消防应急照明和疏散指示系统技术标准3篇

合集下载

《消防应急照明和疏散指示系统技术标准》

《消防应急照明和疏散指示系统技术标准》

《消防应急照明和疏散指示系统技术标准》消防应急照明和疏散指示系统技术标准。

消防应急照明和疏散指示系统是建筑物内部的重要设施,对于保障人员生命安全和财产安全起着至关重要的作用。

为了规范消防应急照明和疏散指示系统的技术标准,提高其可靠性和有效性,特制定本标准。

一、系统设计与布局。

1. 消防应急照明和疏散指示系统应根据建筑物的功能、结构和人员密集程度进行合理设计和布局,确保在火灾等紧急情况下能够为人员提供足够明亮的照明和清晰的疏散指示。

2. 照明和指示系统的布设应符合建筑消防设计规范,合理设置照明灯具和指示标识,确保全面覆盖和清晰可见。

3. 系统设计应考虑到建筑物内部的特殊环境和结构,采用合适的照明灯具和指示标识,避免光污染和视觉干扰。

二、设备选用与安装。

1. 消防应急照明系统应选用符合国家标准的LED照明灯具,具有低能耗、长寿命、高亮度等特点,能够在紧急情况下提供稳定可靠的照明。

2. 疏散指示系统应选用清晰明确的指示标识,采用防水防尘、耐高温、耐腐蚀的材质,确保在恶劣环境下仍能正常使用。

3. 系统设备的安装应由具有相关资质和经验的专业人员进行,确保设备固定牢靠、连接可靠、线路整洁,避免因设备故障导致照明和指示失效。

三、系统联动与监控。

1. 消防应急照明和疏散指示系统应与建筑消防控制系统联动,能够实现火灾报警后自动启动,保障人员疏散安全。

2. 系统应配备相应的监控设备,能够实时监测照明和指示设备的运行状态,及时发现并排除故障,确保系统的可靠性和稳定性。

四、维护与管理。

1. 消防应急照明和疏散指示系统的设备应定期进行维护和检查,确保设备的正常运行和性能稳定。

2. 系统的管理应建立健全的档案记录和应急预案,对设备运行情况和维护记录进行详细记录,定期进行演练和检查,提高系统的应急响应能力。

五、总结。

消防应急照明和疏散指示系统技术标准的制定和执行,对于提高建筑物内部的消防安全水平具有重要意义。

通过合理设计和布局、设备选用与安装、系统联动与监控以及维护与管理等方面的要求,能够有效提高系统的可靠性和有效性,保障人员在紧急情况下的生命安全和财产安全。

{技术规范标准}重消防应急照明和疏散指示系统技术规范

{技术规范标准}重消防应急照明和疏散指示系统技术规范

{技术规范标准}重消防应急照明和疏散指示系统技术规范一、引言重消防应急照明和疏散指示系统是指在火灾等突发情况下,为人员提供安全疏散和应急照明的系统。

本技术规范旨在规范重消防应急照明和疏散指示系统的设计、施工、验收和维护等工作,确保其在突发火灾等情况下的安全可靠性。

二、系统设计要求1.系统范围:重消防应急照明和疏散指示系统应覆盖建筑的各个疏散通道、出口以及公共区域,并达到必要的照明要求。

2.设计原则:(1)基于人员疏散需求,合理布置疏散通道,并确保通道畅通、救援设施易于操作;(2)考虑建筑特点和功能划分,合理规划疏散组织和指示,使人员能迅速熟悉疏散路线;(3)技术设备和设施选择应符合国家或地方相关规定标准,并考虑易用性、可靠性和维护性。

三、系统施工要求1.施工前准备:施工前应全面了解设计要求,并确保所需设备和材料的质量符合国家或地方的标准要求。

2.施工细节:(1)安装疏散指示标志:按照设计要求,在适当的位置安装疏散指示标志,并确保其易于辨识、清晰可见;(2)设置应急照明灯具:根据设计要求,在疏散通道的合适位置设置应急照明灯具,确保其亮度和覆盖范围符合国家或地方标准;(3)接线与测试:对系统的电线、电缆等进行正确的接线,并进行必要的测试和检验,确保其连接正常、可靠;(4)配置备用电源:为确保在断电情况下系统的正常运行,应配置符合要求的备用电源,并进行合理布置和测试。

四、系统验收要求1.验收前准备:在系统施工结束后,进行系统的检查和测试,并记录相关数据和结果。

2.验收标准:(1)照明亮度符合国家或地方相关标准要求;(2)疏散指示标志的位置、大小、内容和颜色符合国家或地方相关标准要求;(3)疏散通道、出口等的设置符合设计要求,并符合国家或地方相关标准要求;(4)疏散通道的畅通情况符合设计要求;(5)系统的电线、电缆等连接正确、可靠。

五、系统维护要求1.定期检查和维护:按照相关规定,定期对系统进行检查和维护,并记录维护情况。

消防应急照明及疏散指示系统技术规范标准

消防应急照明及疏散指示系统技术规范标准

消防应急照明和分散指示系统技术规范1 总则为了合理设计消防应急照明和分散指示系统,提升消防应急照明和分散指示系统的施工质量,保证系统正常运转,保证在发生火灾时人员顺利逃生和消防作业,拟订本规范。

本规范合用于新建、改建、扩建、内装饰和改变使用性质的工业与民用建筑内设置的消防应急照明和分散指示系统的设计、施工、查收与保护;不合用于生产和存贮火药、炸药、弹药、火工品等有爆炸危险的场所。

