适当地拧紧螺栓。
5. 连接电缆:将传感器的电缆与现场控制系统或仪表连接。
确保电缆连接可靠,避免松动或断开。
6. 安装附件:根据需要,可以安装附件,如温度补偿装置、防护罩等。
7. 检查安装质量:安装完成后,检查传感器的安装质量,确保传感器牢固可靠,并且与流体接点稳定。
8. 测试和校验:在使用差压传感器前,需要进行测试和校验。
使用专用设备或测试仪器对传感器进行校验,并根据校验结果调整传感器的零点和灵敏度。
注意事项在安装差压传感器时,需要注意以下事项:- 避免安装在高温或有振动的环境中,以免影响传感器的测量精度。
- 注意保护传感器表面,避免刮伤或损坏。
- 选择合适的螺栓和垫片,确保传感器的固定可靠。
不要过度拧紧螺栓,以免破坏传感器。
- 在连接电缆时,确保电缆连接牢固可靠,避免因松动而影响传感器的工作。
楼控传感器、阀门、DDC安装与调试
1.1.1调试和安装图纸(一)、传感器安装图纸以下是建筑设备监控系统中的典型传感器的安装图纸:1、室外温度传感器安装图纸:2、房间压差传感器安装图纸3、防冻开关安装图纸4、压差开关安装图纸5、空气压力传感器安装图纸6、水流开关安装图纸7、水压差传感器安装图纸8、水压力传感器安装图纸9、液位开关安装图纸(二)、典型阀门安装图纸(三)、控制器安装图纸1、PXC控制器安装图纸2、PXC modular &TX-I/O1.1.2调试指南(一)、调试应具备的条件(1)、受BAS监控的设备必须先手动调试通过;(2)、各设备机房必须有良好的照明和正确的电源;(3)、当涉及与其他有关厂家机电设备接口时,厂家必须有人配合;(4)、BA监控中心必须装修完整,清扫干净,并且有充足的照明和电源;(5)、系统调试的环境要求:温度0-49℃,相对湿度≤93%;(二)、调试工具(1)、手提电脑三台;(2)、对讲机若干;(3)、万用表若干;(4)、常用电工工具若干;(5)、标准温湿度计2台;(6)、标准压差计2台(7)、信号发生器2台;(三)、调试指南由于建筑设备监控系统结构特殊、设备分散,线路较长等原因,整个建筑设备监控系统按照以下指南来完成调试:建筑设备监控系统将按照如下的流程进行调试:(1)、BAS设备与受控设备的单体调试○1、传感器调试由于传感器的精度是工厂在生产时,由其材料、原理、制作工艺以及校正设备的精度而定,因此,如无专业设备及专门机构一般不对传感器的精度作现场校正,如有特殊要求的客户,则在订购设备时尽量选择带出厂校验报告的型号或厂家。
如客户对传感器的精度有疑问则可用分开测试DDC及传感器的方法来确认设备的好坏或精度,对DDC检测时,可用标准电阻箱或信号发生器等设备,来模拟传感器的信号,观察DDC中的响应是否正确,然后再用万用表来检测传感器的输出,与标准值比较,观察结果是否在允许范围内。
在BA系统中常用的传感器由以下几种,现分别介绍这几种传感器的调试方法:第一类:1000欧姆RTD型温度传感器:此种传感器如544-339,常用于新风温度、送风温度及回风温度等,水管型的有544-577,常用于冷冻冷却水系统及热交换系统,在调试前可先用万表测量其电阻值,与标准的电阻温度对照表比较,读出此传感器的温度值与标准温度计测得的值比较,判断是否在精度范围内,以决定是否更换此传感器。
压差传感器安装方法
压差传感器安装方法压差传感器主要用于测量管道或容器中两个不同位置之间的压力差。
它可以帮助监控或控制流体或气体的流动,广泛应用于工业生产、环境监测、流体控制等领域。
以下是压差传感器的安装方法:1. 安装位置选择压差传感器的准确度和可靠性与其安装位置密切相关。
首先要选择合适的安装位置,一般在管道或容器中的两个不同位置之间。
对于液体压差传感器,应选择压力差较大且流速较小的位置,避免流动干扰;对于气体压差传感器,应选择压力差较小且压力稳定的位置。
2. 安装支架制作根据所选择的安装位置,制作合适的支架来固定压差传感器。
支架的材料应具备足够的强度和稳定性,能够承受压力差,同时避免振动和干扰。
支架的设计应考虑到安装和调整的便捷性,以方便后续的维护和调试。
3. 清洁安装区域在安装压差传感器之前,应确保安装区域干净整洁。
清除杂物、灰尘和油污等污染物,以防止对传感器的影响。
同时,还要确保传感器与管道或容器的密封面光滑平整,以保证传感器的性能。
4. 安装传感器将压差传感器固定在支架上,并采取适当的固定方法。
通常使用螺栓、法兰等方式进行固定,确保传感器的牢固稳定。
在安装过程中,要注意不要过度拧紧螺栓,否则可能导致传感器损坏。
5. 连接管路根据实际情况选择合适的管路连接方式,将管道或容器与压差传感器连接起来。
连接过程中要遵循正确的操作方法,确保连接紧密,防止泄漏和松动。
同时,还要注意管路的布置,避免弯曲、拉伸和挤压等对传感器的影响。
6. 封装保护为了保护压差传感器免受外部环境的影响,可以将传感器进行封装保护。
常见的封装形式有防护壳、密封胶等,可根据具体情况选择合适的封装方式。
封装后,还应进行防水、防尘和防腐处理,以延长传感器的使用寿命。
7. 调试和测试安装完成后,需进行相应的调试和测试,以确保压差传感器的准确度和灵敏度。
可以通过外部设备接口或控制器进行校准和调整,确保传感器的测量精度符合要求。
同时,还要进行压力泄漏和连接可靠性测试,以确保系统的安全性和稳定性。
Series DX差压传感器操作指南和安装说明说明书
The Series DX is a pressure switch that makes a contact output based on the differential pressure between two pressure sources. Unit incorporates a SPDT snap switch in a weatherproof, type 4X enclosure. Series DX features low differential pressure set points with high single pressure limit.OPERATING PRINCIPLEThe DX uses opposing diaphragms to sense the high and low pressure. A pivot mechanism transfers the difference of the two pressures to the switch.SPECIFICATIONSService:Compatible gases and liquids.Wetted Materials: Connection: Brass; Diaphragm: Fluoroelastomer.Temperature Limits:30 to 140°F (-1 to 60°C).Pressure Limits:200 psig (13.8 bar).Enclosure Rating:Weatherproof UL type 4X (IP65).Repeatability:±2% of full range. Switch Type:SPDT snap switch.Electrical Rating:Electrical Connection:Removable terminal block.Conduit Connection:0.871˝ diameter hole for 1/2˝ conduit fitting.Process Connection:1/4˝ NPT female. Continuous single side only pressure should not exceed 1.25 x full differential range.Mounting Orientation:Ports on horizontal plane, ±10°.Set Point Adjustment:External screw.Housing Materials:Body: Aluminum; Housing: Polycarbonate; Cover: 300 SS.Vibration and Shock:Set point repeats after 2.5 Gs, 5 to 500 Hz. Set point repeats after a 15 Gs, 10 millisecond duration.Altitude Limit: 6560 ft (2000 m).Humidity Limit: 80% (non-condensing).Pollution Degree:2.Environment:Intended for indoor and outdoor use. Weight:1 lb 3 oz (0.54 kg).Agency Approvals:CE, UL.Example SeriesConstruction Wetted Materials Process Connection Circuit Options RangeOptionsDX DXW W111115315321234M SSTPRESET DXW-11-153-2-M Differential Pressure SwitchWeatherproofBrass/Fluoroelastomer 1/4˝ NPT SPDT2.5 to 10 psi 10 to 25 psi 25 to 50 psi 50 to 75 psiStainless Steel tag Preset set pointAdjustable Rangepsid (bar)2.5 to 10 (0.17 to 0.69)10 to 25 (0.69 to 1.72)25 to 50 (1.72 to3.45)50 to 75 (3.46 to 5.17)At High Set Point 2.5 (0.17)3.5 (0.24)6.0 (0.41)8.0 (0.55)Approximate DeadbandsFixed Deadbandpsid (bar)At Low Set Point 1.5 (0.10)2.5 (0.17) 3.5 (0.24) 6.0 (0.41)UNPACKINGRemove the DX from the shipping carton and inspect for damage. I