EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENT ALLY SOUND R−410A REFRIGERANT1−1/2 THRU 5 TONS SPLIT SYSTEM208 / 230 Volt, 1−phase, 60 Hz REFRIGERATION CIRCUITS Copeland Scroll t compressors on all modelsS Filter−Drier supplied with every unit for field installation S External high and low refrigerant service portsS Copper tube/aluminum fin coil PERFORMANCES2−speed Fan Motors factory wired on all modelsS Compressor Sound Jacket standardEASY TO INSTALL AND SERVICES Comfort Alert t Diagnostics device on all modelsS Easy Access service valves on all modelsS Innovative control box designS High and Low pressure switchesS Fan motor in−line disconnect plugS Only two screws to access control panelS Factory charged with R−410A refrigerantBUILT TO LASTS High gloss, baked−on powder coat finish over galvanized steelS Post−painted (black) coil finsS Coated, weather−resistant cabinet screwsS Coated inlet grille with 3/8” (10mm) spacing for extra protection (hail guard)S Corner Posts for extra strength and styleLIMITED WARRANTY*S1 year No Hassle Replacement t limited warrantyS5 year compressor limited warranty Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to .S5 year parts limited warranty (including compressor and coil)− With timely registration, an additional 5 year parts limited warranty (including compressor and coil) *For owner occupied, residential applications only. Seewarranty certificate for complete details andrestrictions, including warranty coverage for otherapplications.Model NumberSize(tons)NominalBtu/hrMin. CircuitAmpacityMax. Fuseor BreakerOperating Dimensionsheight x width x depth in. (mm)Ship / OperatingWeight lbs. (kg)H4A318GKN1−1/218,00011.82025−3/16 x 23−1/8 x 23−1/8(640 x 587 x 587)143 / 117 (65 / 53)H4A324GKN224,00017.63025−3/16 x 23−1/8 x 23−1/8(640 x 587 x 587)142 / 118 (64 / 54)H4A330GKN2−1/230,00016.82528−9/16 x 23−1/8 x 23−1/8(726 x 587 x 587)151 / 127 (69 / 58)H4A336GKN336,00021.93525−3/16 x 31−3/16 x 31−3/16(640 x 793 x 793)196 / 160 (89 / 73)H4A342GKN3−1/242,00023.54032 x 31−3/16 x 31−3/16(813 x 793 x 793)230 / 195 (104 / 89)H4A348GKN448,00026.04035−3/8 x 31−3/16 x 31−3/16(899 x 793 x 793)243 / 203 (110 / 92)H4A360GKN560,00034.25028−9/16 x 31−3/16 x 31−3/16(726 x 793 x 793)250 / 215 (113 / 98)OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase)Digit Position:12345, 6789101112 Example Part Number:H4A318G K N100 H = Airquest Mainline4 = R−410A REFRIGERANTA = Air ConditionerH = Heat Pump TYPE3 = 13 SEER4 = 14 SEER5 = 15 SEER6 = 16 SEER7 = 17 SEER8 = 18 SEER NOMINAL EFFICIENCY18 = 18,000 BTUH = 1−1/2 tons24 = 24,000 BTUH = 2 tons30 = 30,000 BTUH = 2−1/2 tons36 = 36,000 BTUH = 3 tons42 = 42,000 BTUH = 3−1/2 tons48 = 48,000 BTUH = 4 tons60 = 60,000 BTUH = 5 tons NOMINAL CAPACITYA = Standard GrilleG = Coil Guard GrilleC = Coastal FEATURESK = 208/230−1−60VOLTAGESales CodeEngineering RevisionExtra DigitExtra DigitACCESSORIES PART NUMBER IDENTIFICATION GUIDEDigit Position:123456, 78, 910, 11 Example Part Number:N A S A00 101 C H N = Non−Branded BRANDINGA = Accessory PRODUCT GROUPS = Split System (AC & HP)KIT USAGEA = OriginalB = 2nd Generation MAJOR SERIES0 = Generic or Not Applicable2 = R−224 = R−410A REFRIGERANTProduct Identifier NumberPackage QuantityType of Kit(Example: CH = Crankcase Heater)PHYSICAL DATAModel Size18243036424860 Nominal Cooling Capacity (BTU/hr)18,00024,00030,00036,00042,00048,00060,000 Nominal SEER13.013.013.013.013.013.013.0Sound Rating** High Speed Fan (dBA) Low Speed Fan (dBA)7068747173727372747473717472PSC Fan Motor HP1/121/101/101/51/51/41/4Fan RPM High Fan RPM Low 109499510929901087937840803841799828764816735Fan CFM (High)1747219121913359335939373937Coil Face Area ft2 (m2)8.40(0.78)8.40(0.78)9.80(0.91)12.93(1.20)17.25(1.60)19.40(1.80)15.09(1.40)Coil Rows−fins per inch1−201−251−251−251−251−252−20Low Pressure Switch Open Pressure (psig) Close Pressure (psig)50 ± 795 ± 750 ± 795 ± 750 ± 795 ± 750 ± 795 ± 750 ± 7 95± 750 ± 795 ± 750 ± 795 ± 7High Pressure Switch Open Pressure (psig) Close Pressure (psig)610 ± 10420 ± 25610 ± 10420 ± 25610 ± 10420 ± 25610 ± 10420 ± 25610 ± 10420 ± 25610 ± 10420 ± 25610 ± 10420 ± 25Liquid Line Connection Size in. (mm)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10) Vapor Line Connection Size in. (mm)3/4 (19)3/4 (19)3/4 (19)7/8 (22)7/8 (22)7/8 (22)7/8 (22) Rated Line Set Liquid TubeDiameter in. (mm)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10) Rated Line Set Vapor TubeDiameter in. (mm)*3/4 (19)*3/4 (19)*3/4 (19)*7/8 (22)*7/8 (22)*7/8 (22)*1−1/8 (29)*Factory Charge R−410A lbs. (kg) 3.50(1.59)3.80(1.72)4.10(1.86)5.34(2.42)5.84(2.65)7.00(3.18)8.00(3.63)Required Subcooling °F (°C)10 (6)10 (6)10 (6)12 (7)10 (6)15 (8)10 (6) *Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset. Note: See unit Installation Instruction for proper installation.ELECTRICAL DATA (208/230−1−60, voltage range 197V − 253V)Model Size18243036424860 Minimum Circuit Ampacity −MCA (amps)11.817.616.821.923.526.034.2Maximum OverCurrentProtective device −MOCP (amps)20302535404050Compressor RLA (Rated Load Amps) LRA (Locked Rotor Amps)9.04813.558.312.86416.77917.911219.910926.4134Fan Motor FLA (Full Load Amps)0.50.750.75 1.1 1.1 1.2 1.2 **Sound Rating tested in accordance with AHRI Standard 270−2008 (not listed with AHRI).Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz. When using other length or diameter liquid lines, charge adjustments are required per the chart above.Charging Formula:[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustmentExample 1: System has 15 ft of line set using existing 1/4“ liquid line. What charge adjustment is required?Formula:(.27 oz/ft x 15ft) – (9 oz) = (-4.95) oz.Net result is to remove 4.95 oz of refrigerant from the systemExample 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?Formula:(.40 oz/ft. x 45ft) – (9 oz.) = 9 oz.Net result is to add 9 oz of refrigerant to the systemLONG LINE APPLICATIONSAn application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.For Air Conditioner systems, the charts below shows when an application requires a TXV and long line accessories due to lineset length.AC with R−410A Refrigerant Long Line Description ft (m) Beyond these lengths, a TXV is requiredAC with R−410A Refrigerant Long Line Description ft (m) (Beyond these lengths, long line accessories are required)Note: See Long Line Guideline for detailsR−410A COOLING CAPACITY LOSS FOR VARIOUS LINE LENGTHS & TUBE DIAMETERSModel SizeLiquidLinein.(mm)AcceptableVapor LineSizesin.(mm)Cooling Capacity Loss (%) at Total Equivalent Line Length, feet (m)Refer to Long Line Application Guideline to calculate equivalent lengthStandard Application Long Line Application (Requires Accessories)25’(7.6)50’(15.2)80’(24.4)81’(24.7)100’(30.5)125’(38.1)150’(45.7)175’(53.3)200’(61)225’(68.6)250’(76.2)183/8 (10)1/2 (13)1233467891012 5/8 (16)00111122333 3/4 (19)00000111111245/8 (16)01112334456 3/4 (19)00000111112 7/8 (22)00000000001305/8 (16)12333456789 3/4 (19)00111122233 7/8 (22)00000111111365/8 (16)12445679101113 3/4 (19)00111223344 7/8 (22)00000111122423/4 (19)01222344566 7/8 (22)00111122233 1−1/8 (29)0000000000148/493/4 (19)01223455678 7/8 (22)00111222334 1−1/8 (29)0000000011160/613/4 (19)12445679101112 7/8 (22)01222344556 1−1/8(29)00001111112Consult the Long Line Application Guideline document before purchasing/installing line sets.Applications in shaded area may have height restrictions that limit allowable total equivalent length when outdoor unit is below indoor unit.COOLING PERFORMANCE FOR COMBINATION RATINGS Indoor ModelsFor complete ratings information, use the AHRI website directory search: .New ratings may be listed online before Specification Sheets are updated.Unit Size Indoor Model Furnace ModelAHRI Standard RatingsCooling95°F (35°C)CapacityFactoryEnhanceSEEREERStandardW/ FieldTDRW/FieldTXVH4A318GKN*ED*4X18B**17200TXV1310.9 H4A324GKN*ED*4X24B**23000TXV1311 H4A330GKN*ED*4X30B**27200TXV1310.8 H4A336GKN*ED*4X36F**35200TXV13.211 H4A342GKN*ED*4X42J**41000TXV13.211 H4A348GKN*ED*4X48J**46000TXV13.211 H4A360GKN*ED*4X60L**57500TXV1311 TESTED AHRI COMBINATION RATINGS*Or scan this QR code: NOTE: Ratings contained in this document are subject to change at any time.For AHRI ratings certificates, please refer to the AHRI directory. Additional ratings and system combinations can be accessed via the Airquest database:/AHRIratings/ratings.aspx?Brand=AirquestACCESSORY USAGE GUIDELINESAccessoryREQUIRED FORLOW−AMBIENT APPLICATIONS{Below 55°F (13°C)}REQUIRED FORLONG−LINE APPLICATIONS*Crankcase Heater Yes Yes Evaporator Freeze Thermostat Yes No Winter Start Control Yes**NoTXV Yes YesǂHard Start Kit (Capacitor & Relay)Yes YesLow Ambient Kit (Pressure Switch)Yes NoSupport Feet, 4” (102mm) tall Recommended No* Refer to the Long Line Application Guideline document.**Can only be installed in conjunction with the Low Pressure SwitchǂTXV required beyond 20 ft (6.1m) vertical separation or 50 ft (15.2) total length.ACCESSORIESPart Number Description Used OnModel Size NASA001CH Crankcase Heater for Scroll Compressor (208/230 V)42, 48, 60 NASA003CH Crankcase Heater for Scroll Compressor (208/230 V)18, 24, 30, 36 NASA001SC Start Component − PTC Device ALL NASA00201FS Evaporator Freeze Thermostat ALL NASA401LS Liquid Line Solenoid Valve, R−410A ALL NASA001TD Time Delay Relay, Indoor Blower ALL NASA00201WS Winter Start Control ALL NASA001AC Anti−Cycle Timer (5 minute delay)ALL NASA005SC Hard Start Kit (Capacitor & Relay)ALL NASA401LA Low Ambient Kit (Pressure Switch), R−410A ALL NASA00201SF Support Feet, 4” (102mm) tall (5 blocks)18, 24, 36 NASA001SF Support Feet, 4” (102mm) tall (4 blocks)30, 42, 48, 60 EBAC05TXVX TXV Kit, R−410A − 2005−2009 R−22 TXV Fancoils (air handlers)18, 24, 30 EBAC06TXVX TXV Kit, R−410A − 2005−2009 R−22 TXV Fancoils (air handlers)36, 42 EBAC07TXVX TXV Kit, R−410A − 2005−2009 R−22 TXV Fancoils (air handlers)48, 60 NAEA40501TX TXV Kit, R−410A − 2010 and later Piston Coils18, 24, 30 NAEA40601TX TXV Kit, R−410A − 2010 and later Piston Coils36, 42 NAEA40701TX TXV Kit, R−410A − 2010 and later Piston Coils48, 60Copyright 2016 International Comfort ProductsLewisburg, Tennessee 37091 USA。
大金 CUW--D型说明书(M03SK001C)
意
机组外壳应接地。 接地线不能与气管、水管、避雷针 或通讯线路连接,接地方法错误会 发生电击事故。
应设置漏电断路器。 漏电断路器应按电气设备技术标 准和内线规程进行安装。错误安 装将可能造成电击事故。
!