消防应急照明和分散指示系统的设计,一定依据国家有关目标、政策,针对使用对象的特色,做到安全合用、技术先进、经济合理。

消防应急照明和分散指示系统的设计、施工、查收与保护,除切合本规范外尚应履行国家有关标准、规范规定。

2 术语消防应急照明和分散指示系统Fire emergency lighting system为人员分散和发生火灾时仍需正常工作的场所供给照明和分散指示的系统,由各种消防应急灯具及有关装置构成。

消防应急灯具Fire emergency luminaire为人员分散、消防作业供给照明和标记的各种灯具,包含消防应急照明灯具、消防应急标记灯具和消防应急照明标记灯具。

消防应急照明灯具Fire emergency lighting luminaire为人员分散、消防作业供给照明的消防应急灯具。

消防应急标记灯具Fire emergency indicating luminaire用图形和 / 或文字达成下述功能的消防应急灯具。

a)指示安全出口及其分散方向;b)指示楼层、逃难层及其余安全场所;c)指示禁止入内的通道、场所及危险品寄存处。

消防应急照明标志灯具Fire emergency lighting&indicating luminaire同时具备消防应急照明灯具和消防应急标记灯具功能的消防应急灯具。

自带电源型消防应急灯具Fire emergency luminaire powered by self contained battery电池、光源及有关电路装在灯具内部的消防应急灯具。

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准消防应急照明和疏散指示系统是建筑物内部重要的安全设施,其技术标准的制定和执行对于保障人员生命安全具有重要意义。

本文将就消防应急照明和疏散指示系统技术标准的相关内容进行详细介绍。

首先,消防应急照明系统的设计应符合国家相关标准,确保在火灾等紧急情况下能够提供足够的照明,使人员能够清晰地看到疏散通道和安全出口。

照明系统的亮度、照射范围、灯具布局等都需要符合标准要求,同时还需要保证系统的稳定性和可靠性,以确保在紧急情况下能够正常工作。

其次,疏散指示系统也是消防安全中不可或缺的一部分。

疏散指示系统应当设置在建筑物内部的显眼位置,指示明确、清晰,能够引导人员快速、安全地撤离现场。

系统的指示标识应当符合国家标准,颜色醒目、文字清晰,能够在各种光线条件下都能够清晰可见。

此外,消防应急照明和疏散指示系统的供电方式也是需要重点考虑的问题。

系统应当采用备用电源或者紧急照明电池等设备,以确保在主电源故障时,系统仍然能够正常工作。

同时,还需要考虑系统的自动测试和报警功能,及时发现并排除故障,保证系统的可靠性。

最后,消防应急照明和疏散指示系统的安装和维护也是至关重要的环节。

安装应当由具有相关资质的专业公司进行,并且需要严格按照国家标准和设计要求进行。

对于系统的日常维护和定期检测也是必不可少的,只有确保系统的正常运行,才能够在紧急情况下发挥作用。

总的来说,消防应急照明和疏散指示系统技术标准的制定和执行,对于保障人员生命安全具有重要意义。

只有严格按照标准要求设计、安装和维护系统,才能够在紧急情况下发挥应有的作用,保障人员的生命安全。

希望相关单位和个人能够重视这一问题,确保消防应急照明和疏散指示系统的正常运行,为人员的生命安全提供有力保障。

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准

主要内容介绍
3. 系统设计 3.5 非集中控制型系统的控制设计 1 系统手动应急启动设计
手动操作应急照明集中电源或应急照明配电箱的应急启 动按键(钮) 控制逻辑:
1) 灯具的光源由节电模式转入应急点亮模式 2) 应急照明集中电源转入蓄电池电源输出; 3) 应急照明配电箱切断主电源输出。
主要内容介绍
和配电设计方案
➢ 3.根据各区域的疏散预案确定该区域的控制逻辑和
控制时序
➢ 系统与其他建筑疏散设施有机的结合 ➢ 科学 、有效的指导人员的安全疏散
修订思路及原则
➢ 简化系统架构 、控制逻辑的设计原则 ➢ 1.根据建 、构筑物的规模 、使用性质及日常管理及
维护难易程度选择系统的类型
➢ 2.基于分散控制 、集中监管的原则 , 简化系统的架
援行动提供必要的照度条件及正确的疏散指示信息的 消防系统
2. 消防应急照明及疏散指示系统的分类和组成 按照消防应急灯具的控制方式的不同 , 消防应急照
明及疏散指示系统分为集中控制型系统和非集中控制 型系统两种类型
主要内容介绍
2. 消防应急照明及疏散指示系统的分类和组成 2. 1 集中控制型系统
系统设置应急照明控制器 , 由应急照明控制器集中 控制并显示应急照明集中电源或应急照明配电箱及其 配接的消防应急灯具工作状态的消防应急照明和疏散 指示系统。
《消防应急照明和疏散指示系统技术标准》 GB51309-202X
内容简介
《消防应急照明和疏散指示系统技术标准》
■ 规范主编部门: 公安部 ■ 规范主编单位: 公安部沈阳消防研究所 ■ 参编单位: 上海市公安消防总队 、广东省公安
消防总队 、 中国建筑设计院有限公司等有代表 性的设计院 、科研院所 ■ 202X年7月10 日由住房城乡建设部批准发布; 自 202X年3月1 日起实施

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准消防应急照明和疏散指示系统是建筑物内部的重要设施,其作用在于在火灾等紧急情况下为人员提供安全疏散的必要条件。