f damage is found, notify the carrier immediately. INSTALLATIONInsure that the process fluid is compatible with the wettedDo not exceed the maximum device ratings.Insure that the system is not pressurized before installing orremoving this device or other objects from the system.The DX is to be mounted with the pressure connections horizontal ±10°. For pipe mounting, mount the unit from the pressure connections to the pipe. Make sure the piping is properly supported to handle the weight of the pressure switch. For surface mounting, mount the unit to the selected surface using the mountingear holes provided using two #6 or #8 screws. See the Figure 2 for mounting hole spacing.Make sure that connections are connected to the proper port. The high pressure port is marked with the “+” sign and is on the left side of the unit with the label side facing you. The low pressure port is marked by the “-“ sign and is the right side of the unit. Piping or tubing should always be turned into the pressure port, do not turn the pressure switch. When installing the piping or tubing into the switch always use a wrench on the flats of the pressure connection. Use pipe thread sealant tape or other suitable pipe joint compound when making the pressure connection.ELECTRICAL CONNECTIONA SPDT snap action switch is provided. The output logic is shown in Table 1.Power must be off while wiring connections are being made.Installation must be made in accordance with local codes andElectrical connections are made to the removable terminal block inside the enclosure. Remove the terminal block from the circuit board for wiring if desired.Feed stripped and tinned leads through the conduit opening and connect them as shown in Figure 2. 250V @ 60C 14 to 24 AWG / 2.5 to .25 mm2wiring with PVC or equivalent insulation with 94-V0 or FV-0 flammability rating is recommended for the switch. Replace terminal block after wiring. The DX provides one 0.871˝ diameter hole for 1/2˝ conduit fitting. The conduit connections must be made such that condensation is not allowed to enter the sensor housing. I f necessary install a conduit breather drain in a separate conduit body to prevent buildup of moisture. For weatherproof applications, install directly to conduit or usethe optional cable gland accessory.SETPOINT ADJUSTMENTThe set point is adjusted with a standard slotted head screw driver.1) Remove rubber plug over set point adjustment screw located on the right side of the unit (with the label side facing you).2) Insert the screw driver to turn the set point adjustment.3) A clockwise rotation is an increase in differential pressure set point and a counterclockwise rotation is a decrease in differential pressure set point. (The set point screw can be turned too far as to fall out; do not turn the screw to the point that there are no longer any female threads visible in the switch body). 4) Using a pressure source and pressure gauge adjust the set point screw to the set point desired while monitoring the contact output.5) Once desired set point is achieved replace set point adjustment cover. Design a fail-safe system that takes into consideration thepossibility of switch failure, power failure, and operator error.MAINTENANCE & REPAIRI nspect and clean switch with water or damp cloth as needed. Disassembly or modifications made by the user will void the warranty and could impair the continued safety of the product. f repair is required obtain a Return Goods Authorization (RGA) number and send the unit, freight prepaid, to the address below. Please include a detailed description of the problem and conditions under which the problem was encountered. Dwyer Instruments, Inc.Attn: Repair Department 102 Indiana Hwy 212Michigan City, IN 46360Description Direct current Alternating currentProtective conductor terminalSymbol Explanation of Symbols:~PublicationIEC 50417 - 5031IEC 50417 - 5032IEC 50417 - 5019Figure 2: Mounting Hole Dimensions©Copyright 2010 Dwyer Instruments, Inc.Printed in U.S.A. 10/10FR# M3-443822-00。
系统感应器空气气流感应器安装与维护指南说明书