设备安装位置应确保排水系统畅 通。 排水系统不合理将可能引起排水 不畅,而使设备装置受潮。
!
机组使用的冷冻水应符合水质标 准要求。 水质恶化有损机组性能和寿命, 亦可能引起漏水。
控制箱门开启时不能启动机组以 免引起电击或火灾。
8
!注
禁止改变安全保护装置的设置 保护装置失控将造成火灾事故。
机身上禁止摆设液体容器(如花 瓶等)。 如果液体溢出流入机组内会损 坏电气装置从而导致电击事故。
清扫时应使机组停止运转并切 断电源,以免造成意外伤害。
!
冷冻水、冷却水禁止饮用 饮用冷冻水、冷却水有害健康。
沉或伤人事故。
!
安装基础时,应按规定做好防风防
震等防范措施。
否则可能造成机组倾倒、坠落等事
故。
!
用规定电缆、电线进行线路连接,并
确保各接头牢固。
线路、接头连接不牢固将可能产
生高温引起火灾。
!
辅助设备必须由专业人员安装。 辅助设备应选用大金指定产品, 选用不当易发生触电、火灾等。
!
6
!注
机组不得安置于可能发生可燃性 气体泄漏之处。 一旦可燃性气体泄漏并聚集于机 组周围将可能会引发火灾。
1d
DAIKIN 水冷式单螺杆冷水机组
使用说明书
适用于以下机型
CUW40D5Y CUW50D5Y CUW60D5Y CUW80D5Y CUW90D5Y CUW100D5Y CUW110D5Y CUW120D5Y CUW140D5Y CUW160D5Y CUW180D5Y CUW200D5Y CUW220D5Y CUW240D5Y CUW260D5Y CUW280D5Y CUW300D5Y CUW320D5Y CUW340D5Y CUW360D5Y CUW80DS5Y CUW100DS5Y CUW120DS5Y
大きん日本制冷机远程控制手册说明书
OPERATING MANUALOperating Manual Handset WirelessOM-GS02-0211(0)-DAIKIN (SASO)Part No.: R08019036067GS02 Remote Control IndicationHOW TO MOUNT ONTO THE WALLTO INSERT BATTERIES (AAA.R03)REMOTE CONTROLLER LOSS PREVENTION WITH BALL CHAIN(OPTIONAL)Installation1. Match the ring at the end of the ball chain with the screw hole on the back of the remotecontroller and secure it with the screw.2.Attach the holder and the ball chain as above at the position where signals from theremote controller can be received easily.3. Pass the ball chain through the back of the holder and match the ring at the end of theball chain to the upper hole of the holder. Fix the holder to the wall by putting through2 screws across it.E N G L I S H1. Transmission source• The source where the signal will be transmitted.2. Signal transmission indication • Blink to con À rm that the last setting has been transmitted to the unit.3. “ON/OFF” Button• Press once to start the air conditioner unit. • Press again to stop the unit.4. Fan speed selection •P ressingthebutton continuously will toggle the fan speed in the followingorder:• Stop pressing when the desired fan speed appears on the display screen.5. Operation mode • Press the MODE button to select the type of operating mode. • F or cooling only unit, the available modes are: COOL (), DRY () andFAN (). • FAUTO (), COOL (), DRY (),FAN () and . • The AUTO ()6. Automatic air swing • Press the SWING button to activate the automatic air swing function. • T o distribute the air to a speci À c direction, press theSWING button and waituntil the louver move to the desired direction and press the button once again. Swing mode selection method (for CK-E model) • P ress SWING () button for 4 seconds to enter À eld setting mode. While in À eldsetting mode, it will only show .• P ress temperatureand button to selectrotation fromSwing Mode 1 to Swing Mode 3.• , which are:Swing mode 2 Swing mode 3SWING MODE will not activate unless SWING is activated. Swing is indicated by the logo: • I f no mode changes within 4 seconds, unit will operate according to the selectedSWING MODE 7. • Pressfor fast cooling or heating operation. • Fan speed turn to maximum speed. • Press again to deactivate the function.• Available under HEAT and COOL modes only.• Any change of fan speed will deactivate this function.• T he Turbo function () is unavailable for chilled water system and remote controlwith SWING MODE function.O r i g i n a l I n s t r u c t i o n8. OFF timer settingOFF TIMER button will activate the off timer function.thePress•• S et the desired off time by pressing the OFF TIMER button continuously.CANCEL button to cancel the off timer setting.the•Press9. Quiet function (model dependant)Press for quiet operation.•• Fan speed turn to minimum speed.• Press again to deactivate the function.• Any change of fan speed will deactivate this function.• The Silent function () is unavailable for chilled water system.10. Clock time setting• Press and hold button to set the clock time.11. ON timer settingthe ON TIMER button will activate the on timer function.•Press• S et the desired on time by pressing the ON TIMER button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30am sharp.CANCEL button to cancel the on timer setting.the•Press12. Sleep mode settingthe button will activate the sleep mode function.•P ress• T his is an energy saving option. When the Array unit is operating under cooling mode, the settemperature is increased by 0.5°C after the À rsthalf an hour, another 0.5°C after the second halfan hour and 1°C after the following 1 hour.• W hen the unit is operating under heatingmode, the set temperature is decreased by1°C after the À rst half an hour, another 1°Cafter the second half an hour and 1°C after thefollowing 1 hour.• T his function is available under COOL,HEAT and AUTO mode.13. Temperature setting• T o set the desired room temperature, press the or button to increase or decrease the set temperature.• T he temperature setting range is from 16°C to 30°C (Optional setting 20°C to 30°C).• Press both buttons and simultaneously to toggle from °C to °F setting.。
Daikin 环保空调 13 SEER 环保 R-410A 冷却系统 1.5-5 吨拆分系统说明书
421 61 5400 01 March 2006Specifications subject to change without notice.EFFICIENT 13 SEER AIR CONDITIONERENVIRONMENT ALLY SOUND R −410A REFRIGERANT1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1−phase, 60 HzREFRIGERATION CIRCUITS Copeland SCROLL compressors on all modelsS Filter −Drier supplied with every unit for field installation S External high and low refrigerant service ports S Copper tube /aluminum fin coilS 5 ton model has 2−row coil for reduced height PERFORMANCES 2−speed Fan Motors factory wired on all models S Compressor Sound Jacket standardEASY TO INSTALL AND SERVICES Comfort Alert t Diagnostics device on all models S Easy Access service valves on all modelsS Compressor access panelSNew, innovative control box design S High and Low pressure switches S Fan motor in −line disconnect plugS Only two screws to access control panel S Factory charged with R −410A refrigerantBUILT TO LASTS High gloss, baked −on powder coat finish over galvanized steelS Post −painted (black) coil finsS SermaGard ® coated cabinet screwsS Coated inlet grille with a ” spacing for extra protection S Corner Posts for extra strength and style S 5 year No Hassle replacement warrantyS 10 year limited compressor, 5 year limited coil and parts warrantiesRated in accordance with ARI Standard 210.Certification applies only when used with propercomponents as listed with ARI.Model Number Size (tons)Nominal Btu/hr Min. Circuit Ampacity Max. Fuse or BreakerOperating Dimensions height x width x depth (in)Ship / Operating Weight (lbs)H4A318GKA 1½18,00011.720@(8 ~ #!x ~ #@c 187 / 160H4A324GKA 224,00016.525@(8 ~ #!x ~ #@c 189 / 162H4A330GKA 2½30,00018.730#%, ~ #!x ~ #@c 200 / 172H4A336GKA 336,00021.935#(a ~ #!x ~ #@c 215 / 187H4A342GKA 3½42,00025.940$#2 ~ #% ~ #^b 282 / 248H4A348GKA 448,00028.640$#2 ~ #% ~ #^b 285 / 251H4A360GKA560,00034.350#^w ~ #% ~ #^b299 / 265PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A3421 61 5400 013Specifications subject to change without notice.PHYSICAL DATAModel Size18243036424860Nominal Cooling Capacity (BTU/hr)18,00024,00030,00036,00042,00048,00060,000Nominal SEER13.013.013.013.013.013.013.0Sound Rating, High Speed Fan (dBA)Low Speed Fan (dBA)7372737075707572767476747675PSC Fan Motor HP 1/121/121/51/51/51/41/4Fan RPM High Fan RPM Low 825750825750825750825750825750825750825750Fan CFM (High)2140214028002800327036703670Coil Face Area (ft 2)11.2611.2614.4716.0822.3622.3618.30Coil Rows − fins per inch 1−201−251−251−251−251−252−20Liquid Line Connection Size (in.)3/83/83/83/83/83/83/8Vapor Line Connection Size (in.)5/85/83/43/47/87/87/8Recommended Line Set Liquid TubeDiameter (in.)3/83/83/83/83/83/83/8Recommended Line Set Vapor TubeDiameter (in.) *5/8 *5/8 *3/4 *3/4 *7/8 *7/8 *18 **Recommended Vapor Tube Line size is for standard installations. These recommendations may not apply to “Long Line” installations. When the total equivalent line length exceeds 80 feet