为了确保这一系统的正常运行和有效性,制定了一系列的技术标准,以保障人员生命财产的安全。

首先,消防应急照明和疏散指示系统的技术标准要求其在建筑物内部的布置应符合相关的国家标准和规定。

照明设备应当布置在疏散通道上方,以保证在火灾等紧急情况下能够提供足够的光照,方便人员疏散。

同时,疏散指示系统的标识应当明确、醒目,能够清晰地指引人员朝向安全出口。

其次,在技术标准中还规定了消防应急照明和疏散指示系统的供电方式和备用电源的要求。

系统应当采用可靠的供电方式,保证在停电情况下仍能正常工作一段时间,以保障人员的安全疏散。

同时,备用电源的设置也是必不可少的,以应对主电源故障或其他突发情况。

此外,技术标准还要求消防应急照明和疏散指示系统的设备应当具备防水防尘、抗震抗冲击等特性,以保证在各种恶劣环境下仍能正常工作。

设备的可靠性和稳定性是保障系统正常运行的重要保障。

最后,技术标准还规定了系统的日常维护和检测要求。

定期的维护和检测工作是保证系统长期有效运行的关键,只有在日常维护和检测工作到位的情况下,系统才能在紧急情况下发挥应有的作用。

综上所述,消防应急照明和疏散指示系统技术标准的制定对于保障人员在紧急情况下的安全疏散起到了至关重要的作用。

通过严格遵守技术标准的要求,能够有效地提高系统的可靠性和稳定性,最大程度地保障人员生命财产的安全。

因此,各相关单位在建设和维护消防应急照明和疏散指示系统时,务必严格遵守相关技术标准的要求,确保系统的正常运行和有效性。

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准一、前言消防应急照明和疏散指示系统(以下简称“消防照明系统”)是指为在火灾等紧急情况下维护场所内照明和疏散指示所设置的系统。

其性能及质量的优劣直接关系到人民生命财产安全。

为了规范消防照明系统的设计、施工和维护,保障消防设施的有效运行,制定本标准。

二、术语和定义1、消防照明系统:专门为火灾等紧急情况下提供照明及疏散指示的设施。

2、灯具:发光元器件及支架,供安装和使用的成套照明装置。

3、疏散指示灯具:指示疏散设施及相关信息的灯具。

4、紧急照明灯具:无需启动电源或在主电源故障状态下能够持续照明的灯具。

5、联动:指消防照明系统与消防控制系统的数据互通,实现协同工作的过程。

6、自动切换:在主电源故障时,灯具自动切换到备用电源供电的过程。

7、手动切换:在主电源故障时,由人工操作控制灯具切换至备用电源供电的过程。

8、独立电源:消防照明系统的备用电源。

三、系统设计1、适用范围本标准适用于各类公共场所、建筑物、地下商场、娱乐场所等建筑物内消防照明系统的设计。

2、设计准则2.1 疏散指示应覆盖整个建筑物内,保证在火灾发生后人员能够快速、有序地撤离。

2.2 灯具的数量应满足建筑物内的照明要求,并应根据消防控制系统和建筑物自身的特点进行合理布置。

2.3 紧急照明灯具应在不依赖于主电源、手动切换或自动切换的情况下,最长程度持续照明15min。

2.4 消防照明系统应具备联动功能,能够与消防控制系统实现数据互通查控。

3、系统布局图消防照明系统的设计需要制定系统布局图,并在图纸上注明各灯具的名称、型号、数量和布置位置。

4、灯具的选型依据消防照明系统的照明、疏散指示及自动切换等要求,应选用符合国家标准和行业标准的灯具及其附件。

5、备用电源的选型消防照明系统的独立电源应符合国家标准及行业标准,满足自动切换需求。

备用电源容量按照消防设施应急预留电力的要求进行设计。

四、系统施工1、施工单位应具备从事消防照明系统设计、施工、维修等工作的相应资质。

消防应急照明和疏散指示系统规范

消防应急照明和疏散指示系统规范
详细描述
根据规定,系统的照明亮度应符合国家相关标准,如《消防应急照明和疏散指示系统》中的规定。具体来说,系 统的照明亮度应能够在各种紧急情况下(如火灾、地震等)保持足够的亮度,以帮助人员识别逃生路线和指示标 志。此外,系统的亮度还应根据不同的使用场景和场所进行调整,以满足实际需要。
指示准确度要求
总结词
定期对指示标志进行检查,确保 其完好无损、清晰可见。
及时修复
如发现指示标志有损坏或模糊不 清的情况,应及时进行修复或更
换。
清洁保养
定期对指示标志进行清洁保养, 保持其整洁美观,提高疏散引导
效果。
04
CHAPTER
系统性能要求
照明亮度要求
总结词
照明亮度是消防应急照明和疏散指示系统的重要性能指标,要求系统在紧急情况下提供足够的亮度,确保人员能 够清晰地看到指示标志和逃生路线。
定制化与人性化
针对不同场所和人群的需求,消防应急照明和疏散指示系 统将趋向定制化和人性化,以满足不同场所的特殊要求和 使用体验。
THANKS
谢谢
定义与范围
定义
消防应急照明和疏散指示系统是在火 灾或其他紧急情况下,为人员提供照 明和疏散指示的设备系统。
范围
本规范适用于新建、改建和扩建的建 筑物中的消防应急照明和疏散指示系 统的设计、安装和维护。
02
CHAPTER
消防应急照明系统规范
照明灯具选择
01
02
03
照明灯具类型
应选择高效、低功耗的 LED灯具,具有较长的使 用寿命和稳定的照明性能。
消防应急照明和疏散指示系统 规范
目录
CONTENTS
• 引言 • 消防应急照明系统规范 • 消防疏散指示系统规范 • 系统性能要求 • 安全注意事项 • 结论

消防应急照明和疏散指示系统检测与维护范本(3篇)

消防应急照明和疏散指示系统检测与维护范本(3篇)