INSTALLATION AND MAINTENANCE INSTRUCTIONS3825 Ohio Avenue, St. Charles, Illinois 601741-800-SENSOR2, FAX: 630-377-6495/www.systemsensor.caBEFORE INSTALLINGPlease read the System Smoke Detectors Application Guide , which provides detailed information on detector spacing, placement, zoning, wiring, and spe-cial applications. Copies of this application guide are available from System Sensor. Observe guidelines for NFPA 72 or CAN/UL C S524 (depending on location).NOTICE : This manual should be left with the owner/user of this equipment.IMPORTANT : Use only with compatible ULC-listed detector heads for proper system function. The detector used with this base must be tested and main-tained regularly following requirements of NFPA 72 or CAN/ULC S536 (de-pending on location). The detector should be cleaned at least once a year.IMPORTANT : Utiliser uniquement avec des détecteurs homologuées UL C pour le bon fonctionnement du système. Le détecteur utilisé avec cette base doit être testé et entretenu régulièrement en conformité avec les exigences de la norme CAN/ULC S536. Le détecteur doit être nettoyé au moins une fois par an.GENERAL DESCRIPTIONThe B501-WHITE, B501-IV , and B501-BL are plug in detector bases intended for use in an intelligent system with screw terminals provided for power (+ and –), and remote annunciator connections. Communication takes place over the power lines (+ and –). BASE TERMINALS No. Function1 Power (–), Remote Annunciator (–)2 Power (+)3 Remote Annunciator (+)FIGURE 1. TERMINAL LAYOUTSPECIFICATIONS Base Diameter: 4.0" (10.2 cm)Base Height: 0.74" (18.8 mm) Operating T emperature: Refer to applicable sensor Operating T emperature Range using the Base/Sensor Cross Reference Chart at Electrical Ratings – includes base and detector Operating Voltage: 15 to 32 VDC Standby Current: 150 µA Listings: UL268, ULC S529I56-3738-004MOUNTINGThis detector base mounts directly to 4" square with plaster ring, 31/2" octa-gon, 50 mm, 60 mm, and 70 mm centers.INSTALLATION AND WIRING GUIDELINES (SEE FIGURE 2)All wiring must be installed in compliance with all applicable local codes and any special requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.For signal wiring (the wiring between interconnected detectors and modules), it is recommended that the wiring be no smaller than 18 A WG (0.823 mm²). Wire sizes up to 12 A WG (3.31 mm²) may be used with the base.Alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance allowed before wiring the detector loops.Make wiring connections by stripping about 3/8" (10 mm) of insulation from the wire end (use strip gauge molded in base). Then slide the wire under the clamping plate and tighten the clamping plate screw. Do not loop the wire under the clamping plate. (See Figure 3.)Check the zone wiring of all bases in the system before installing the detec-tors. This includes checking the wiring for continuity, correct polarity, ground fault testing and performing a dielectric test.The base includes an area for recording the zone, address, and type of detec-tor to be installed at that location. This information is useful for setting the detector head address and for verification of the detector type required for that location.Once all detector bases have been wired and mounted, and the loop wiring has been checked, the detector heads may be installed in the bases. FIGURE 2. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP(–)(+)+-U L /U L C L i s t e d C o m p a t i b l eC o n t r o l P a n e lCAUTION: Do not loop wire under terminal 1 or 2. Break wire run to provide supervision of connections.MISE EN GARDE : Ne pas boucler le fil sous la borne 1 ou 2.Couper le fil pour assurer la supervision des connexions.CLASS A OPTIONAL WIRINGREMOTE ANNUNCIA TOR(–)(+)321321321C0133-03B501-WHITE, B501-IV, and B501-BL 4" Plug-in Detector Bases1 I56-3738-004 03/07/2018FIGURE 3.C0473-00TAMPER-RESIST FEATURENOTE: Do not use the tamper-resist feature if the removal tool is to be used.The detector base includes a tamper-resist feature that prevents removal of the detector without using a small screwdriver or similar tool.T o activate this feature, use needle-nose pliers to break the tab on the detector base as shown in Figure 4A. Then, install the detector.T o remove the detector from the base once the tamper-resist feature has been activated, insert a small-bladed screwdriver into the small hole on the side of the base and push the plastic lever away from the detector head. (See Figure 4B). This allows the detector to be rotated counterclockwise for re-moval.The tamper-resist feature can be defeated by breaking and removing the plas-tic lever from the base. However, this prevents the feature from being used again.FIGURE 4A. ACTIVATE TAMPER-RESIST FEATUREBREAK