or there is more than 20 feet vertical separation between indoor and outdoor units, consult the Long Line Application Guideline document before purchasing/installing line sets.Factory Charge R −410A (lbs.) 3.90 4.25 5.75 5.857.138.409.35Required Subcooling (°F)10131712121312Weight, shipping (lbs.)187189200215282285299Weight, operating (lbs.)160162172187248251265ELECTRICAL DATA (208/230−1−60, voltage range 197V − 253V)Model Size18243036424860Minimum Circuit Ampacity −MCA (amps)11.716.518.721.925.928.634.3Maximum OverCurrentProtective device − MOCP (amps)20253035404050Compressor RLA (Rated Load Amps)LRA (Locked Rotor Amps)9.04812.858.314.17316.77919.910921.811726.3134Fan Motor FLA (Full Load Amps)0.50.51.11.11.11.41.4PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A34421 61 5400 01Specifications subject to change without notice.R −410A COOLING CAPACITY LOSS FOR VARIOUS LINE LENGTHS & TUBE DIAMETERSModelSize Liquid Line(in.)Acceptable Vapor Line Sizes (in.)Cooling Capacity Loss (%) at Total Equivalent Line Length (ft.)Refer to Long Line Application Guideline to calculate equivalent length Standard Application Long Line Application (Requires Accessories)25’50’80’81’100’125’150’175’200’225’250’18as 0111222333424s 11223344566w 01111112222 d 0000111111130s 12334567899w 01111223334 d 0011111112236s 13445789111213w 11222333445 d 0111112222342w 11223345567 d 01111222333!80000011111148w 12333456788 d 01112233344!80000111111160w 13445689101113 d 11223344566!800111111122* Applications are considered “Long Line” if the total equivalent tubing length exceeds 80 feet or there is more than 20 foot vertical separation between indoor and outdoor units). These applications require additional accessories and system modifications for reliable system operation. Refer to the Long Line Application Guideline document for required piping and system modifications. Refer to Accessory Usage Guidelines below for required accessories.Applications in this shaded area may have height restrictions that limit allowable total equivalent length when outdoor unit is below indoor unit. Refer to the Long Line Application Guideline document for instructions.The maximum allowable total equivalent length is 250 feet.ACCESSORY USAGE GUIDELINESAccessoryREQUIRED FOR LOW −AMBIENTAPPLICATIONS (Below 55° F)REQUIRED FOR LONG LINEAPPLICATIONS*(Over 80 Ft.)Crankcase Heater Yes Yes Evaporator Freeze Thermostat Yes No Winter Start Control Yes No Hard Start Kit (Capacitor & Relay)Yes Yes Low Ambient Kit (Pressure Switch)Yes No Support Feet, 4” tall Recommended No Liquid Line Solenoid Valve No See Long −Line Application Guideline * For Line Set lengths between 80 and 200 ft horizontal, or more than 20 ft indoor −outdoor vertical separation,refer to the Long Line Application Guideline document.PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A3421 61 5400 015Specifications subject to change without notice.ACCESSORIESPart Number DescriptionUsed On Model Size NASA001CH Crankcase Heater for Scroll Compressor (208/230 V)42, 48, 60NASA003CH Crankcase Heater for Scroll Compressor (208/230 V Star Body)18, 24, 30, 36NASA001SC Start Component − PTC Device ALL NASA001FS Evaporator Freeze Thermostat ALL NASA401LS Liquid Line Solenoid Valve, R −410A ALL NASA001TD Time Delay Relay, Indoor BlowerALL NASA001WS Winter Start ControlALL NASA001AC Anti −Cycle Timer (5 minute delay)ALL NASA005SC Hard Start Kit (Capacitor & Relay)ALL NASA401LA Low Ambient Kit (Pressure Switch), R −410AALL NASA001SF Support Feet, 4” tall ALL EBAC05TXVX TXV Kit, R −410A *18, 24, 30EBAC06TXVX TXV Kit, R −410A *36, 42EBAC07TXVX TXV Kit, R −410A *48EBAC08TXVXTXV Kit, R −410A *60* ONLY converts Fan Coils equipped with factory installed R −22 TXV.PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A36421 61 5400 01Specifications subject to change without notice.COOLING PERFORMANCE FOR COMBINATION RATINGSCurrent Indoor ModelsOutdoor Model Current Indoor Model(‡ tested combo)Furnace ModelFactoryInstalled Cooling (95 °F)SEERBTU/hrS/TEERfactoryw/ field TDR w/ field R−410A TXVw/ field R−410A TXV+TDRH4A318GKA‡ ED*4X18B**TXV 17,4000.7711.0013.00ED*4X18B**MV08B15****TDR & TXV 18,0000.7711.7014.00ED*4X24B**TXV 17,7000.7711.0013.00ED*4X24B**MV08B15****TDR & TXV 18,4000.7712.0014.00ED*4X24F**TXV 17,7000.7711.0013.00ED*4X24F**MV12F19****TDR & TXV 18,0000.7712.0014.00EHD4X24A**TXV 17,7000.7711.0013.00EHD4X24A***9MPV050TDR & TXV 18,4000.7711.5014.00EHD4X24A***9MPV075TDR & TXV 18,4000.7711.2013.50EHD4X24A**MV08B15****TDR & TXV 18,4000.7712.0014.00EHD4X24A**MV12F19****TDR & TXV 18,0000.7712.0014.00EMA4X24D**TXV 17,5000.7711.0013.00FEM4X18****TDR & TXV 17,8000.7711.5014.00FEM4X24****TDR & TXV 18,0000.7711.7014.00FS(M,U)4X18****TDR & TXV 17,3000.7711.0013.00FS(M,U)4X24****TDR & TXV 17,6000.7711.0013.00H4A324GKA‡ ED*4X24B**TXV 24,0000.7611.0013.00ED*4X24B***8MPV050TDR & TXV 24,4000.7611.5014.00ED*4X24B**MV08B15****TDR & TXV 24,6000.7611.7014.00ED*4X24F**TXV 24,0000.7611.0013.00ED*4X24F***8MPV075TDR & TXV 24,8000.7611.5014.00ED*4X24F***9MPV050TDR & TXV 24,2000.7611.5014.00ED*4X24F***9MPV075TDR & TXV 24,4000.7611.5014.00ED*4X24F**MV12F19****TDR & TXV 24,4000.7611.7014.00ED*4X30B**TXV 24,2000.7611.0013.00ED*4X30B***8MPV050TDR & TXV 24,6000.7611.5014.00ED*4X30B**MV08B15****TDR & TXV 24,8000.7611.7014.00ED*4X30F**TXV 24,2000.7611.0013.00ED*4X30F***9MPV050TDR & TXV 24,6000.7611.5014.00ED*4X30F***9MPV075TDR & TXV 24,8000.7611.5014.00ED*4X30F**MV12F19****TDR & TXV 24,8000.7612.0014.00EHD4X24A**TXV 23,8000.7611.0013.00EHD4X24A***8MPV050TDR & TXV 24,2000.7611.2013.50EHD4X24A***8MPV075TDR & TXV 24,4000.7611.5014.00EHD4X24A***8MPV100TDR & TXV 24,8000.7611.5014.00EHD4X24A***8MPV125TDR & TXV 24,8000.7611.7014.00EHD4X24A***9MPV050TDR & TXV 24,2000.7611.5014.00EHD4X24A***9MPV075TDR & TXV 24,4000.7611.2013.50EHD4X24A***9MPV100TDR & TXV 24,2000.7611.5014.00EHD4X24A***9MPV125TDR & TXV 24,6000.7611.5014.00EHD4X24A**MV08B15****TDR & TXV 24,2000.7611.7014.00EHD4X24A**MV12F19****TDR & TXV 24,4000.7611.7014.00EHD4X24A**MV16J22****TDR & TXV 24,4000.7611.7014.00EHD4X24A**MV20N26****TDR & TXV 24,6000.7611.7014.00EHD4X30A**TXV 24,2000.7611.0013.00EHD4X30A***8MPV050TDR & TXV 24,6000.7611.5014.00EHD4X30A***8MPV075TDR & TXV 25,2000.7611.5014.00EHD4X30A***8MPV100TDR & TXV 25,2000.7611.7014.00EHD4X30A***8MPV125TDR & TXV 25,2000.7611.7014.00EHD4X30A***9MPV050TDR & TXV 24,6000.7611.5014.00EHD4X30A***9MPV075TDR & TXV 24,8000.7611.5014.00EHD4X30A***9MPV100TDR & TXV 24,8000.7611.7014.00EHD4X30A**MV08B15****TDR & TXV 24,8000.7611.7014.00EHD4X30A**MV12F19****TDR & TXV 24,8000.7611.7014.00EHD4X30A**MV16J22****TDR & TXV 25,0000.7612.0014.00EHD4X30A**MV20N26****TDR & TXV 24,8000.7612.0014.00EMA4X24D**TXV 23,8000.7611.0013.00FEM4X24****TDR & TXV 24,4000.7611.5014.00FEM4X30****TDR & TXV 24,6000.7611.7014.00FS(M,U)4X24****TDR & TXV 23,8000.7611.0013.00FS(M,U)4X30****TDR & TXV 24,4000.7611.0013.20H4A330GKA‡ ED*4X30B**TXV 29,0000.7711.0013.00ED*4X30B***8MPV050TDR & TXV 29,2000.7711.2013.50ED*4X30B**MV08B15****TDR & TXV 29,4000.7711.5014.00ED*4X30F**TXV 29,0000.7711.0013.00− continued on next page −PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A3421 61 5400 017Specifications subject to change without notice.COOLING PERFORMANCE FOR COMBINATION RATINGS (continued)Current Indoor ModelsOutdoor SEERCooling (95 °F)Model w/ field R−410A TXV+TDRw/ field R−410A TXVw/ field TDRfactoryEERS/TBTU/hrFactoryInstalled Furnace ModelCurrent Indoor Model(‡ tested combo)H4A330GKA (continued)ED*4X30F***8MPV075TDR & TXV 29,4000.7711.5014.00ED*4X30F***9MPV050TDR & TXV 29,0000.7711.2013.50ED*4X30F***9MPV075TDR & TXV 29,2000.7711.2013.50ED*4X30F**MV12F19****TDR & TXV 29,8000.7711.5014.00ED*4X36B**TXV 29,0000.7711.0013.00ED*4X36B***8MPV050TDR & TXV 29,4000.7711.2013.50ED*4X36B**MV08B15****TDR & TXV 29,4000.7711.5014.00ED*4X36F**TXV 29,0000.7711.0013.00ED*4X36F***8MPV075TDR & TXV 29,4000.7711.5014.00ED*4X36F***9MPV050TDR & TXV 29,2000.7711.2013.50ED*4X36F***9MPV075TDR & TXV 29,2000.7711.2013.50ED*4X36F**MV12F19****TDR & TXV 29,8000.7711.7014.00ED*4X36J**TXV 29,0000.7711.0013.00ED*4X36J***8MPV100TDR & TXV 29,6000.7711.7014.00ED*4X36J***8MPV125TDR & TXV 29,6000.7711.7014.00ED*4X36J***9MPV100TDR & TXV 29,6000.7711.5014.00ED*4X36J**MV16J22****TDR & TXV 29,6000.7711.7014.00EHD4X30A**TXV 28,8000.7711.0013.00EHD4X30A***8MPV050TDR & TXV 29,2000.7711.2013.50EHD4X30A***8MPV075TDR & TXV 29,2000.7711.5014.00EHD4X30A***8MPV100TDR & TXV 29,6000.7711.5014.00EHD4X30A***8MPV125TDR & TXV 29,6000.7711.5014.00EHD4X30A***9MPV050TDR & TXV 28,8000.7711.0013.20EHD4X30A***9MPV075TDR & TXV 29,0000.7711.2013.50EHD4X30A***9MPV100TDR & TXV 28,8000.7711.5014.00EHD4X30A***9MPV125TDR & TXV 29,2000.7711.5014.00EHD4X30A**MV08B15****TDR & TXV 29,6000.7711.5014.00EHD4X30A**MV12F19****TDR & TXV 29,8000.7711.5014.00EHD4X30A**MV16J22****TDR & TXV 29,6000.7711.7014.00EHD4X30A**MV20N26****TDR & TXV 29,6000.7711.7014.00EHD4X36A**TXV 29,0000.7711.0013.00EHD4X36A***8MPV050TDR & TXV 29,4000.7711.5014.00EHD4X36A***8MPV075TDR & TXV 29,4000.7711.5014.00EHD4X36A***8MPV100TDR & TXV 29,4000.7711.7014.00EHD4X36A***8MPV125TDR & TXV 29,2000.7711.7014.00EHD4X36A***9MPV050TDR & TXV 29,2000.7711.2013.50EHD4X36A***9MPV075TDR & TXV 29,2000.7711.5014.00EHD4X36A***9MPV100TDR & TXV 29,6000.7711.5014.00EHD4X36A***9MPV125TDR & TXV 29,6000.7711.7014.00EHD4X36A**MV08B15****TDR & TXV 29,4000.7711.7014.00EHD4X36A**MV12F19****TDR & TXV 29,8000.7711.7014.00EHD4X36A**MV16J22****TDR & TXV 29,6000.7711.7014.00EHD4X36A**MV20N26****TDR & TXV 29,6000.7711.7014.00EMA4X36D**TXV 28,8000.7711.0013.00FEM4X30****TDR & TXV 29,2000.7711.5014.00FEM4X36****TDR & TXV 30,0000.7711.5014.00FS(M,U)4X30****TDR & TXV 28,8000.7711.0013.00FSU4X36****TDR & TXV 29,0000.7711.0013.00H4A336GKAED*4X36B**TXV 34,8000.7711.0013.00ED*4X36B**MV08B15****TDR & TXV 34,8000.7711.2013.50‡ ED*4X36F**TXV 35,0000.7711.0013.00ED*4X36F***8MPV075TDR & TXV 34,8000.7711.2013.50ED*4X36F***9MPV050TDR & TXV 34,4000.7711.0013.20ED*4X36F***9MPV075TDR & TXV 34,6000.7711.0013.20ED*4X36F**MV12F19****TDR & TXV 35,0000.7711.5014.00ED*4X36J**TXV 35,0000.7711.0013.00ED*4X36J***8MPV100TDR & TXV 35,2000.7711.5014.00ED*4X36J***8MPV125TDR & TXV 35,2000.7711.5014.00ED*4X36J***9MPV100TDR & TXV 35,2000.7711.2013.50ED*4X36J**MV16J22****TDR & TXV 35,0000.7711.7014.00ED*4X42J**TXV 35,2000.7711.0013.00ED*4X42J***8MPV100TDR & TXV 35,4000.7711.5014.00ED*4X42J***8MPV125TDR & TXV 35,4000.7711.5014.00ED*4X42J***9MPV100TDR & TXV 35,4000.7711.2013.50ED*4X42J**MV16J22****TDR & TXV 35,2000.7711.5014.00ED*4X42L**TXV 35,2000.7711.0013.00− continued on next page −PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A38421 61 5400 01Specifications subject to change without notice.COOLING PERFORMANCE FOR COMBINATION RATINGS (continued)Current Indoor ModelsOutdoor SEERCooling (95 °F)Model w/ field R−410A TXV+TDRw/ field R−410A TXVw/ field TDR factoryEERS/TBTU/hrFactoryInstalled Furnace ModelCurrent Indoor Model(‡ tested combo)H4A336GKA (continued)ED*4X42L***9MPV125TDR & TXV 35,0000.7711.5014.00EHD4X36A**TXV 35,0000.7711.0013.00EHD4X36A***8MPV050TDR & TXV 34,8000.7711.2013.50EHD4X36A***8MPV075TDR & TXV 34,8000.7711.2013.50EHD4X36A***8MPV100TDR & TXV 35,0000.7711.5014.00EHD4X36A***8MPV125TDR & TXV 35,8000.7711.5014.00EHD4X36A***9MPV050TDR & TXV 34,4000.7711.2013.50EHD4X36A***9MPV075TDR & TXV 34,6000.7711.2013.50EHD4X36A***9MPV100TDR & TXV 34,8000.7711.5014.00EHD4X36A***9MPV125TDR & TXV 35,0000.7711.5014.00EHD4X36A**MV08B15****TDR & TXV 35,0000.7711.5014.00EHD4X36A**MV12F19****TDR & TXV 35,0000.7711.7014.00EHD4X36A**MV16J22****TDR & TXV 35,6000.7711.7014.00EHD4X36A**MV20N26****TDR & TXV 35,6000.7711.7014.00EHD4X42A**TXV 35,2000.7711.0013.00EHD4X42A***8MPV050TDR & TXV 35,2000.7711.2013.50EHD4X42A***8MPV075TDR & TXV 35,4000.7711.5014.00EHD4X42A***8MPV100TDR & TXV 35,4000.7711.5014.00EHD4X42A***8MPV125TDR & TXV 35,4000.7711.7014.00EHD4X42A***9MPV050TDR & TXV 34,8000.7711.2013.50EHD4X42A***9MPV075TDR & TXV 35,2000.7711.2013.50EHD4X42A***9MPV100TDR & TXV 35,6000.7711.5014.00EHD4X42A***9MPV125TDR & TXV 35,8000.7711.5014.00EHD4X42A**MV08B15****TDR & TXV 35,6000.7711.5014.00EHD4X42A**MV12F19****TDR & TXV 35,2000.7711.7014.00EHD4X42A**MV16J22****TDR & TXV 36,2000.7711.7014.00EHD4X42A**MV20N26****TDR & TXV 36,2000.7711.7014.00EMA4X36D**TXV 34,8000.7711.0013.00FEM4X36****TDR & TXV 35,6000.7711.5014.00FEM4X42****TDR & TXV 36,0000.7711.5014.00FS(M,U)4X42****TDR & TXV 35,4000.7711.0013.00FSM4X36****TDR & TXV 35,4000.7711.0013.00FSU4X36****TDR & TXV 34,4000.7711.0013.00H4A342GKA‡ ED*4X42J**TXV 42,0000.7511.0013.00ED*4X42J***8MPV100TDR & TXV 42,0000.7511.5014.00ED*4X42J***8MPV125TDR & TXV 42,0000.7511.5014.00ED*4X42J***9MPV100TDR & TXV 42,0000.7511.2013.50ED*4X42J**MV16J22****TDR & TXV 42,5000.7511.5014.00ED*4X42L**TXV 42,0000.7511.0013.00ED*4X42L***9MPV125TDR & TXV 42,5000.7511.0013.20ED*4X48F**TXV 43,0000.7511.0013.00ED*4X48F***8MPV075TDR & TXV 43,0000.7511.2013.50ED*4X48J**TXV 42,5000.7511.0013.00ED*4X48J***8MPV100TDR & TXV 42,5000.7511.5014.00ED*4X48J***8MPV125TDR & TXV 43,0000.7511.5014.00ED*4X48J***9MPV100TDR & TXV 43,0000.7511.0013.20ED*4X48J**MV16J22****TDR & TXV 43,5000.7511.7014.00ED*4X48L**TXV 42,5000.7511.0013.00ED*4X48L***9MPV125TDR & TXV 43,0000.7511.5014.00EHD4X42A**TXV 42,0000.7511.0013.00EHD4X42A***8MPV075TDR & TXV 42,0000.7511.2013.50EHD4X42A***8MPV100TDR & TXV 42,5000.7511.2013.50EHD4X42A***8MPV125TDR & TXV 42,0000.7511.5014.00EHD4X42A***9MPV100TDR & TXV 42,0000.7511.2013.50EHD4X42A***9MPV125TDR & TXV 42,0000.7511.2013.50EHD4X42A**MV16J22****TDR & TXV 42,0000.7511.7014.00EHD4X42A**MV20N26****TDR & TXV 42,0000.7511.5014.00EHD4X48A**TXV 43,0000.7511.0013.00EHD4X48A***8MPV075TDR & TXV 43,0000.7511.2013.50EHD4X48A***8MPV100TDR & TXV 42,5000.7511.5014.00EHD4X48A***8MPV125TDR & TXV 43,0000.7511.5014.00EHD4X48A***9MPV100TDR & TXV 43,0000.7511.2013.50EHD4X48A***9MPV125TDR & TXV 43,0000.7511.2013.50EHD4X48A**MV16J22****TDR & TXV 43,5000.7511.7014.00EHD4X48A**MV20N26****TDR & TXV 43,5000.7511.5014.00EMA4X48D**TXV 42,0000.7511.0013.00− continued on next page −PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A3421 61 5400 019Specifications subject to change without notice.COOLING PERFORMANCE FOR COMBINATION RATINGS (continued)Current Indoor ModelsOutdoor SEERCooling (95 °F)Model w/ field R−410A TXV+TDRw/ field R−410A TXVw/ field TDRfactoryEERS/TBTU/hrFactoryInstalled Furnace ModelCurrent Indoor Model(‡ tested combo)H4A342GKA (continued)FEM4X42****TDR & TXV 43,0000.7511.5014.00FEM4X48****TDR & TXV 44,0000.7511.7014.00FS(M,U)4X42****TDR & TXV 42,0000.7511.0013.00FS(M,U)4X48****TDR & TXV 43,0000.7511.0013.20FSM4X36****TDR & TXV42,5000.7511.0013.00H4A348GKAED*4X48F**TXV 46,5000.7611.0013.00‡ ED*4X48J**TXV 47,0000.7611.0013.00ED*4X48J***8MPV125TDR & TXV 47,0000.7611.0013.20ED*4X48J**MV16J22****TDR & TXV47,0000.7611.2013.50ED*4X48L**TXV 47,0000.7611.0013.00ED*4X48L***9MPV125TDR & TXV46,5000.7611.0013.20ED*4X60J**TXV 48,0000.7611.0013.00ED*4X60J***8MPV100TDR & TXV 48,5000.7611.2013.50ED*4X60J***8MPV125TDR & TXV 47,5000.7611.2013.50ED*4X60J***9MPV100TDR & TXV 48,0000.7611.0013.20ED*4X60J**MV16J22****TDR & TXV49,0000.7611.5014.00ED*4X60L**TXV 48,0000.7611.0013.00ED*4X60L***9MPV125TDR & TXV48,0000.7611.2013.50EHD4X48A**TXV 47,0000.7611.0013.00EHD4X48A***8MPV100TDR & TXV 47,0000.7611.0013.20EHD4X48A***8MPV125TDR & TXV 47,0000.7611.0013.20EHD4X48A***9MPV125TDR & TXV 47,0000.7611.0013.20EHD4X48A**MV16J22****TDR & TXV 47,0000.7611.2013.50EHD4X48A**MV20N26****TDR & TXV47,0000.7611.2013.50EHD4X60A**TXV 48,0000.7611.0013.00EHD4X60A***8MPV100TDR & TXV 48,5000.7611.2013.50EHD4X60A***8MPV125TDR & TXV 47,5000.7611.2013.50EHD4X60A***9MPV125TDR & TXV 48,0000.7611.2013.50EHD4X60A**MV16J22****TDR & TXV 49,0000.7611.5014.00EHD4X60A**MV20N26****TDR & TXV49,0000.7611.5014.00EMA4X48D**TXV 46,0000.7611.0013.00FEM4X48****TDR & TXV 48,0000.7611.2013.50FEM4X60****TDR & TXV 49,0000.7611.5014.00FS(M,U)4X48****TDR & TXV 47,5000.7611.0013.00FS(M,U)4X60****TDR & TXV48,0000.7611.0013.00H4A360GKAED*4X60J**TXV 59,0000.7611.0013.00ED*4X60J***8MPV100TDR & TXV 58,5000.7611.0013.20ED*4X60J**MV16J22****TDR & TXV59,5000.7611.0013.20‡ ED*4X60L**TXV 59,5000.7611.0013.00ED*4X60L***9MPV125TDR & TXV57,5000.7611.0013.20EHD4X60A**TXV 59,5000.7611.0013.00EHD4X60A***8MPV100TDR & TXV 58,5000.7611.0013.20EHD4X60A***9MPV125TDR & TXV 57,0000.7611.0013.20EHD4X60A**MV16J22****TDR & TXV 59,5000.7611.0013.20EHD4X60A**MV20N26****TDR & TXV 59,5000.7611.2013.50FEM4X60****TDR & TXV 60,5000.7611.0013.20FS(M,U)4X60****TDR & TXV59,0000.7611.0013.00PRODUCT SPECIFICATIONS Split System Air Conditioner: H4A310421 61 5400 01Specifications subject to change without notice.COOLING PERFORMANCE FOR COMBINATION RATINGSObsolete Indoor ModelsOutdoor Model ObsoleteIndoorModelFurnace Model FactoryInstalled Cooling (95 °F)SEERBTU/hr S/T EER factoryw/ field TDRw/ field R−410A TXV w/ field R−410A TXV+TDRH4A318GKAEBP18****TDR 16,7000.7710.7012.40EBP24****TDR 17,5000.7710.7012.95EBV24****TDR & TXV 18,2000.7711.7014.00EBXX18****TDR & TXV 17,5000.7711.0013.00EBXX24****TDR & TXV 17,6000.7711.0013.20EL*18B****NONE 16,1000.7710.1011.65EL*24B****NONE 16,8000.7710.5512.20EL*24B****MV08B15****TDR 17,1000.7711.5014.00EMH24F****NONE 16,8000.7710.5512.20EP*18B****NONE 16,1000.7710.1011.65EP*24B****NONE 16,8000.7710.5512.20EP*24B****MV08B15****TDR 17,1000.7711.5014.00EP*24F****NONE 16,8000.7710.5512.20EP*24F****MV12F19****TDR 17,1000.7711.5014.00EPP024****NONE 15,8000.779.7511.50EXX*24B****TXV 17,7000.7710.7012.95EXX*24B****MV08B15****TDR & TXV 18,3000.7711.7014.00EXX*24F****TXV 17,7000.7710.7012.95EXX*24F****MV12F19****TDR & TXV 18,3000.7711.7014.00FWM18****TDR 16,8000.7710.7012.85FWM24****TDR 17,4000.7710.7012.75H4A324GKAEBP24****TDR 23,6000.7610.7012.95EBP30****TDR 24,0000.7611.0013.20EBV24****TDR & TXV 24,6000.7611.5014.00EBV36****TDR & TXV 24,6000.7611.7014.00EBXX18****TDR & TXV 23,6000.7610.7012.95EBXX24****TDR & TXV 24,0000.7611.0013.20EL*24B****NONE 22,4000.7610.7012.20EL*24B*****8MPV050TDR 22,6000.7611.0013.00EL*24B****MV08B15****TDR 23,0000.7611.2013.50EL*30B****NONE 22,8000.7610.7012.40EL*30B*****8MPV050TDR 23,0000.7611.0013.00EL*30B****MV08B15****TDR 23,2000.7611.2013.50EMH24F****NONE 22,4000.7610.7012.20EMH30F****NONE 22,8000.7610.7012.40EP*24B****NONE 22,4000.7610.7012.20EP*24B*****8MPV050TDR 22,6000.7611.0013.00EP*24B****MV08B15****TDR 23,0000.7611.2013.50EP*24F****NONE 22,4000.7610.7012.20EP*24F*****9MPV050TDR 22,8000.7611.0013.00EP*24F*****9MPV075TDR 22,6000.7611.0013.20EP*24F****MV12F19****TDR 22,8000.7611.2013.50EP*30B****NONE 22,8000.7610.7012.40EP*30B*****8MPV050TDR 23,0000.7611.0013.20EP*30B****MV08B15****TDR 23,2000.7611.2013.50EP*30F****NONE 22,8000.7610.7012.40EP*30F*****9MPV050TDR 23,0000.7611.2013.50EP*30F*****9MPV075TDR 23,2000.7611.0013.20EP*30F****MV12F19****TDR 23,4000.7611.5014.00EPP024****NONE 20,8000.769.8011.40EPP030****NONE 22,0000.7610.6512.00EXX*24B****TXV 24,0000.7611.0013.00EXX*24B*****8MPV050TDR & TXV 24,2000.7611.2013.50EXX*24B****MV08B15****TDR & TXV 24,2000.7611.7014.00EXX*24F****TXV 24,0000.7611.0013.00EXX*24F*****8MPV075TDR & TXV 24,4000.7611.2013.50EXX*24F*****9MPV050TDR & TXV 24,2000.7611.2013.50EXX*24F*****9MPV075TDR & TXV 24,0000.7611.2013.50EXX*24F****MV12F19****TDR & TXV 24,4000.7611.7014.00FWM24****TDR 23,6000.7610.7012.70FWM30****TDR 24,0000.7610.7012.90H4A330GKAEBP30****TDR 28,4000.7710.7012.90EBP36****TDR 28,6000.7710.7012.60EBV24****TDR & TXV 29,2000.7711.2013.50EBV36****TDR & TXV 29,4000.7711.5014.00EBV48****TDR & TXV 30,4000.7711.7014.00− continued on next page −COOLING PERFORMANCE FOR COMBINATION RATINGS (continued)Obsolete Indoor ModelsOutdoorSEER Cooling (95 °F)Modelw/ fieldR−410ATXV+TDRw/ fieldR−410ATXVw/ fieldTDRfactoryEERS/TBTU/hrFactoryInstalledFurnaceModelObsoleteIndoorModelH4A330GKA (continued)EBXX36****TDR & TXV29,0000.7711.0013.00EL*30B****NONE26,8000.7710.2511.90 EL*30B*****8MPV050TDR26,8000.7710.2012.25EL*30B****MV08B15****TDR27,0000.7710.7012.80EL*36B****NONE27,8000.7710.7012.40 EL*36B*****8MPV050TDR28,0000.7710.7012.80EL*36B****MV08B15****TDR28,0000.7711.0013.20EL*36F****NONE27,8000.7710.7012.40 EL*36F*****8MPV075TDR28,2000.7711.0013.20EL*36F*****9MPV050TDR27,8000.7710.7012.80EL*36F*****9MPV075TDR28,0000.7710.7012.90EL*36F****MV12F19****TDR28,4000.7711.2013.50EMH30F****NONE26,8000.7710.7011.90 EMH36F****NONE27,8000.7710.7012.40 EP*30B****NONE26,8000.7710.7011.90 EP*30B*****8MPV050TDR26,8000.7710.3012.25EP*30B****MV08B15****TDR27,0000.7710.7012.90EP*30F****NONE26,8000.7710.7011.90 EP*30F*****8MPV075TDR27,0000.7710.7012.70EP*30F*****9MPV050TDR26,8000.7710.2012.25EP*30F*****9MPV075TDR26,8000.7710.2512.30EP*30F****MV12F19****TDR27,4000.7711.0013.00EP*36B****NONE27,8000.7710.3512.40EP*36B*****8MPV050TDR28,0000.7710.7012.90EP*36B****MV08B15****TDR28,0000.7711.0013.20EP*36F****NONE27,8000.7710.3512.40 EP*36F*****8MPV075TDR28,2000.7711.0013.20EP*36F*****9MPV050TDR27,8000.7710.7012.80EP*36F*****9MPV075TDR28,0000.7710.7012.90EP*36F****MV12F19****TDR28,4000.7711.2013.50EP*36J****NONE27,8000.7710.3512.40 EP*36J*****8MPV100TDR28,0000.7711.2013.50EP*36J*****8MPV125TDR28,0000.7711.2013.50EP*36J*****9MPV100TDR28,0000.7711.0013.20EP*36J****MV16J22****TDR28,4000.7711.2013.50EPP030****NONE25,8000.779.5511.45 EPP036****NONE26,2000.779.8011.70 EXX*36B****TXV29,0000.7711.0013.00EXX*36B*****8MPV050TDR & TXV29,2000.7711.2013.50EXX*36B****MV08B15****TDR & TXV29,4000.7711.5014.00EXX*36F****TXV29,0000.7711.0013.00EXX*36F*****8MPV075TDR & TXV29,2000.7711.2013.50EXX*36F*****9MPV050TDR & TXV29,2000.7711.0013.20EXX*36F*****9MPV075TDR & TXV29,2000.7711.0013.20EXX*36F****MV12F19****TDR & TXV29,6000.7711.5014.00EXX*36J****TXV29,0000.7711.0013.00EXX*36J*****8MPV100TDR & TXV29,8000.7711.5014.00EXX*36J*****8MPV125TDR & TXV29,8000.7711.5014.00EXX*36J*****9MPV100TDR & TXV29,8000.7711.2013.50EXX*36J****MV16J22****TDR & TXV29,6000.7711.7014.00FWM30****TDR28,6000.7710.7012.65H4A336GKA EBP36****TDR34,0000.7710.7012.45 EBP42****TDR34,8000.7710.7012.75EBV36****TDR & TXV35,4000.7711.2013.50EBV48****TDR & TXV36,8000.7711.7014.00EBXX36****TDR & TXV34,8000.7710.7012.75EL*36B****NONE32,4000.7710.3012.30EL*36B****MV08B15****TDR33,0000.7711.0013.00EL*36F****NONE33,2000.7710.2512.25EL*36F*****8MPV075TDR33,0000.7710.7012.95EL*36F*****9MPV075TDR32,8000.7710.7012.65EL*36F****MV12F19****TDR33,4000.7711.0013.20EL*42F****NONE34,0000.7710.7012.70EL*42F*****8MPV075TDR34,2000.7711.0013.20EL*42F*****9MPV075TDR34,0000.7710.7012.80EL*42F****MV12F19****TDR34,4000.7711.2013.50− continued on next page −。
油冷机说明书中文版
重要通告1.使用本产品前,请用户或操作者认真阅读并理解本使用手册。
2.只有能够遵守安全操作要求的人才被允许操作使用本产品。
对因为没有理解本使用手册或没有严格按照本使用手册的使用要求进行操作而造成的安全事故或伤害,本公司不承担任何法律责任。
3.对不能按照本产品使用手册的安装、使用及维护要求进行操作的,或者未经本公司售后部门授权擅自改动本产品内部线路、管路、部件、内部设定参数的,或者强行按住电气元件使其非正常工作的,本公司将不承担质保期内的保修服务。
4.使用时应保证被控制对象及使用环境对本产品本身没有影响或伤害。
5.在把本产品连接之前确保先接地线,否则可能会导致触电或短路。
6.本产品所有的接线和接管必须由专业技术人员按照规范要求进行操作。
7.应按照规定的电工接线标准及使用手册中的接线方法说明进行接线,否则可能会导致触电、火灾或功能障碍。
8.在接线或拆线之前必须切断总电源,不小心碰到电气元件或带电部分可能导致触电。
9.本产品工作时内部的某些部件或管路温度会很高,请不要碰这些部件或管路,否则会烫伤。
10.不要用铅笔头或其它尖东西进行操作,否则会导致功能障碍。
11.本产品的维修只能由生产厂家或有授权资格的服务工程师执行。
12.若本使用手册与本公司产品样本的内容发生冲突,请以本使用手册为准。
13.本使用手册仅供用户和操作者使用。
本使用手册及所包含的技术图纸都禁止被复印、传播或出于市场竞争的目的自用或提供给第三方。
如经发现,本公司将依法追究其法律责任。
14.本使用手册的内容变更时恕不另行通知。
15.本使用手册的最终解释权归本公司所有。
16.本使用手册的版权归本公司所有。