消防应急照明和疏散指示系统检测与维护范本消防应急照明和疏散指示系统是保障人员在火灾等紧急情况下安全疏散的关键设施之一。

为了确保该系统的正常运行和有效性,在日常工作中必须进行定期检测和维护。

本文将介绍消防应急照明和疏散指示系统的检测与维护范本。

一、检测与维护的目标检测与维护的目标是确保消防应急照明和疏散指示系统在火灾等紧急情况下能够正常运行,提供有效的照明和指示,保障人员的安全疏散。

二、检测与维护的内容1. 系统设备的检测与维护(1)定期检查系统的配电箱、电缆、开关等设备,确保其完好无损,且能正常工作。

(2)检查疏散指示灯、应急照明灯、应急按钮等设备是否正常工作,是否有损坏,如有问题及时进行修理或更换。

(3)检查电池的充电情况,确保电池能够正常供电,保障系统的长时间运行。

(4)检测警报音响是否清晰可辨,是否能够迅速引起人员的注意。

2. 光源的检测与维护(1)定期检查应急照明灯的灯泡是否正常,如果发现灯泡已损坏,则需要及时更换。

(2)对疏散指示灯进行定期测试,确保其灯光亮度足够,能够清晰指示疏散方向。

(3)检查灯光的照明范围是否覆盖到每个疏散通道,确保在紧急情况下能够提供足够明亮的照明。

3. 数据记录与报告(1)对每次的检测与维护工作进行详细记录,包括检测时间、检测的项目、存在的问题以及解决方案等。

(2)及时向相关部门提交检测与维护的报告,包括系统的运行情况、存在的问题和处理情况等。

三、检测与维护的周期和频率1. 系统设备的检测与维护周期(1)每年至少进行一次全面的系统设备检测与维护,包括电缆、开关、配电箱等设备的检查和修理。

(2)定期对电池进行检测和维护,确保电池能够正常工作并提供足够的电力。

2. 光源的检测与维护周期(1)每半年进行一次应急照明灯的灯泡更换,确保其正常工作。

(2)每季度对疏散指示灯进行测试,确保其能够正常发光且指示清晰。

四、检测与维护的方法和标准1. 系统设备的检测与维护方法(1)通过可视检查,检查设备是否存在明显的损坏和故障。

《消防应急照明和疏散指示系统技术标准》

《消防应急照明和疏散指示系统技术标准》

《消防应急照明和疏散指示系统技术标准》消防应急照明和疏散指示系统技术标准。

消防应急照明和疏散指示系统是建筑物内部的重要设施,其作用是在火灾等突发事件发生时,为人员提供必要的照明和指引,以保障人员安全疏散。

本文将对消防应急照明和疏散指示系统的技术标准进行详细介绍,以期为相关从业人员提供参考和指导。

首先,消防应急照明和疏散指示系统的设计应符合国家标准和相关规定,确保系统的可靠性和稳定性。

在设计过程中,需要考虑建筑物的结构特点、人员密集区域、疏散通道等因素,合理布局照明设备和指示标识,确保系统在发生火灾等情况下能够有效发挥作用。

其次,消防应急照明和疏散指示系统的设备选择应符合相关标准要求,保证设备的品质和性能。

照明设备应具有防水防尘、耐高温、抗震等特性,能够在紧急情况下正常工作;指示标识应清晰明了,能够在黑暗环境中迅速指引人员疏散方向。

此外,系统的供电方式也需要考虑,可以选择备用电源或者应急发电机等设备,确保系统在停电情况下依然能够正常运行。

再者,消防应急照明和疏散指示系统的安装和维护应符合相关规定,确保系统的可靠性和持续性。

安装过程中需要注意设备的固定和接线,避免因松动或接触不良导致系统失效;定期进行系统的检测和维护,确保设备的正常运行和性能稳定。

最后,消防应急照明和疏散指示系统的使用和管理应建立健全的制度和规范,确保系统能够得到有效运行和管理。

制定相关操作规程和应急预案,对系统进行定期演练和检查,提高人员的应急处理能力和系统的应急响应能力;建立健全的档案管理制度,对系统的日常运行情况和维护记录进行详细记录,为系统的管理和维护提供依据。

总之,消防应急照明和疏散指示系统是建筑物内部的重要设施,其技术标准的合理制定和严格执行对于保障人员生命财产安全至关重要。

只有通过科学规范的设计、设备选择、安装维护和使用管理,才能够确保系统在紧急情况下能够可靠发挥作用,最大限度地保障人员的生命安全。

希望本文所述内容能够为相关从业人员提供一定的参考和指导,推动消防应急照明和疏散指示系统技术标准的全面落实和提升。

《消防应急照明和疏散指示系统技术规范》 GB 51309-2018

《消防应急照明和疏散指示系统技术规范》 GB 51309-2018
UDC
P
中华人民共和国国家标准
GB 51309 – 2018
消防应急照明和疏散指示系统技术标准
Technical Standard for fire emergency lighting and evacuate indicating system
2018– 07 –01 发布
2019 – 03 –01 实施
4 3.1 一般规定····················································································· 5 3.2 灯具······························································································· 12 3.3 系统配电的设计············································································· 3.4 应急照明控制器及集中控制型系统通信线路的设计······································17 19 3.5 系统线路的选择················································································ 3.6 集中控制型系统的控制设计··································································20 3.7 非集中控制型系统的控制设计·······························································25 26 3.8 备用照明设计··················································································· 4 施工 28 ································································································ 28 4.1 一般规定····················································································· 30 4.2 材料、设备进场检查·········································································· 30 4.3 布线····························································································· 4.4 应急照明控制器、集中电源、应急照明配电箱安装········································32 34 4.5 灯具安装························································································· 5 系统调试 37 ··························································································· 37 5.1 一般规定····················································································· 38 5.2 调试准备························································································ 5.3 应急照明控制器、集中电源和应急照明配电箱的调试·····································39 5.4 集中控制型系统的系统功能调试·····························································41 5.5 非集中控制型系统的系统功能调试··························································44 46 5.6 备用照明功能调试············································································· 6 系统检测与验收 47 ·················································································· 7 系统运行维护 51 ····················································································· 附录 A 消防应急照明和疏散指示系统子分部、