TAB AT DOTTED LINE BYC0132-00FIGURE 4B. DETECTOR REMOVALUSE SMALL-BLADED SCREWDRIVER TO PRESS C0132-01System Sensor warrants its enclosed smoke detector base to be free from defects in ma-terials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector base. No agent, representative, dealer, or employee of the Company has the au-thority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector base which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: Honeywell, THREE-YEAR LIMITED WARRANTY12220 Rojas Drive, Suite 700, El Paso TX 79936 USA. Please include a note describing themalfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall theCompany be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.Please refer to insert for the Limitations of Fire Alarm SystemsREMOTE ANNUNCIATOR (RA100Z)The remote annunciator is connected between terminals 1 and 3 using the spade lug terminal packed with the remote annunciator. The spade lug termi-nal is connected to the base terminal as shown in Figure 5.It is not acceptable to have three stripped wires under the same wiring ter-minal unless they are separated by a washer or equivalent means. The spade lug supplied with the model RA100Z is considered an equivalent means. See Figure 2 for proper installation.FIGURE 5. CONNECTION TO REMOTE ANNUNCIATOR TERMINALC0116-00System Sensor® is a registered trademark of Honeywell International, Inc.NOTE: B501-WHITE, B501-IV , and B501-BL replace the previous model num-bers B501 and B501A; all are functionally the same.2 I56-3738-004©2018 System Sensor. 03/07/2018。
压差传感器安装方法
压差传感器安装方法压差传感器是一种用于测量液体或气体中压力差异的装置。
它通常由传感器本体和连接设备组成,通过测量两个点之间的压力差来检测流体的流速或流量。
在实际应用中,压差传感器的安装方法非常重要,可以影响到传感器的测量精度和稳定性。
首先,压差传感器的安装位置需要选择在流体管路中的合适位置。
一般情况下,应将压差传感器安装在流体管路的上游和下游两个点之间,以便测量流体在这两个点之间的压力差。
在选择安装位置时,需要考虑管道的直径、材质和流体的性质,确保传感器能够准确地测量压力差。
其次,压差传感器的安装需要注意避免流体中的杂质和颗粒物对传感器的影响。
在安装位置周围可以加装过滤器或隔离器,以阻止杂质和颗粒物进入传感器内部,保证传感器的正常运行和测量精度。
另外,压差传感器的安装还需要考虑流体的温度和压力。
在高温或高压环境下,需要选择耐高温和高压的传感器,并采用合适的密封材料和连接方式,以防止流体泄漏或传感器损坏。
在具体的安装过程中,需要按照厂家提供的安装说明和技术要求进行操作。
通常情况下,安装包括以下几个步骤:1. 清洁安装位置:将安装位置周围的管道清洁干净,确保没有杂质和污垢会影响传感器的正常运行。
2. 安装支架或固定装置:根据传感器的安装方式和要求,安装支架或固定装置,以固定传感器在合适的位置。
3. 安装传感器:将传感器安装在支架或固定装置上,并根据要求使用密封材料对传感器和管道进行密封,防止流体泄漏。
4. 连接导管:将传感器的测量端口与上游和下游的测量点通过导管连接起来,确保压差传感器能够准确地测量流体的压力差。
5. 调试和校准:在安装完成后,需要进行传感器的调试和校准工作,以确保传感器能够正常工作和准确测量压力差。
调试和校准的具体方法和要求可以参考厂家提供的相关资料。
需要注意的是,在安装过程中,应仔细检查传感器和连接管路,确保所有部件安装正确,连接紧固,没有松动和漏气现象。
此外,还需要考虑传感器的维护和保养工作,定期对传感器进行检查和清洁,确保其正常运行和稳定性。
压差传感器安装使用注意事项
1. 传感器应安装在尽量高的位置。 2. 传感器应按垂直方向安装并且压力输入口朝下。压力输入口的安装倾角应小于15°。 3. 压力端口推荐初次安装方式:最大允许径向安装力为高压端80N,低压端40N。传感器 正常工作时最大允许径向力为高压端40N, 低压端20N。 4. 传感器应在合适位置或在指定支架上安装。传感器应使用M6 紧固螺钉安装,拧紧力矩 为:8±2Nm。 5. 连接传感器的橡胶软管和金属导管应连续下降,不应出现U型结构。 6. 确保无水汽和其他杂质在传感器内聚积。 7. 传感器电气连接应避免曝露在过高温度环境下。 8. 传感器应安装在可以避免灰尘和泥土污染的位置。 9. 传感器应远离发动机上的高电压线缆和设备。传感器线缆应避免与高压线缆平行布置。 10. 安装位置应保证传感器的维护和拆卸方便,以便于日后的维护。 11.排气温度受发动机的大 小和安装位置影响。所以客户在确定导管长度时,应实地测量传感器端的尾气温度, 并确保温度在传感器的工作范围内(-40~140℃)。 12. 如果客户需要直接将传感器安装到发动机上时,需要事先评估一下发动机舱温度。
洁净室压差调试方法
洁净室压差调试方法一、引言洁净室是一种控制室内环境污染的特殊空间,通常用于需要高度洁净的生产、实验和加工过程。
而洁净室的核心指标之一就是压差,它可以有效控制空气流动,防止污染物进入洁净区域。
本文将介绍洁净室压差调试的方法和步骤。
二、洁净室压差调试方法1. 准备工作在开始调试洁净室压差之前,需要先进行一些准备工作。
首先,确保洁净室的其他设备和系统已经安装并正常运行。
其次,检查洁净室的门窗密封性能,确保其能有效阻隔外界空气进入洁净室。
最后,准备好所需的测试仪器和设备,如压差计、风速计等。
2. 测量压差将压差计置于洁净室的两个不同区域,分别测量室内的静压差和外界的静压差。
静压差是指洁净室内部与外部的气压差异,通常以帕斯卡(Pa)为单位。
测量时,要确保压差计的传感器位置正确,并保持稳定,避免外界干扰。
3. 调整风量根据测得的压差数据,调整洁净室的风量。
如果室内的静压差大于外界的静压差,说明洁净室内的风量过大,需要减小送风量。
反之,如果室内的静压差小于外界的静压差,说明洁净室内的风量过小,需要增加送风量。
通过逐步调整送风量,使室内的静压差接近或等于外界的静压差。
4. 检查过滤效果调试完成后,需要对洁净室的过滤效果进行检查。
使用颗粒计数器或采样器,对洁净室内的微粒浓度进行检测。
根据洁净室的等级要求,确定测得的微粒浓度是否符合标准。
如果不符合标准,可能是由于过滤器的损坏或堵塞导致的,需要及时更换或清洗过滤器。
5. 定期监测和维护洁净室压差的调试是一个持续的过程,在调试完成后,仍需定期监测和维护洁净室的压差。
定期测量室内外的压差,并根据测得的数据,及时调整送风量,确保洁净室的正常运行。
同时还要定期检查过滤器的状态,及时更换或清洗,保证过滤效果。
三、结论洁净室压差调试是确保洁净室正常运行的重要环节。
通过测量压差、调整风量,以及检查过滤效果,可以有效控制洁净室内部的空气流动,防止污染物进入洁净区域。
定期监测和维护洁净室的压差,可以保持洁净室的稳定性和可靠性。
空气压差开关安装方法
空气压差开关安装方法一、概述空气压差开关是一种用于感知管路中气压差变化的开关装置,通常被用于控制系统中的空气压力变化。
合理的安装空气压差开关可以保证系统的稳定运行,并在一定程度上确保系统的安全性。
本文将详细介绍空气压差开关的安装方法,以供参考。
二、安装前的准备工作1. 确定安装位置:在进行空气压差开关的安装之前,首先需要确定最佳的安装位置。
通常情况下,建议将空气压差开关安装在管路上,以便能够准确感知管路中的气压差变化。
还需要考虑到安装后是否能够方便进行维护和检修。
2. 准备安装工具:在进行安装工作之前,需要准备好所需的安装工具,如螺丝刀、扳手等。
还需要检查安装所需的管路连接件和密封件是否齐全。
3. 安全检查:在进行安装之前,需要对管路进行安全检查,确保管路没有损坏或者泄漏的情况,以免安装完成后出现问题。
三、安装步骤1. 确定安装位置:根据系统的实际情况,确定空气压差开关的安装位置,并用标尺或者其他工具将位置标记出来,以便后续进行固定。
2. 安装支架:根据标记的位置,选择合适的支架,将支架固定在管路上,确保支架牢固可靠。
3. 安装空气压差开关:将空气压差开关安装在支架上,并根据说明书或者技术要求连接好管路。
在连接管路时,需要注意管路的安装方向,确保管路畅通无阻。
4. 连接电气线路:根据空气压差开关的电气连接要求,将电气线路连接到空气压差开关上,并确保接线牢固可靠。