目录1.概述................................................................................................4 2.基本结构及原理.............................................................................................4基本结构.............................................................................................4制冷系统 (4)2.2.1基本配置 (4)2.2.1原理描述.............................................................................................4油路系统 (5)2.3.1基本配置 (5)2.3.2 原理描述 (5)电气系统基本配置及说明 (5)2.4.1基本配置 (5)2.4.2温度控制器 (5)2.4.3开关 (5)2.4.4运行及报警灯 (6)2.4.5电气元件符号说明 (6)3.工作模式................................................................................................6制冷工作模式 (6)制热工作模式(可选) (6)4.安装 (7)安装要求 (6)4.1.1安装环境 (7)4.1.2安装基础 (7)4.1.3安装原则 (7)4.1.4吊装要求.............................................................................................8基本安装步骤 (8)油路连接 (8)4.3.1接口要求 (8)4.3.2管径及长度要求 (8)4.3.3油管要求 (8)4.3.4外置油泵安装要求 (8)4.3.5油箱吸/回油口位置要求 (8)4.3.6油过滤器安装要求 (9)4.3.7其它使用要求..........................................................................................9电气连接 (9)4.4.1电源要求 (9)4.4.2电源接线 (9)4.4.3外油泵控制连锁 (10)4.4.4远程控制接口 (10)4.4.5报警输出接口.......................................................................................10 5.使用操作 (10)使用前的检查 (10)5.1.1油管路检查 (10)5.1.2电气开关检查 (10)设置 (10)5.2.1温度控制器操作面板说明 (10)5.2.2温度控制器的设置方法 (11)油温设定…………………………………………………………………………开机 (11)关机 (12)6.温度控制器各参数库表 (12)I C901各参数库表 (12)6.1.1C P参数库 (12)6.1.2d i S参数库 (12)6.1.3C n F参数库 (12)I C915各参数库表 (13)6.2.1r E1/r E2参数库 (13)6.2.2d i S参数库 (13)6.2.3C n F参数库………………………………………………………………………………137.日常保养检查…………………………………………………………………………保养检查概述…………………………………………………………………………………14保养检查操作说明…………………………………………………………………………148.常见故障处理 (15)YL15-YL300 (15)YL400-YL1200 (16)9.技术参数及使用条件…………………………………………………………………………...17技术参数 (17)设定参数 (17)使用条件 (17)10.图表清单 (17)11.联系信息 (17)电话、传真、电子邮箱………………………………………………………………………… (17)附图一:油冷机电气原理图(YLD15~YLD400)或油冷机主电路原理图(YLD500~YLD1200)附图二:油冷机控制电路原理图(YLD500~YLD1200)1.概述在液压系统或润滑系统工作过程中,由于系统溢流、卸荷、摩擦等因素的影响,引起液压油或润滑油的温度不断升高。
油冷机说明书
工业用油冷却机使用说明书一、产品性能及用途液体冷却机能有效地降低机械设备冷却水和切削液的温度,保证机械设备冷却系统的正常温度,并使冷却液的温度能控制在理想状态下,从而消除了机械设备中由于热带来的不良影响,并提高了机械设备的使用寿命和机械加工质量水平。
本产品分XLW型、XLW-P型、XLW-PT型XLW-C型四大系列,二十多个品种,可广泛用于CNC综合加工中心,各种高精度车床、磨床、铣床等机床设备和各种液压设备、专用设备,是机械加工工业必不可少的液体温度控制装置。
二、工作原理液体冷却机外围空气经过冷凝器,将冷凝器中来自压缩机的高温高压气态制冷剂冷却为高温高压的液态制冷剂,此液态制冷剂经毛细管降压、降温,成为易于蒸发的低温低压液态制冷剂,至蒸发器中蒸发吸热,将经过管外、来自机械设备的液体冷却,液体冷却机内液体泵或机械设备中的循环泵将冷却的液体送到工作设备,使设备降温。
此液态制冷剂经蒸发吸热成为气态,再回到压缩机,完成一次冷却循环。
经过不断的冷却循环使液体温度逐渐降低,并保持最佳状态,从而保证机械设备在高效率、高精度下运行。
三、结构特点工业用液体冷却机主要由制冷系统、空气循环系统、液体循环系统和XLW-P型电子控制系统等组成,其主要特点为:1、机组采用整体结构,结构紧凑,节省安装空间。
2、制冷系统为全封闭循环系统,采用条翅式散热片的热交换器,高效全封闭制冷压缩机,低噪音、大风量风机,高效板式换热器,XLW-□型液体循环泵(XLW-P)型制冷能力强、换热效率高、密封性能好,在使用期间无需填充制冷剂和润滑油。
3、为防止由于温度过低而使板式换热器出现故障,特增加了防冻保护器。
4、电子控制系统采用轻触摸按键式微电脑控制,具有压缩机工作控制、液体泵工作控制、压缩机延时启动、过载保护、电机逆相序保护、制冷系统高低压保护、防冷冻保护及故障报警、液体温度自动控制和调节、液体温度设定及实际液体温度数码显示等多种功能。
操作简单,功能齐全,性能稳定可靠。
大金 CUW--D型说明书(M03SK001C)
漏电断路器 电源总开关
机组
11
冷冻水管安装
在进水管上必须安装过滤器, 并在合适位置设置集渣器。 如果砂砾、渣物、铁锈等进入 水系统,将使金属材料受到机 械损伤。(过滤器和集渣器必 须定期维护,安装时应预留维 修空间)
本机组不附带水泵。使用时 务必选择安装合适的水泵以 克服水管阻力。
机组进、出口水管上应安装 水量调节阀(截止阀)。
1d
DAIKIN 水冷式单螺杆冷水机组
使用说明书
适用于以下机型
CUW40D5Y CUW50D5Y CUW60D5Y CUW80D5Y CUW90D5Y CUW100D5Y CUW110D5Y CUW120D5Y CUW140D5Y CUW160D5Y CUW180D5Y CUW200D5Y CUW220D5Y CUW240D5Y CUW260D5Y CUW280D5Y CUW300D5Y CUW320D5Y CUW340D5Y CUW360D5Y CUW80DS5Y CUW100DS5Y CUW120DS5Y
控制箱门开启时不能启动机组以 免引起电击或火灾。
8
!注
禁止改变安全保护装置的设置 保护装置失控将造成火灾事故。
机身上禁止摆设液体容器(如花 瓶等)。 如果液体溢出流入机组内会损 坏电气装置从而导致电击事故。
清扫时应使机组停止运转并切 断电源,以免造成意外伤害。
!
冷冻水、冷却水禁止饮用 饮用冷冻水、冷却水有害健康。
!
禁止采用任何方法改装机组构件。 否则可能造成电击或着火。
意
机组移位应得到大金公司技术指 导。 自行移位可能引起电击或着火事 故。
!
!注
依法进行废液、废水处理。 非法处理不仅违法,而且对健康和 环境均有害处。
大金VRV3技术手册
变频风扇
由于该系统为空气热交换系统,因此,风扇使用变频器以 8 级转速运转。
电子膨胀阀(总:EV1)
在加热操作过程中,使用 PI 控制,使空气换热器的出口过 热度保持稳定。
电子膨胀阀(过冷:EV3) 使用 PI 控制,使过冷换热器的出口过热度保持稳定。
电磁阀(热气体:SVP) 用于防止低压瞬时下降。
R6T
R7T
变频压缩机(INV)
变频压缩机使用变频器运转,频率为 26rps 至 105rps;而
标准压缩机 1 (STD 1)
标准压缩机仅采用商用电源运转。变频压缩机与标准压缩 机结合运行时的运行级数如下。 RXYQ10,12P:37 级
变频风扇
由于该系统为空气热交换系统,因此,风扇使用变频器以 9 级转速运转。
电子膨胀阀(总:EV1)
在加热操作过程中,使用 PI 控制,使空气换热器的出口过 热度保持稳定。
电子膨胀阀(过冷:EV3) 使用 PI 控制,使过冷换热器的出口过热度保持稳定。
电磁阀(热气体:SVP) 用于防止低压瞬时下降。
电磁阀(回油:SVO) 用于从储液器向压缩机回油。
四通阀
用于在冷却和加热模式之间切换。
[冷却操作] 控制压缩机容量,对 Te 进行调整以达到目标值 (TeS)。 Te 设定值(在设置模式 2 下进行该设置)
Te 设置
M(正常出厂
L
H
设置)
Te:低压等价饱和温度(℃)
TeS:目标 Te 值 (因 Te 设置、操作频率等的不同而不同)
*在带多台室外机的系统中,根据由压力传感器检测 到的最优先单元的值进行该控制。
制冷剂回路
Si39-505
1.2 RXYQ8P
大金空调使用手册
大金空调使用手册VRV空调系统环球财讯中心大厦空调系统采用的是日本大金公司的水环VRV (variablerefrigerant volume)中央空调系统。
VRV直译为变制冷剂流量,这是一种有用完善的独立区域控制能力的空调系统。
能够在一个制冷回路上连接多台不同规格型号的室内机,因为室外机是微电脑控制的变频式压缩机,所以每一台室内机都拥有完全独立的开关和调节的控制能力。
BRC1C611控制器介绍、1按下此钮,系统开始运转。
再按一开/关次该钮,系统停止运转。
、2运转时,该指示灯运转指示灯(红色)点亮。
当系统出现故障时,该灯闪烁。
、3只有四面出风和两面出显示(风向挡板)风的设备有该显示,内藏风管机没有该显示。
4、表示系统在预热或除霜5、表示现在的运转方式。
由左至运转方式右分别为通风、除湿、自动、制冷、制热。
、6表示程式设定的(程序设定的时间)显示系统开始运转和停止运转的时间。
、7℃”表示目前空调的设“27 设定温度定温度、8该图标只有当过滤网脏时才会出现空气过滤网清洗提示、9L低风高风送风速度显示表示风扇的速度。
H、10显示表示处于集中控制下或非主控制器表示该控制器不能进行冷暖切换(没有该显示的控制器为主控制器)、11运转模式转换选择钮:按动该按钮则设备运转模式在通风、除湿、制冷、制热切换。
(非主控制器只能在主控制器执行的模式下进行转换:当主控制器为制冷时,可以进行通风、除湿、制冷运转,当主控制器是制热时只能进行通风和制热运转。
)12、风扇速度控制钮可根据要求选择风扇的速度,“高”“低”。
13、空气滤尘网清扫指示复位钮。
14、风向调节钮(风管机没有该功能)。
15、温度设定钮:可设定需要的使用温度,该温度为设备工作目标温度。
16、时间调节钮与17、18键配合使用17、定时开、关机启动/停止钮18、定时开、关机确定/取消钮19、设置及检查钮(只有专业人员操作)20、HRV风机风量高低设置钮21、HRV风机工作模式选择钮下列现象并不表示空调机异常。
Daikin 水冷冷却机和远热源冷却机产品介绍说明书
EWWD120-540MBYN EWLD120-540MBYNApplied systemsWater-cooled chillers Remote condenser chillersNEWw w w .d a i k i n e u r o p e .c o mFlexible applicationDaikin’s unique position as a manufacturer of air conditioning equipment,compressors and refrigerants has led to its close involvement in environmental issues.For several years Daikin has had the intention to become a leader in theprovision of environmental friendly products. This challenge demands the eco design and development of a wide range of products and an energy management system;which involves energy conservation and reduction of waste.•flow switch standard supplied with the unit•water filter with diameter perforations of 1mm supplied as standard accessory •Standard fitted with victaulic joints on evaporator:-Victualic joints absorb vibrations, reduce operating sound and thermal deflection and simplify chiller piping and installation-They can accommodate 8°angles and guarantee stress free, leak tight water piping connection.Easy installationLeaving water condenser°CLeaving Water Evaporator (°C)Pull-down areaContinuous operation areaWaterGlycol60504030201044-10410162030•9 models available with cooling capacities ranging from 123 to 546kW and heating capacities from 147 to 655kW•ideal for use in severe weather conditions and over a wide operation range.•2 independent circuits from 360kW onwards•remote condenser version available (EWLD120-540MBY)•compact, simple and robust construction•extended operation range from 50°C to 60°CA range to rely on.The new large Daikin chillers are fitted with a G-type single screw compressor with stepless capacity control. The G-type stepless single screw compressor enables capacity requirements to be closely matched by modulating the sliding valve position according to the chilled water control condition. Main advantages of continuous modulation are better part load efficiency and more stable chilled water temperatures with closer control tolerance. Capacity control is infinitely variable between 30% and 100% on single circuit units and between 15% and 100% on dual circuit units.Single screw compressorElectronic control•advanced pco 2control•detailed information on and accurate control of all functional parameters by easy menu scrolling: schedule timer, floating set point, free cooling, double evaporator pump, manual pump on,date and time information, daily pump on.•chilled water and brine temperatures down to -10°C on standardunit. (Parameter in the service menu of the DDC controller must be set by the installer)•changeable digital input/output such as remote on/off, remote cooling/heating, dual setpoint and limit capacity.•self diagnostic and can be set up in several languages.•Lead lag function is standard•standard equipped with night setback and peak load limitation.•optional digital controller can be installed up to 600 m from the unit.