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准

中华人民共和国国家标准消防应急照明和疏散指示系统技术标准Technical standard for fire emergency lighting and evacuate indicating system GB 51309 -2018主编部门:中华人民共和国公安部批准部门:中华人民共和国住房和城乡建设部施行日期:2019年03月01日根据住房城乡建设部《关于印发〈2007年工程建设标准规范制订、修订计划〉的通知》(建标[2007]125号)的要求,消防应急照明和疏散指示系统技术规范编制组经广泛调查研究,认真总结实践经验,参考有关国际标准和国外先进标准,并在广泛征求意见的基础上,编制了本标准。

本标准共分为7章和6个附录,主要技术内容包括:总则,术语,系统设计,施工,系统调试,系统检测与验收及系统运行维护。

本标准中以黑体字标志的条文为强制性条文,必须严格执行。

本标准由住房城乡建设部负责管理和对强制性条文的解释,由应急管理部负责日常管理,由应急管理部沈阳消防研究所负责具体技术内容的解释。

执行过程中如有意见或建议,请寄送应急管理部沈阳消防研究所(地址:辽宁省沈阳市皇姑区文大路218-20号甲,邮政编码:110034)。

本标准主编单位、参编单位、主要起草人和主要审查人:主编单位:应急管理部沈阳消防研究所参编单位:上海市公安消防总队广东省公安消防总队中国建筑设计研究院有限公司北京市建筑设计研究院有限公司中国建筑东北设计研究院有限公司上海建筑设计研究院有限公司中国建筑西南设计研究院有限公司宝星电器(上海)有限公司沈阳宏宇光电子科技有限公司广东拿斯特(国际)照明有限公司北京市崇正华盛应急设备系统有限公司浙江台谊消防设备有限公司集保(福州)电气技术有限公司大连路明发光科技有限公司主要起草人:丁宏军张颖琮刘凯刘激扬李小白张磊严洪朱鸣王金元吕立陈琪汪猛陈众励蔡钧钟桂生牟宏伟李强汤鲁文周志平江清姚增硕主要审查人:陈南倪照鹏赵克伟郭树林黄德祥王东林李炳华李忠陈汉民1 总则1.0.1 为了合理设计消防应急照明和疏散指示系统,保证消防应急照明和疏散指示系统的施工质量,确保系统正常运行,制定本标准。

消防应急照明和疏散指示系统检测与维护(三篇)

消防应急照明和疏散指示系统检测与维护(三篇)