5. 调试和检查:完成安装后,需要进行调试和检查,确保空气压差开关能够正常感知管路中的气压变化,并能够准确地输出信号。
还需要检查安装处是否存在漏气、漏电等安全隐患,并及时做好防护措施。
四、注意事项1. 注意安装方向:在安装空气压差开关时,需要注意其安装方向,确保管路连接正确,以免造成误差。
2. 防止振动干扰:在安装过程中,需要注意避免机械振动对空气压差开关产生干扰,如有需要,可以采取一些减震措施。
3. 注意安全防护:在安装过程中,需要注意自身安全防护,确保不会因为操作过程中的不慎造成伤害。
22ADP-154F双通道空气压差传感器说明书
双通道空气压差传感器带两个独立测量系统的差压变送器。
具有8个不同的测量范围可选及Modbus通讯功能。
主要监测空气及其他非可燃性、非腐蚀性气体的过压、欠压或压差,HVAC系统中的典型应用涵盖空气过滤网、风机、以及压差系统等场合。
防护等级:IP65/NEMA 4X。
型号概述型号测量范围 [Pa] [Pa]通信有源压力输出信号流量有源输出信号过载压力显示类型22ADP-154F-100...2500Modbus RTU0...5 V, 0...10 V0...5 V, 0...10 V40 kPa LCD显示技术参数电气参数额定电压AC/DC 24 V额定电压范围AC 19...29 V / DC 15...35 V额定功耗AC 4.3 VA额定功耗DC 2.3 W电气接线可拆卸弹簧加载端子排,最大 2.5 mm²线缆连接电缆格兰头, 带2 x ø6 mm防拉扣数据总线通讯通信Modbus RTU节点数量Modbus见接口描述功能参数传感器技术压电式测量元件应用空气多量程8个测量范围可选电压输出 2 x 0...5 V, 0...10 V, 最小阻抗 10 kΩ传感器有源输出信号注意事项可通过开关选择 0...5/10V输出显示LCD显示, 29x35 mm带背光容积流量测量值: m³/h, cfm (可参数化)压力测量值: Pa,inch WC (可参数化设置)典型响应时间自适应 0.8秒或4.0秒测量参数测量值压差流量测量介质空气和非腐蚀性气体压力参数压力测量范围设置设置范围 [Pa]范围 [inch WC]出厂设置S00...25000 (10)S10...20000 (8)S20...15000 (6)S30...10000 (4)S40...5000 (2)S50...2500 (1)S60...1000...0.4S7-100...100-0.4...0.4压力参数精度与参考设备相比的偏差量程 ≤500 Pa 时: ±5 Pa 量程 >500 Pa 时: ±10 Pa长期稳定性±2.5% FSO (满量程输出) / 4 yr.材质电缆格兰头PA6, 黑色外壳盖板:PC ,橙色底座:PC ,橙色密封:NBR70,黑色抗紫外线安全参数防触电保护等级IEC/EN III ,安全特低电压 (SELV)电源 UL 认证Class 2 Supply 电气防护等级IEC/EN IP65NEMA/UL 防护等级NEMA 4X附件UL Enclosure Type 4X 欧盟一致性CE 标志IEC/EN 认证IEC/EN 60730-1 和 IEC/EN 60730-2-6质量标准ISO 9001UL 认证cULus 遵循 UL60730-1A/-2-6,CAN/CSA E60730-1运行方式类型 1额定冲击电压0.8 kV 安装模式独立安装控制污染等级3环境湿度最大 95% 相对湿度,无结露环境温度-10...50°C [15...122°F]介质温度-10...50°C [15...122°F]技术参数安全注意事项该设备设计用于特定的暖通空调系统中,在专属场合之外的应用是无法确保其使用的。
气体传感器---压力传感器准确安装介绍
气体传感器压力传感器的安装很重要,如果安装的不正确,就会不能正工作,耽误时间和工作效率,如何正确的安装压力传感器呢?下面就来介绍下。
通常高温熔体气体传感器压力传感器的损坏都是由于其安装位置不恰当而引起的,如果将气体传感器强行安装在过小的孔或形状不规则的孔中,就有可能造成气体传感器的震动膜受到冲击而损坏,选择合适的工具加工安装孔,有利于控制安装孔的尺寸,另外,合适的安装扭矩有利于形成良好的密封,但是如果安装扭矩过高就容易引起高温熔体压力气体传感器的滑脱,为防止这种现象发生,通常在传感器安装之前在其螺纹部分上涂抹防脱化合物。
通过适当的仪表,在普通大气压和标准温度条件下,核实压力传感器的频率反应值。
核实压力传感器的编码与相应的频率反应信号的正确性。
为了确定压力传感器的编号和具体安装位置,需按充气网的各个充气段来考虑。
压力传感器必须沿着线缆进行安装,最好安装在线缆接头处。
每条线缆的始端和末端分别安装1每条线缆的分支点应装1个,如果两个分支点相距较近(小于100 m),可只装1个。
线缆敷设方式(架空、地下)改变处应装1个对无分支的线缆,因垒线的线缆程式一致,压力传感器的安装隔距不大干500m,并使其总数不少于4个。
为了便于确定压力传感器故障点,除在起点安装压力传感器外,距起点150~200m处,还要另外安装1个当然在设计中,一定要考虑经济与技术的因素,在不需要安装压力传感器的地方,则应不必安装。
如果安装孔的尺寸不合适,高温熔体压力传感器在安装过程中,其螺纹部分就很容易受到磨损,这不仅会影响设备的密封性能,而且使传感器不能充分发挥作用,甚至还可能产生安全隐患。
只有合适的安装孔才能够避免螺纹的磨损(螺纹工业标准1/2-20UNF2B),通常可以采用安装孔测量仪对安装孔进行检测,以做出适当的调整。
以上就是正确安装压力传感器的方法,希望你能学会哦!!。
Series 668 差压传感器规格与安装操作指南(Bulletin A-30-668)说明书
Series 668 Differential Pressure TransmitterSpecifications - Installation and Operating InstructionsBulletin A-30-668Ø5/32 [3.97]Our low cost Series 668 Differential Pressure Transmitter is capable of measuring low pressures with a ±1% accuracy ideally suited for proper building pressurization and air flow control. Transmitters can withstand up to 10 psig overpressure with no damage to the unit. Variable capacitance sensor design provides excellent sensitivity and long-term stability. Compact, lightweight design makes installation simple and easy. Units also feature reverse-polarity protection.INSTALLATION MountingThe 668 Series is designed for mounting in either a switch box or by using the two (2) holes that are provided on the housing. Optimum performance is obtained by isolating the instrument from vibration and providing relatively clean, dry ambient air to the pressure ports. In most cases, preferred installation is withthe baseplate mounted vertically and located on a relatively flat surface in a junction box or attached to a nearby beam.CAUTION: The axis most sensitive to vibration is the one perpendicular to the mounting base. Avoid mounting with maximum vibration along the axis.Pressure FittingTwo (2) 3/16˝ O.D. pressure fittings are supplied for pressure connection with 1/4˝ push-on tubing. Both the positive (high) pressure port and the reference (low) pressure port are located on the top face of the unit, labeled High and Low respectively. For best results (shortest response times), 3/16˝ I.D. tubing is suggested for tubing lengths up to 100 feet long, 1/4˝ I.D. for tubing lengths up to 300 feet, and 3/8˝ I.D. for tubing lengths up to 900 feet.