•remote DDC (EKRUPC) can be installed up to 1,000m from the unit•thanks to the standard DICN, simultaneous operation of up to 4 chillers is allowed.This function enables a Daikin 2MW chiller plant to be operated via a single controller.NEWSHELL & TUBE CONDENSER•special header distribution system and design of water system results in high efficiency and reduced heat transfer surface•compact dimensions and lower weight result in a smaller refrigerant volume.BPHE EVAPORATOR•brazed plate heat exchanger made of stainless steel plate, brazed gas tight with copper•optimised distribution benefits of R-134a•the use of this plate heat exchanger results in a compact units: single and double circuits have the same small footprint (2,672mm x 898mm)Heat exchangerNote: 1. For refrigerant charge of EWLD-MBY , please consult the databookNOTE: 1. For refrigerant charge of EWLD-MBY , please consult the databookNominal capacitycooling (EWWD)kW cooling (EWLD)kW heating (EWWD)kW Nominal inputcooling (EWWD)kW cooling (EWLD)kW heating (EWWD)kWEER EWWD/EWLD COP Capacity steps %Refrigerant circuittype charge (1)kg control oil type oil chargel Compressor type No. of circuits/compressors Dimensionsmm Machine weight (EWWD/EWLD)kg Sound power level standard /low noise option dB(A)Casing Piping connectionsevaporator water in/outlet evaporator water drain condenser water in/outlet condenser water drain relief device outletOperation range leaving water condenser °C EWWD/EWLD condensing temperature °C leaving water evaporator°C Power supplyYN EWWD-MBYN/EWLD-MBYN120/120180/170240/240280/26012318324927311617023526514721629032728.745.261.669.232.049.866.577.934.554.072.883.44.29/3.63 4.05/3.41 4.04/3.53 3.95/3.404.2643.983.9230 ~ 100R-134a18353738thermostatic expansion valveelectronic expansion valveFVC68D7.5101014Semi-hermetic single screw compressor1/11,014 x 2,672 x 898993 / 8841,263 / 1,1001,515 / 1,3321,613 / 1,41887/8193/8794/8893/87Polyester painted galvanised steel plate / Ivory white - Munsell 5Y7.5/13"OD3" victaulicfield installation2" 1/2 victaulic 3" victaulicM61 x 1"2 x 1"20°C ~ 50°C / 25°C ~ 55°C20°C ~ 50°C / 25°C ~ 55°C20°C ~ 60°C / 25°C ~ 62°C 20°C ~ 60°C / 25°C ~ 62°C25°C ~ 55°C -10°C ~ 20°C 3~/50Hz/400VEWWD-MBYN/EWLD-MBYNNominal capacitycooling (EWWD)kW cooling (EWLD)kW heating (EWWD)kW Nominal inputcooling (EWWD)kW cooling (EWLD)kW heating (EWWD)kWEER (EWWD/EWLD)COPCapacity steps %Refrigerant circuit typecharge (1)kgcontrol oil typeoil chargelCompressor type No. of circuits/compressors Dimensionsmm Machine weight (EWWD/EWLD)kg Sound power level standart/Low Noise option dB(A)Casingmaterial / colour Piping connectionsevaporator water in/outlet evaporator water drain condenser water inlet/outlet condenser water drain relief device outletOperation range leaving water condenser °C EWWD/EWLD condensing temperature °C leaving water evaporator°C Power supplyYN360/340440/400500/480520/500540/5403664324985225463404054705005304305055806176558910712713113898.4116133144156106.91271461561674.11/3.46 4.04/3.49 3.92/3.53 3.98/3.47 3.96/3.404.023.98 3.97 3.963.9230 ~ 10015 ~ 100R-134a70727475762 x thermostatic expansion valve1x thermost. exp. val v e+1x el e ctr. exp. val v eelectronic expansion valveFVC68D102 x 10 2 x 1010 + 14 2 x 14Semi-hermetic single screw compressor2/22,000 x 2,672 x 8982,526 / 2,2002,778 / 2,4323,030 / 2,6643,128 / 2,7503,326 / 2,83696/9096/9096/9096/9096/90Polyester painted galvanised steel plate / Ivory white - Munsell 5Y7.5/13" victaulic field installation 3" victaulic M62 x 1"3 x 1"4 x 1"20°C ~ 50°C / 25°C ~ 55°C20°C ~ 50°C / 25°C ~ 55°C20°C ~ 60°C / 25°C ~ 62°C20°C ~ 60°C25°C ~ 62°C25°C ~ 55°C -10°C ~ 20°C 3~/50Hz/400VOption Number Option description Completely combinable optionsop03dual pressure relief valve on the condenser (EWWD) op12suction stop valveop52main isolator switchop57a-meter, V-meterOPLN low noise operationAvailable kitsEKCLWS Leaving water controlsensor for DICN EKAC200A BMS cardEKBMSMBA BMS gateway modbus / j-bus protocol EKBMSBNA BMS gateway bacnet protocol EKRUPC Remote user interfaceTo install EKBMSMBA, EKBMSBNA --> EKAC200A needs to be installed on the unit(S) Option required for Swedish national law SNFS 1992 : 16120180/170240280/260360/340440/400500/480520540o (S)o (S)o (S)o (S)o (S)o (S)o (S)o (S)o (S)factory mounted o o o o o o o o o factory mounted o o o o o o o o o factory mounted o o o o o o o o o factory mounted o o o o o o o o o factory mountedo o o o o o o o o kito o o o o o o o o kito o o o o o o o o kito o o o o o o o o kito o o o o o o o o kito availableunit sizeAvailability1. Nominal cooling capacities are based on: evaporator: 12°C/7°C - condenser: 30°C/35°C (EWWD); condensing temperature: 45°C (EWLD) - liquid temperature: 40°C (EWLD)2. Nominal heating capacities are based on: evaporator: 12°C/7°C - condenser: 40°C/45°C3. The sound power level is an absolute value indicating the "power" which a sound source generates. Measuring conditionsE P L E 05-51 / 685 / 05/06 / L a M o v i d a P r i n t e d o n n o n -c h l o r i n a t e d p a p e r / P r i n t e d i n B e l g i umZandvoordestraat 300B-8400 Oostende, Belgium “The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V ..Daikin Europe N.V . has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V . explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet.All content is copyrighted by Daikin Europe N.V ..”Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard.ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.Daikin units comply with the European regulations that guarantee the safety of the product.Daikin Europe NV participates in the Eurovent Certification Programme for Air Conditioners (AC),Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.。
大金空调使用手册
大金空调使用手册第一部分:安装与设置1.1 安装前的准备在安装大金空调之前,请确保您已阅读并理解本使用手册的内容。
确保安装位置符合以下要求:- 所选位置应有足够的空间容纳空调,并且要求周围没有阻挡物,以确保空气流通。
- 安装位置应远离热源、水源和其他可能影响空调性能的设备。
- 确保安装位置有稳固的支撑面,并且能够承受空调的重量。
- 安装位置应便于电源线和排水管的接入。
1.2 操作面板介绍大金空调的操作面板位于室内机上,包括以下主要部分:- 电源开关:控制空调的开启和关闭。
- 模式选择按钮:用于选择不同的操作模式。
- 温度控制按钮:用于调节设定温度。
- 风量控制按钮:用于调节风速。
- 定时功能:可以设置定时开关机的功能。
- 其他附加功能:根据空调型号的不同,还可能包括其他特殊功能按钮。
第二部分:基本操作2.1 开启与关闭按下电源开关键,空调将开启并运行。
再次按下电源开关键,空调将关闭。
2.2 模式选择通过模式选择按钮,您可以选择以下操作模式:- 制冷模式:用于降低室内温度。
可以通过温度控制按钮调节设定温度。
- 除湿模式:用于降低室内湿度。
可以通过温度控制按钮调节设定温度。
- 加热模式:用于提高室内温度。
可以通过温度控制按钮调节设定温度。
- 送风模式:仅向室内送风,不进行冷却或加热。
可以通过风量控制按钮调节风速。
2.3 温度控制与风速调节在制冷或加热模式下,您可以通过温度控制按钮调节设定温度。
调节温度较低时,空调将提供更强的冷却或加热效果。
在送风模式下,您可以通过风量控制按钮调节风速。
根据个人偏好,您可以选择低、中、高三档风速。
2.4 定时功能大金空调配备了定时功能,您可以在特定时间段内设置定时开关机。
通过按下定时功能按钮,并根据指示进行设定,空调将在设定的时间自动开启或关闭。
第三部分:高级功能3.1 睡眠模式大金空调的睡眠模式可以帮助您获得更好的睡眠质量。
通过按下睡眠模式按钮,空调将自动调整温度和风速,提供舒适的睡眠环境。
Daikin 环保冷气系统产品说明书
Specifications subject to change without notice.421 14 9300 05 Dec 2009DUCT FREE SPLIT SYSTEM HIGH WALL, R −410AEfficient 13 SEER Air Conditioners and 7.7 HSPF Heat Pumps w THRU 2 TONSS Rotary compressors in all modelsS Wireless remote for enhanced functionality S Programmable time/temperature settings S Sleep mode S DiagnosticsS Low ambient cooling feature allows safe cooling modeoperation down to −20°F outdoor ambient *S Auto −Swing louversS Compressor lockout protection S 115 volt on w and 1 ton modelsS Factory charged with R −410A refrigerantS 5 year limited compressor, 5 year limited coil and parts warrantiesRated in accordance with ARI Standard 210 and/or 240. Certification applies only when used withproper components as listed with ARI.