消防应急照明和疏散指示系统检测与维护消防应急照明和疏散指示系统是建筑物内重要的安全设备,能够在火灾发生时提供照明和指示,帮助人员疏散。

为了确保这些系统的正常运行,必须进行定期的检测和维护。

1. 检测和测试消防应急照明设备的电源和电路是否正常。

首先需要检查应急照明设备的电源供应是否正常,包括照明设备的电池或电源线路等。

然后需要测试照明设备的电路是否正常,是否能够在停电时自动开启,以及是否能够持续供电一定时间。

2. 检测和测试疏散指示系统的显示和指示功能。

疏散指示系统通常包括紧急照明、指示灯和指示标识等,需要确保这些设备的显示和指示功能正常。

通过检查各个指示灯和指示标识是否亮起并清晰可见,以及指示灯是否能够随着疏散路线指示方向的变化而改变,来测试疏散指示系统的正常工作。

3. 检测和测试疏散指示系统的音响报警功能。

除了视觉指示外,疏散指示系统通常还有音响报警功能用于提醒人员疏散。

测试时需要确保音响设备的声音能够在整个建筑物内清晰可听,并能够发出模拟火灾报警声、疏散指令等。

4. 定期更换电池和维护电源设备。

应急照明设备通常使用电池供电,为了确保其正常工作,需要定期更换电池。

同时,还需要定期检查电池盒、电源线路等设备的连接是否正常,并进行维护和清洁。

5. 检查和维护消防应急照明和疏散指示设备的安装位置。

消防应急照明和疏散指示设备的安装位置非常重要,需要确保其位置合理、明显可见,并且不被障碍物遮挡。

定期检查设备的安装位置是否变动,并进行必要的调整和维护。

6. 建立消防应急照明设备和疏散指示系统的记录和档案。

对于每次检测和维护,都需要建立详细的记录和档案,包括检测日期、检测人员、检测结果等。

这样可以追踪和记录设备的维护情况,以便及时发现和解决问题。

7. 定期进行演练和培训。

除了检测和维护,还需要定期进行应急疏散演练和培训,让人员熟悉应急照明和疏散指示系统的使用方法和疏散路线。

通过演练和培训,可以提高人员的应急意识和疏散能力,确保在火灾发生时能够迅速疏散。

《消防应急照明和疏散指示系统技术标准》

《消防应急照明和疏散指示系统技术标准》

《消防应急照明和疏散指示系统技术标准》消防应急照明和疏散指示系统技术标准。

消防应急照明和疏散指示系统是建筑物内部重要的安全设备,其设计和安装需要符合一定的技术标准。

本文将对消防应急照明和疏散指示系统技术标准进行详细介绍,以便相关从业人员能够准确理解并遵守相关规定,确保建筑物内部在火灾等紧急情况下能够迅速、有序地疏散。

一、系统设计标准。

1. 照明系统设计应满足建筑物内部的照明需求,保证在火灾等紧急情况下能够提供充足的照明,确保人员能够清晰地看到疏散通道和安全出口。

2. 疏散指示系统应设置在建筑物内部的关键位置,包括走廊、楼梯间、安全出口等处,并应采用明确、易于识别的指示标识,指示方向清晰,确保人员能够快速找到安全出口。

3. 设计应考虑建筑物内部的结构和功能布局,合理设置照明和指示系统的位置和数量,确保全面覆盖,避免死角和盲区,提高疏散效率。

二、设备选用标准。

1. 照明设备应选用符合国家标准的LED照明灯具,具有高亮度、低功耗、长寿命等特点,能够在紧急情况下提供稳定、持久的照明。

2. 疏散指示系统应选用明确的指示标识,包括指示灯、逃生指示标识等,应具有防水防尘、耐高温等特性,确保在紧急情况下能够正常工作。

3. 设备选用应考虑设备的可靠性和稳定性,避免因设备故障导致照明和指示系统无法正常工作,影响疏散安全。

三、安装和维护标准。

1. 安装应由具有相关资质和经验的专业人员进行,严格按照设计要求进行安装,确保设备位置准确、连接可靠,避免因安装不当导致设备故障。

2. 定期进行设备的维护和检查,确保照明和指示系统的正常运行,及时发现并排除潜在故障,保证系统在紧急情况下能够可靠工作。

3. 维护和检查记录应及时记录并保存,对设备的维护和检查情况进行定期总结和评估,及时更新和修复设备,确保系统的长期稳定运行。

四、应急演练标准。

1. 定期组织建筑物内部的应急疏散演练,让建筑物内的人员熟悉疏散通道和安全出口的位置,提高疏散效率和安全意识。

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准

消防应急照明和疏散指示系统技术标准消防安全是当今社会中最重要的安全管理之一,越来越多的消防应急照明和疏散指示系统正在投入使用,以保护消防人员和无辜的平民。

《消防应急照明和疏散指示系统技术标准》是一部系统性、综合性的技术标准,旨在帮助消防安全管理者正确的选择和使用消防应急照明和疏散指示系统,以确保公共场所的安全。

本技术标准包括消防应急照明和疏散指示系统的主要技术指标、规范、结构和设计要求、安装要求和检查测试要求等内容,具体如下:(1)技术指标:消防应急照明和疏散指示系统包括照明系统、指示系统、控制系统和紧急电源系统,应满足GB50223《消防应急照明和疏散指示系统技术标准》和其他相关技术标准的要求。

(2)规范、结构和设计要求:消防应急照明和疏散指示系统的规范、结构和设计要求,应遵循《消防应急照明和疏散指示系统技术标准》、GB50047《消防电气设备安装规范》和其他相关技术标准及说明书的要求。

(3)安装要求:安装消防应急照明和疏散指示系统时,应按照《消防应急照明和疏散指示系统技术标准》、GB50047《消防电气设备安装规范》和其他相关技术标准及说明书的要求进行安装。

(4)检查测试要求:安装完毕后,应对消防应急照明和疏散指示系统进行试验,确保系统的正常运行。

试验应符合《消防应急照明和疏散指示系统技术标准》及其他相关技术标准要求。

除此之外,设计、安装、施工、运行和维护消防应急照明和疏散指示系统,应按照本技术标准及其他相关技术标准的要求,确保系统的安全可靠,为公共场所的安全提供有力的保障。

《消防应急照明和疏散指示系统技术标准》是消防安全中一个重要的部分,规范了消防应急照明和疏散指示系统的设计、安装、运行等方面,为消防安全管理指明了方向,帮助管理者正确的选择和使用消防安全设备,从而确保公共场所安全。

消防应急照明和疏散指示系统技术标准【最新版】

消防应急照明和疏散指示系统技术标准【最新版】

消防应急照明和疏散指示系统技术标准附规范全文:《消防应急照明和疏散指示系统技术标准》GB51309-2018,自2019年3月1日起实施。

其中,第3.2.4、3.3.1、3.3.2、4.1.4、4.5.11(6)、6.0.1、6.0.5条(款)为强制性条文,必须严格执行。

中华人民共和国国家标准消防应急照明和疏散指示系统技术标准Technical standard for fire emergency lighting and evacuate indicating systemGB 51309 -2018主编部门:中华人民共和国公安部批准部门:中华人民共和国住房和城乡建设部施行日期:2019年03月01日中国计划出版社2018 北京前言根据住房城乡建设部《关于印发〈2007年工程建设标准规范制订、修订计划〉的通知》(建标[2007]125号)的要求,消防应急照明和疏散指示系统技术规范编制组经广泛调查研究,认真总结实践经验,参考有关国际标准和国外先进标准,并在广泛征求意见的基础上,编制了本标准。