®ELECTRICAL CONNECTIONSThe Series 668 Differential Pressure Transmitter is a loop-powered 4-20 mA current output unit. The current flows into +EXC. terminal and returns back to the power supply through the -EXC. terminal. the power supply must be a DC voltage source with a voltage range between 12 and 30 VDC measured between terminal +EXC. and -EXC.The unit is calibrated at the factory using a 250 Ω load at 28 VDC.Notes:Minimum Supply Voltage (VDC) = 12 + 0.02 x (resistance of receiver plus line).Maximum Supply Voltage (VDC) = 30 + 0.004 x (resistance of receiver plus line). CALIBRATIONThe 668 series is factory calibrated and should require no field adjustment. However, both zero and span adjustments are provided. Whenever possible, any zero and/or span offsets should be corrected by software adjustment in the user’s control system. Use the zero and span adjustments on the 668 Series only if absolutely necessary. The 668 series is calibrated in the vertical position at the factory. For use in other orientations, position the unit and follow the zero adjustment procedure listed below. Pressure ranges are fixed and cannot be changed in the field.Zero AdjustmentWhile monitoring the current output with both pressure ports open to atmosphere, the zero may be adjusted. For unidirectional pressure ranges, turn the zero adjustment screw until a reading of 4 mA (±0.15 mA) is achieved.Span Adjustment (Complete the zero adjustment before setting span)Span on full scale output adjustments should only be performed by using an accurate pressure standard (electronic manometer, digital pressure gage, etc.) with at least comparable accuracy to the 668 series (<±1% full scale). With full scale pressure applied to the high pressure port (reference port open to atmosphere) adjust span to achieve 20 mA output.Example 1: Unidirectional pressure range of 0 to 1 in w.c. Apply 1.00 in w.c., adjust span to 20 mA.Notes: The input is reverse-voltage protected. The output is internally protected against damage is shorted to ground. Recheck all connections before applying power. MAINTENANCEAfter final installation of the Series 668 Differential Pressure Transmitter, no routine maintenance is required. A periodic check of system calibration is recommended. These devices are not field repairable and should be returned if recalibration or other service is required. Contact customer service to obtain an RGA number. Pleaseinclude a clear description of the problem plus any application information available.©Copyright 2019 Dwyer Instruments, Inc.Printed in U.S.A. 7/19FR# 443095-00 Rev. 4。
变压范围空气差压传感器安装与维护指南说明书
Maintenance InstructionsSERIES 500VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTERINDEX1. INSTALLATION2. COMPRESSED AIR SUPPLY3. FLOW MEASURE CONNECTIONS4. VESSELS LEVEL MEASURE CONNECTIONS4.1 ATMOSPHERIC PRESSURE VESSELS CONNECTION4.2 DEPRESSION DEVICE CALIBRATION4.3 PRESSURE VESSELS CONNECTION4.4 ELEVATOR CALIBRATION5. CALIBRATION6. MAINTENANCE6.1 DYNAMIC RESTRICTION CLEANING6.2 NOZZLE CLEANING7. DISASSEMBLING7.1 DIAPHRAGM REPLACEMENTIn case of mounting or operation problems,pleasecontact our Local Agent or Service DepartmentOMC s.r.l. - Via Galileo Galilei, 18 - 20060Cassina de Pecchi (MI) - ITALYTel.:(+39)02.95.28.468-Fax:(+39)****************************1. INSTALLATIONThe variable range differential pressure transmitter Series500is designed for horizontal,vertical or upside-down installation.The transmitters series 550 H, 550 L e 550 HH (Fig.1.1) are supplied with a clamp for installation on a 2" pipe. The transmitters series 550 FH e 550 FHH (Fig.1.2) are provided with a DN80 flange for direct mounting. Note.When mounting the unit make sure to leave sufficient free space aside the transmitter for zero adjustment and cover removal.2. COMPRESSED AIR SUPPLY(see Fig. 2.1)The pneumatic connections(1/4"NPT)areidentified by"IN"(air supply input20psi)and"OUT"(control signal output3÷15psi).Thepneumatic instrumentation operation dependson the purity of the air supply.A filter,generallyan integrated filter,must be installed in the air pressure relief system upstream to the transmitter.To prevent rusting,use only pneumatic connections in non-ferrous material (copper,nylon or polyethilene).The horizontal supply line should run towards the instrument with a minimal2%slope.The connection of the supply line to the compressed air manifold must be made in the upper part of the tubing to keep condensate from entering the instrument. If necessary,a moisture trap can be installed upstream to the filter to remove any water or oil in the air supply.For a correct operation of the pressure reducer filter,the minimal air pressure must be set at min. 2.8-3bar.We advise against the indiscriminate use of a single reducer supplying many instruments,since abrupt variations in air consumption,due to the simultaneous operation of several instruments, might adversely affect the operation of each transmitter.Fig.1.1Fig. 2.1 COMPRESSED AIR SUPLLYFig.1.23. FLOW MEASURE CONNECTIONSIn the transmitters series 550H,550L and 550HH the process connections are screwed 1/2"NPT and are identified by "+"and "-".For better maintenance operation integrated Manifolds must be installed (see Fig.2.1).Connect the pressure tap upstream to the measure flange to the transmitter input (+)and the pressure tap downstream to the measure flange to the transmitter input (-).Accuracy in the flow measurement is obtained by connecting the transmitter as in fig. 2.3, 2.4and 2.5according to the working fluid (vapour, liquid, air/gas).The diameter of the horizontal supply line should be min.20times the diameter upstream to the measure flange (d) and 10 times the diameter downstream to the measure flange (D). See Fig. 2.1FLOWFig. 2.1Fig. 2.3VAPOUR CONNECTIONSFig. 2.4LIQUID CONNECTIONSFig. 2.5AIR - GAS CONNECTIONSto the Transmitterto the Transmitter to the Transmitter4. VESSELS LEVEL MEASURE CONNECTIONSIn the transmitters series550H,550L and550HH the process connections are screwed1/2"NPT and are identified by "+" and "-".In the transmitters550FH and550FHH one of the process connections is flanged DN80(+)and the other is screwed 1/2"NPT (-). See Fig.4.4.1 ATMOSPHERIC PRESSURE VESSELS CONNECTIONFor atmospheric pressure vessel,connect the zero level tap of the vessel to the transmitter connection(+). Make sure that the connection(-)is free.See fig.4.The transmitter pressure tap must be below the zero level of the vessel.Note. If "Z" is minor than "Y" the transmitter must be provided with a depression device.Fig.4.2 DEPRESSIONDEVICE4.2 DEPRESSION DEVICE CALIBRATION1) Set the vessel to zero level3) Use the depression screw (Fig.4.2) to obtain a 3psi transmitter outputFig.4.4 ELEVATIONDEVICE4.4 ELEVATOR CALIBRATION1) Set the vessel to zero level 2) Fill it with liquid (W)3) Use the elevation screw (Fig.4.4) to obtain a 3 psi transmitter output4.3 PRESSURE VESSELS CONNECTIONFor pressure vessels,connect the transmitter as in fig.4.3.It must be provided with an elevation device (fig.4.4) since the transmitter output signal would be different from 3 psi at zero level.Note.Y=(Z multiplied by the specific weight of the measure liquid )divided by (the specific weight of the compensation liquid)5. CALIBRATION (Fig.5)Calibration of the transmitter is necessary in case a change of range is required,or if the unit has been removed for cleaning or part replacement.THE FOLLOWING CALIBRATION PROCEDURE IS TO BE PERFORMED BY AUTHORIZED PERSONNEL ONLY.For accurate calibration proceed as follows:1) Apply a 20 psi air supply.2)Connect the transmitter output to a manometer with scale amplitude sufficient for calibration to be carried out3)Connect the transmitter pressure tap(+)to a manual pressure regulator controlled by a manometer with scale amplitude sufficient for calibration to be carried out.4) Keep the pressure tap (-) free to atmospheric pressure5)Loosen the nut(36),place the range setting ring(19)as indicated by the scale alongside the range rod and tighten nut (36).6) With instrument at zero differential pressure, adjust screw (23) until the output reads 3 psi.Note.In case the diaphragm has been removed,proceed as follows:remove bottom plug(34),insert into the opening a1/4"Allen wrench and loosen locknut.Adjust zero screw and tighten nut.Pay attention not to move the force bar from its normal position.In case of output pressure change,loosen again locknut,retighten and mount the plug(1).If output pressure still differs more than0.4psi,it indicates that diaphragm is not perfectly aligned with the body. Provide therefore for alignment.7)Apply to pressure tap(+)a pressure equal to required range.If output value is less than15psi,move ring (19) upwards, or vice versa.8) Repeat steps 6 and 7 until desired accuracy is obtained.2729351514162036193022232425181732111101213642821 269313233 Fig.5696. MAINTENANCEIn normal operating conditions the transmitter Series500does not require specific maintenance.The pneumatic instrumentation operation depends on the purity of the air supplied.Daily bleed the filter