本标准共分为7章和6个附录,主要技术内容包括:总则,术语,系统设计,施工,系统调试,系统检测与验收及系统运行维护。

本标准中以黑体字标志的条文为强制性条文,必须严格执行。

本标准由住房城乡建设部负责管理和对强制性条文的解释,由应急管理部负责日常管理,由应急管理部沈阳消防研究所负责具体技术内容的解释。

执行过程中如有意见或建议,请寄送应急管理部沈阳消防研究所(地址:辽宁省沈阳市皇姑区文大路218-20号甲,邮政编码:110034)。

本标准主编单位、参编单位、主要起草人和主要审查人:主编单位:应急管理部沈阳消防研究所参编单位:上海市公安消防总队、广东省公安消防总队、中国建筑设计研究院有限公司、北京市建筑设计研究院有限公司、中国建筑东北设计研究院有限公司、上海建筑设计研究院有限公司、中国建筑西南设计研究院有限公司、宝星电器(上海)有限公司、沈阳宏宇光电子科技有限公司、广东拿斯特(国际)照明有限公司、北京市崇正华盛应急设备系统有限公司、浙江台谊消防设备有限公司、集保(福州)电气技术有限公司、大连路明发光科技有限公司主要起草人:丁宏军、张颖琮、刘凯、刘激扬、李小白、张磊、严洪、朱鸣、王金元、吕立、陈琪、汪猛、陈众励、蔡钧、钟桂生、牟宏伟、李强、汤鲁文、周志平、江清、姚增硕主要审查人:陈南、倪照鹏、赵克伟、郭树、黄德祥、王东林、李炳华、李忠陈汉民1总则1.0.1 为了合理设计消防应急照明和疏散指示系统,保证消防应急照明和疏散指示系统的施工质量,确保系统正常运行,制定本标准。

浅谈《消防应急照明和疏散指示系统技术标准》

浅谈《消防应急照明和疏散指示系统技术标准》

浅谈《消防应急照明和疏散指示系统技术标准》1. 引言1.1 引言消防应急照明和疏散指示系统技术标准的制定是为了规范这些系统在建筑物中的应用,保障人员在火灾等紧急情况下能够迅速安全地疏散。

消防应急照明系统和疏散指示系统是建筑物内部重要的安全设施,能够在火灾、停电等紧急情况下提供照明和指示,帮助人们安全疏散,减少伤亡事故的发生。

消防应急照明系统和疏散指示系统技术标准的制定不仅能够规范系统的设计、安装和维护,还能够提高系统的可靠性和有效性,确保在紧急情况下起到应有的作用。

遵守技术标准对于建筑物的安全管理至关重要。

本文将重点探讨《消防应急照明和疏散指示系统技术标准》的制定意义、要求和应用,希望能够深入了解这一关乎人员生命安全的重要标准,为建筑物的消防安全工作提供参考和指导。

通过对这些内容的深入探讨,可以更好地认识和操作消防应急照明和疏散指示系统技术标准,进一步提高建筑物的消防安全水平。

2. 正文2.1 技术标准的重要性技术标准在消防应急照明和疏散指示系统的设计、安装和维护中起着至关重要的作用。

技术标准明确了设备和系统的设计要求,确保其满足相关安全标准和规范,从而提高了整个系统的可靠性和稳定性。

技术标准规定了设备的安装位置、布线方式、接线要求等具体细节,有助于提高系统的使用效率和便捷性。

技术标准还包括了针对设备的测试、检验和维护规定,确保系统在日常运行中能够正常工作,一旦发生火灾或其他紧急情况能够及时启动并发挥作用。

通过遵循技术标准,消防应急照明和疏散指示系统可以更好地满足建筑物内人员疏散和逃生的需要,最大限度地减少火灾事故造成的人员伤亡和财产损失。

遵守技术标准不仅是一种法律责任,更是对人们生命财产安全的一种保障。

只有通过严格执行技术标准,才能确保消防应急照明和疏散指示系统在关键时刻发挥最大的作用,保障建筑物内所有人员的安全。

在实际操作中,应该加强对技术标准的理解和执行,采取有效措施确保系统的高效运行,从而为紧急情况下的疏散和逃生提供可靠的保障。

消防紧急照明和疏散指示系统技术规范标准

消防紧急照明和疏散指示系统技术规范标准

消防紧急照明和疏散指示系统技术规范标准1.引言本文档制定了消防紧急照明和疏散指示系统的技术规范标准,目的是通过一系列的技术要求,保证系统具有可靠性、安全性和实用性,让人们在火灾等紧急情况下能够快速、有效地疏散,减少人员伤亡和财产损失。

2.技术要求2.1 系统功能要求- 疏散指示功能:系统应当在紧急情况下发布有效信号,为疏散提供明确的指导和指示。

- 照明功能:消防应急照明应当为非常态灯光,确保在火灾等紧急情况下,即使常规照明故障,也可以保持正常照明状态。

- 自检功能:系统应当具有自检功能,确保每个疏散指示灯和照明灯正常工作。

- 手动控制功能:系统应当具有手动控制功能,以方便在紧急情况下进行手动操作。

2.2 系统设计要求- 疏散指示系统应当装置在公共场所的主要进出口处和疏散通道的交叉出口处。

- 照明设备应该妥善安装,不应影响人员的逃生,不应妨碍疏散途中的人员移动,不应干扰其他设施和设备的正常使用。

- 设备应当具有防水、防潮、防尘,防电磁干扰等措施,确保其长期安全运行。

3.技术指标3.1 光源参数- 显色性:Ra≥70- 光通量:不低于100lm/W- 额定寿命:≥ h3.2 照度参数- 疏散通道及楼梯平台照度: 2~5lx- 疏散楼梯及出口照度:5~10lx- 室内无光污染区:0.5~1lx3.3 其他参数- 标志文字符号:确保字体清晰易读,标志直接编号清晰可见。

- 防护等级:IP65及以上- 自动测试间隔:不大于1个月,自动测试后对故障灯具及时报警。

4.测试方法根据技术指标,进行以下测试:- 光源参数测试- 出光角测试- 光通量测试- 显色性测试- 操作性能测试5.结论消防紧急照明和疏散指示系统技术规范标准确保了在紧急情况下的使用安全性和有效性。