in the air supply line until any water, air or other impurities are completely expelled.6.1 DYNAMIC RESTRICTION CLEANING (Fig.5)Dust and dirt in the air supply might adversely affect the correct operation of the transmitter.For cleaning, proceed as follows:1) Eliminate supply to transmitter.2) Remove screw (64) and clean by means of a Ø 0.15 mm steel wire, as shown in Fig. 6.1.3) If the capillary orifice is obstructed, clean it with a bath in trichloroethylene and a blow of compressed air. Before fastening screw (64), we recommend lubricating O-Rings by applying a coat of silicone lubricant.Fig.6.1 Dynamic Restriction Cleaning6.2 NOZZLE CLEANING (Fig.5)1) Eliminate supply to transmitter2) Engage nut (29) and remove nut (26).3) Remove the pipe connected to relay (69).4) Clean the nozzle by means of a Ø 0.6 mm steel wire, as shown in Fig.6.2.5) If the nozzle is obstructed, clean it with a bath in trichloroethylene and a blow of compressed air.Fig.6.2 Nozzle cleaning7. DISASSEMBLINGNormal transmitter operation does not require removal of parts other than those described in the previous paragraph.NOTE.THE FOLLOWING DIAPHRAGM REPLACEMENT PROCEDURE IS FOR EMERGENCY ONLY AND IS TO BE PERFORMED BY AUTHORIZED PERSONNEL ONLY.7.1 DIAPHRAGM REPLACEMENT (Fig. 7.1)1) Cut off transmitter from process.2) Open vent screw (31) and drain nut (32) on both sides.3) Remove the 4 nuts (2). Do not pull bolts (33) out of the body.4)Remove the bottom plug(1).Insert a1/4"Allen wrench into the opening and loosen the locking nut without completely uncrewing it.5) Remove the diaphragm (6) and the Teflon rings (5).6) Replace diaphragm and perform the calibration procedure indicated in paragraph 5.Fig.7.1 Diaphragm Replacement。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
ASD1600 CWU
ASD1600 CWU
高架地板 接正压
H
接正压
0.5H 0.8X
X
压差传感器压力检测软管的安装
空调机组安装于机房内单侧
不能将空气压力探测点放置在有出风口的 地板下方附近。 此检测点必须安 装在没有空气流 动的房间内
接负压
压差传感器安装于室内或地板下方 1、压差传感器的连接线必须使 用0.75mm2三芯屏蔽线并穿电 线管 2、软管内径Ø = 5.5 mm 3、 软管必须安装在镀锌钢管或 塑料电线管内,以防软管被硬 物扎破或有折弯而影响空气压 力的检测 4、检测点必须垂直于空气的流 向以便能够检测到空气静压 EAIO板
不能将空气压力探测点放置在有出风口的 地板下方附近。 此检测点必须安 装在没有空气流 动的房间内
接负压
压差传感器安装于室内或地板下方 EAIO板 1、压差传感器的连接线必须使 用0.75mm2三芯屏蔽线并穿电 线管 2、软管内径Ø = 5.5 mm 3、 软管必须安装在镀锌钢管或 塑料电线管内,以防软管被硬 物扎破或有折弯而影响空气压 力的检测 4、检测点必须垂直于空气的流 向以便能够检测到空气静压 EAIO板
空气压差传感器 安装指引
Page 1
压差传感器参数
配件编号:M26174 型号:984M523304
984M 5 2 3 类型 IP 保护等级 可配置压力范围 压力单位 压差传感器 IP 54 带电线接口M16x1.5 0 ... 100 Pa (1.0 mbar) 0 ... 250 Pa (2.5 mbar) Pascal
Page 5
压差传感器接线
4 3 2
SA GOห้องสมุดไป่ตู้Y
Switching output, npn Ground GND Output signal 0 … 10 V / 4 ... 20 mA
1
G
Supply voltage 24 VAC/ VDC
Page 6
压差传感器压力检测软管的安装
空调机组安装于机房内两侧 接负压
此检测点必须安 装在没有空气流 动的房间内
接负压
压差传感器安装于室内或地板下方 EAIO板
EAIO板
ASD1600 CWU
ASD1600 CWU
高架地板 接正压
H
接正压
0.5H 0.8X
X
压差传感器压力检测软管的安装
空调机组安装于独立空调机房内单侧
不能将空气压力探测点放置在有出风口的 地板下方附近。
压差传感器安装于 室内或地板下方 EAIO板
ASD1600 CWU
H
高架地板 接正压 X 0.5H 0.65X
压差传感器与EAIO板的接线
压差传感器连接至EAIO板的接线端子 连接线为0.75mm2三芯屏蔽线并穿电线管
压差传感器接线端子 1: Input(24VAC/DC) 2: Output 3: Ground(G0) 连接线的屏蔽线 电控箱内接线端子 电控箱内接线端子排X2的A1 EAIO板的X1引脚的第2个:AIN6 EAIO板的X1引脚的第3个:GND 电控箱内接线端子排X0
此检测点必须安 装在没有空气流 动的房间内
接负压
1、压差传感器的连接线必须 使用0.75mm2三芯屏蔽线并穿 电线管 2、软管内径Ø = 5.5 mm 3、 软管必须安装在镀锌钢管 或塑料电线管内,以防软管被 硬物扎破或有折弯而影响空气 压力的检测 4、检测点必须垂直于空气的流 向以便能够检测到空气静压
3
0 4
信号输出和电源
显示屏 接线方式
4 ... 20 mA or 0 ... 10 V, 3线 24 Vac/Vdc, 带开关
无显示屏 通过螺纹接线排接线
Page 2
压差传感器尺寸
Page 3
压差传感器安装
软管内径Ø = 5.5 mm 软管要求:25 kPa [250 mbar] P1 = 正压 P2 = 负压 P1 + P2 = 压差
ASD1600 CWU
H
高架地板 接正压 X 0.5H 0.65X
压差传感器压力检测软管的安装
空调机组安装于独立空调机房内两侧
不能将空气压力探测点放置在有出风口的 地板下方附近。
接负压
1、压差传感器的连接线 必须使用0.75mm2三芯 屏蔽线并穿电线管 2、软管内径Ø = 5.5 mm 3、 软管必须安装在镀 锌钢管或塑料电线管内 ,以防软管被硬物扎破 或有折弯而影响空气压 力的检测 4、检测点必须垂直于空 气的流向以便能够检测 到空气静压
Page 4
压差传感器参数设定
闭合 默认跳线 压力范围 反应速度 不使用 输出信号 备用 跳线 M=模式 S=设定 指示灯 0…10 V 4…20 mA 低 0 ... 100 Pa 慢 1s 高 0 ... 250 Pa 快 100ms 断开
Offset Calibration偏移误差校正 This function can be used to correct the zero-point deviation (offset) of the output signal in depressurized state (example: to 0 V/4mA at zero Pa). Disconnect the unit from the pressure by opening both hose nozzles or removing the hoses. Then press the "M" button for 5 s. Setting of Switching Output This function is used to set the switching output to "switched through" for a pressure you have defined. Apply the pressure or pressure differential at which the switching output is to be connected. Then press the "S" button for 5 s until the LED flashes quickly (= value is saved). The LED lights up as soon as the defined pressure is reached or exceeded.