相关部门应当遵照本标准进行消防紧急照明和疏散指示系统的设计、制造和安装管理,这样才能够实现消防疏散指示系统顺利运行、及时发现问题、更为安全可靠。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

消防应急照明和疏散指示系统技术标准
第一篇:消防应急照明系统技术标准
1. 前言
随着城市化进程的不断推进,人们对城市安全的要求越
来越高,尤其是对于公共场所的安全性。

消防应急照明系统作为一种重要的消防设施,不仅能够在火灾等紧急情况下提供必要的照明,还能指示疏散方向,提高人员疏散的效率,减少事故损失。

因此,消防应急照明系统的可靠性和安全性非常重要,特别是在建筑物和公共场所的设计和建造中必须非常注重。

2. 体系结构
消防应急照明系统包括三个部分:照明装置、控制装置
和电源设备。

(1) 照明装置:通常使用的照明灯具有紧急照明灯和逃
生路灯两种。

(2) 控制装置:控制装置主要包括控制箱和控制器,通
过监测和控制输入输出信号,实现对紧急照明和逃生路灯的开关和调节。

(3) 电源设备:根据系统的使用需求可选用不间断电源、自动转换开关等。

3. 系统设计
(1) 照明灯的数量和位置应根据建筑物的类型和规模确定,并考虑维修和更换的便利性。

(2) 紧急照明灯应装置在易发生火灾或爆炸的场所,如
火源发生室、储油室等。

(3) 逃生路线和紧急出口处应安装逃生路灯,且必须满足照明的亮度、色温、颜色等指标要求。

(4) 控制箱需具有手动和自动两种操作模式,并装置充电电源等必要设施。

(5) 电源设备的选择应满足系统的功率需求,并保证电源的可靠性和稳定性。

4. 技术指标
(1) 紧急照明灯的照度应≥10lx,逃生路灯照度应≥5lx。

(2) 着急照明灯和逃生路灯的应急照明时间应≥1h。

(3) 着急照明灯和逃生路灯在紧急状态下应具有自动开启及手动开关功能。

(4) 控制装置应具备报警功能。

(5) 照明灯和控制装置应符合相关国家标准、规定和安全要求。

第二篇:疏散指示系统技术标准
1. 前言
疏散指示系统是一种非常重要的消防设施,能够在火灾或紧急事故时,向被困人员提供有效的疏散指引,降低人员伤亡损失。

疏散指示系统的设计和安装应该严格按照相关标准要求,确保系统的可靠性和安全性。

2. 体系结构
疏散指示系统包括四个部分:指示灯具、控制器、电源系统和显示屏。

(1) 指示灯具:疏散指示灯分为平面型和壁装型两种,根据需要选取不同的方案。

(2) 控制器:通过控制器的控制,实现指示灯的亮灭、变色等操作。

(3) 电源系统:系统的电源采用适当的电压和电流,并
具有过载保护、过热保护等功能。

(4) 显示屏:通过显示屏,将疏散指示灯的状态、疏散
路线、紧急出口等信息显示出来。

3. 系统设计
(1) 疏散指示灯的数量和位置应根据建筑物的类型、规
模和布局确定,且需与紧急出口直接相连。

(2) 线路和电缆应使用耐火材料防火防爆,且应留出足
够的裕量,方便维护和更换。

(3) 控制器应具有完善的故障监测和通信功能。

(4) 电源应按照相关国家标准和建筑电气设计规范进行
设计和布置。

4. 技术指标
(1) 疏散指示灯亮度应≥250cd/㎡。

(2) 疏散指示灯的灯色应为绿色,提示文字应为白色。

(3) 显示屏应具有很强的可见性、易读性和可靠性。

(4) 控制器应具有故障保护、通信功能等。

(5) 疏散指示系统应满足相关标准和规范的要求。

第三篇:消防应急照明和疏散指示系统联合应用标准
1. 前言
消防应急照明和疏散指示系统的联合使用,能够提高建
筑物的安全性和应急处理能力。

两个系统在设计和应用过程中,需要具有良好的兼容性、互动性和优化性。

本文将介绍消防应急照明和疏散指示系统联合应用的一些技术标准和要求。

2. 系统设计
(1) 系统布局应满足建筑物的结构和功能布局,疏散指
示灯和紧急照明灯应当完美衔接。

(2) 在安装紧急照明灯时,应考虑照度分布、色温和光源的稳定性,确保在紧急情况下,照明系统能够正常运行。

(3) 在安装疏散指示灯时,应考虑指示灯的亮度、颜色、大小、形状等要素,并保证灯具的可视性和可勘察性。

(4) 控制装置应能够对照明系统和疏散指示系统进行管理和监控,可以通过物理按钮、无线网络等方式进行操作,确保系统的可靠性。

3. 协同工作
(1) 疏散指示系统和紧急照明系统应当共享同一套电源,保证系统的连续性和稳定性。

(2) 紧急照明系统和疏散指示系统的信号应互相独立,确保信号传输的稳定性和可靠性。

(3) 紧急照明系统和疏散指示系统应能够同时作用,即在紧急情况下,灯具能够同时发出警示事件,并进行疏散指示和照明。

4. 技术指标
(1) 紧急照明灯亮度应≥10lx,逃生路灯照度应≥5lx。

(2) 疏散指示灯亮度应≥250cd/㎡。

(3) 紧急照明灯和逃生路灯的应急照明时间应≥1h。

(4) 疏散指示系统应有足够的显示屏或提示标志,确保信息的即时传递。

(5) 消防应急照明和疏散指示系统联合使用应符合相关国家标准和技术要求。