*“A ” series models (12-2 ton) offer low ambient kit as an accessoryAir Conditioners System Model NumberOutdoor Section SizeDimensionsIndoor Section (tons)W x H x D in. (mm)DFS4A309J1BDFC4A309J1B¾30.71 x 21.26 x 10.87(780 x 540 x 276)DFF4AH09J1A¾32.09 x 11.02 x 7.68(815 x 280 x 195)DFS4A312J1BDFC4A312J1B129.92 x 23.23 x 11.42(760 x 590 x 290)DFF4AH12J1A135.67 x 11.26 x 9.25(906 x 286 x 235)DFS4A318K1BDFC4A318K1B1½33.07 x 27.36 x 13.19(840 x 695 x 335)DFF4AH18K1A1½49.21 x 12.80 x 9.06(1250 x 325 x 230)DFS4A324K1ADFC4A324K1A235.00 x 33.50 x 13.11(889 x 851 x 333)DFF4AH24K1A249.21 x 12.80 x 9.06(1250 x 325 x 230)Heat Pumps System Model NumberOutdoor Section SizeDimensionsIndoor Section (tons)W x H x D in. (mm)DFS4H309J1BDFC4H309J1B¾30.71 x 21.26 x 10.87(780 x 540 x 276)DFF4HH09J1A¾32.09 x 11.02 x 7.68(815 x 280 x 195)DFS4H312J1BDFC4H312J1B129.92 x 23.23 x 11.42(760 x 590 x 290)DFF4HH12J1A135.67 x 11.26 x 9.25(906 x 286 x 235)DFS4H318K1ADFC4H318K1A1½33.07 x 27.36 x 13.19(840 x 695 x 335)DFF4HH18K1A1½49.21 x 12.80 x 9.06(1250 x 325 x 230)DFS4H324K1ADFC4H324K1A235.00 x 33.50 x 13.11(889 x 851 x 333)DFF4HH24K1A249.21 x 12.80 x 9.06(1250 x 325 x 230)PRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)HSpecifications subject to change without notice.2421 14 9300 05Fig. 1 - DFF4(A/H)H/DFC4(A/H)3 09−12Parts List and ClearancesNote :- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe before it enters the wall to the indoor unit. This will ensure that rain will drip from the connection pipe before it enters the wall.- The illustration above is only a sketch. Different models may be slightly different.PRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)H Specifications subject to change without notice.421 14 9300 053Fig. 2 - DFF4(A/H)H/DFC4(A/H)3 18−24Parts List and ClearancesNote :- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe before it enters the wall to the indoor unit. This will ensure that rain will drip from the connection pipe before it enters the wall.- The illustration above is only a sketch. Different models may be slightly different.PRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)HSpecifications subject to change without notice.4421 14 9300 05DIMENSIONSINDOOROUTDOORSERVICE VALVE LOCATIONSPRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)HSpecifications subject to change without notice.421 14 9300 055Outdoor/Indoor Model Size 09J1B 12J1B 18K1B 24K1A PHYSICAL DATA − Air ConditionerCooling Capacity (BTU/hr)9,20011,40017,50022,000SEER13.013.013.013.0Moisture Removal Gallons/hr (Liters/hr).24 (0.9).36 (1.35).41 (1.55).53 (2.0)Indoor Fan CFM (High speed)325425630750Indoor Sound Rating (dBA High − dBA Low)53 − 3958 − 5159 − 5464 − 59Outdoor Sound Rating (dBA)65656867Liquid Line Connection Size (in.)1/41/41/43/8Vapor Line Connection Size (in.)3/81/21/25/8Maximum Vertical Separation (ft.)Indoor Higher than Outdoor 35355060Maximum Vertical Separation (ft.)Indoor Lower than Outdoor 35355060Maximum Line −set Length (ft.)6565100100Factory Charge R −410A (lbs.){2.32.94.15.3{ Models 09, 12, and 18 are factory charged for 25 feet of interconnecting line. For greater line lengths (out to the limits specified in the literature) charge should be added at 0.1 oz. per each additional foot of line added.Net Weight, Outdoor Lbs. (Kg)70.4 (32)79.2 (36)116.6 (53)149.6 (68)Net Weight, Indoor Lbs. (Kg)17.6 (8)25.3 (11.5)39.6 (18)39.6 (18)OUTDOOR ELECTRICAL DATA − Air ConditionerRequired Supply Voltage 115−1−60 AC 208/230−1−60 AC Minimum Circuit Ampacity −MCA (amps)12151114Maximum OverCurrentProtective device − MOCP (amps)20252025Compressor RLA (Rated Load Amps )LRA (Locked Rotor Amps)7.5409.9477.332.69.734.8Fan Motor Amps 0.690.690.780.62INDOOR ELECTRICAL DATA − Air ConditionerRequired Supply Voltage 35 DC208/230−1−60 AC FLA (Full Load Amps)1.1 1.180.260.39PRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)HSpecifications subject to change without notice.6421 14 9300 05Outdoor/Indoor Model Size 09J1B 12J1B 18K1B 24K1A PHYSICAL DATA − Heat PumpCooling Capacity (BTU/hr)9,60011,50017,50022,000SEER13.013.013.013.0Heating Capacity (BTU/hr)9,40011,50017,00021,400HSPF7.77.77.77.7Moisture Removal Gallons/hr (Liters/hr).24 (0.9).36 (1.35).41 (1.55).53 (2.0)Indoor Fan CFM (High speed)325425630750Indoor Sound Rating (dBA High − dBA Low)52 − 4259 − 5154 − 5855−60Outdoor Sound Rating (dBA)66647267Liquid Line Connection Size (in.)1/41/41/43/8Vapor Line Connection Size (in.)3/81/21/25/8Maximum Vertical Separation (ft.)Indoor Higher than Outdoor 35355060Maximum Vertical Separation (ft.)Indoor Lower than Outdoor 35355060Maximum Line −set Length (ft.)6565100100Factory Charge R −410A (lbs.){2.43.04.55.3{ Models 09 and 12 are factory charged for 25 feet of interconnecting line. For greater line lengths (out to the limits specified in the literature) charge should be added at 0.1 oz. per each additional foot of line added.Net Weight, Outdoor Lbs. (Kg)72.6 (33)83.6 (38)117.7 (53.5)151 (68.5)Net Weight, Indoor Lbs. (Kg)17.6 (8)25.3 (11.5)39.6 (18)39.6 (18)OUTDOOR ELECTRICAL DATA − Heat PumpRequired Supply Voltage 115−1−60 AC 208/230−1−60 AC Minimum Circuit Ampacity −MCA (amps)12151114Maximum OverCurrentProtective device − MOCP (amps)20252025Compressor RLA (Rated Load Amps )LRA (Locked Rotor Amps)7.5409.9477.332.69.734.8Fan Motor Amps 0.690.690.780.62INDOOR ELECTRICAL DATA − Heat PumpRequired Supply Voltage 35 DC208/230−1−60 AC FLA (Full Load Amps)1.1 1.180.260.39PRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)HSpecifications subject to change without notice.421 14 9300 057ACCESSORIESPart Number Description Used On Model SizeNADA001DK Condensate Pump 9, 12NADA002DK Condensate Pump 18, 24NADA002LA Low Ambient Kit *ALL NADA003CH Crankcase Heater (120V)9, 12NADA004CH Crankcase Heater (240V)18, 241173540Isolation Relay (120V) *9, 121174662Isolation Relay (240V) *18, 24* When Low Ambient Kit is used with Heat Pump, additional Isolation Relay is required.PRODUCT SPECIFICATIONS Duct Free Split System − High Wall: DFS4(A/H), DFC4(A/H)3, DFF4(A/H)HSpecifications subject to change without notice.8421 14 9300 05DUCT FREE SPLIT SYSTEM MODEL NUMBER IDENTIFICATION GUIDE − OUTDOORDFC 4A 309J 1BDFC = Duct Free CondenserDFS = Duct Free System4 = Environmentally Sound R −410A REFRIGERANT A = Air Conditioner H = Heat Pump TYPE3 = 134 = 14NAMEPLATE SEER09 = 9,000 BTUH = ¾ ton 12 = 12,000 BTUH = 1 ton 18 = 18,000 BTUH = 1½ tons 24 = 24,000 BTUH = 2 tons NOMINAL CAPACITYJ = 115−1−60K = 208/230−1−60SUPPLY VOLTAGE1 = Single Zone2 = Dual Zone3 = Tri Zone SALES CODE / FEATURESSales CodeDUCT FREE SPLIT SYSTEM MODEL NUMBER IDENTIFICATION GUIDE − INDOORDFF 4A H 09J 1BDFF = Duct Free Fan CoilDFS = Duct Free System4 = Environmentally Sound R −410A REFRIGERANTA = Air Conditioner H = Heat Pump TYPEH = High Wall U= Under Ceiling C = CassetteAPPLICATION09 = 9,000 BTUH = ¾ ton 12 = 12,000 BTUH = 1 ton 18 = 18,000 BTUH = 1½ tons 24 = 24,000 BTUH = 2 tons NOMINAL CAPACITYJ = 115−1−60K = 208/230−1−60SUPPLY VOLTAGE1 = Single Zone2 = Dual Zone3 = Tri Zone SALES CODE / FEATURESSales CodeInternational Comfort Products, LLC Lewisburg, T ennessee 37091 USA。
油冷机说明书
工业用油冷却机使用说明书一、产品性能及用途液体冷却机能有效地降低机械设备冷却水和切削液的温度,保证机械设备冷却系统的正常温度,并使冷却液的温度能控制在理想状态下,从而消除了机械设备中由于热带来的不良影响,并提高了机械设备的使用寿命和机械加工质量水平。
本产品分XLW型、XLW-P型、XLW-PT型XLW-C型四大系列,二十多个品种,可广泛用于CNC综合加工中心,各种高精度车床、磨床、铣床等机床设备和各种液压设备、专用设备,是机械加工工业必不可少的液体温度控制装置。
二、工作原理液体冷却机外围空气经过冷凝器,将冷凝器中来自压缩机的高温高压气态制冷剂冷却为高温高压的液态制冷剂,此液态制冷剂经毛细管降压、降温,成为易于蒸发的低温低压液态制冷剂,至蒸发器中蒸发吸热,将经过管外、来自机械设备的液体冷却,液体冷却机内液体泵或机械设备中的循环泵将冷却的液体送到工作设备,使设备降温。
此液态制冷剂经蒸发吸热成为气态,再回到压缩机,完成一次冷却循环。
经过不断的冷却循环使液体温度逐渐降低,并保持最佳状态,从而保证机械设备在高效率、高精度下运行。
三、结构特点工业用液体冷却机主要由制冷系统、空气循环系统、液体循环系统和XLW-P型电子控制系统等组成,其主要特点为:1、机组采用整体结构,结构紧凑,节省安装空间。
2、制冷系统为全封闭循环系统,采用条翅式散热片的热交换器,高效全封闭制冷压缩机,低噪音、大风量风机,高效板式换热器,XLW-□型液体循环泵(XLW-P)型制冷能力强、换热效率高、密封性能好,在使用期间无需填充制冷剂和润滑油。
3、为防止由于温度过低而使板式换热器出现故障,特增加了防冻保护器。
4、电子控制系统采用轻触摸按键式微电脑控制,具有压缩机工作控制、液体泵工作控制、压缩机延时启动、过载保护、电机逆相序保护、制冷系统高低压保护、防冷冻保护及故障报警、液体温度自动控制和调节、液体温度设定及实际液体温度数码显示等多种功能。
操作简单,功能齐全,性能稳定可靠。
AKZJ系列大金油冷机使用说明书
1.此处告示的注意事项是为了对您和其他每个人的危害和损害防患于未然。
由于误操作而产生的后果,区分显示如下。
危险警告注意本栏告示了可能会发生死亡或重伤两种迫切危险的内容。
本栏告示了可能会死亡或受重伤两种可能性的内容。
本栏告示了可能会发生对人体伤害、对物品造成损失的内容。
危险由具备专业知识的人来做不能超出规格范围使用须由具备搬运、安装、配管、配线、操作、保养、检修等作业专业知识的人实施。
检查电源(电压、频率)。
请不要进行超出样本、交货说明书所记载规格外使用。
以免发生主机破损、伤害、火灾、触电等重大事故危险。
不可改造设备。
连接电源配线前确认规格说明书确认质量后,放置在指定的位置电源电缆的连接应按照配线图或使用说明书的有关内容来实行。
错误配线会引起触电和火灾。
确认机器铭牌上质量后,在按外形图指定的位置采用符合额定重量要求的挂钩悬吊。
否则,会有掉落、翻倒造成的伤害和破损。
安装接地线不能在爆炸性环境中使用因配备了消音装置。
如不接地线,就有触电的危险。
不能安装在有可燃气体产生、流入、滞留、泄漏危险的场所和碳纤维飘浮的场所。
作业须在切断电源后进行不能进行拆卸和修理必须在切断电源之后才能进行作业。
带电状态作业时,会有触电的危险。
请不要进行改造。
并且,不能由本公司售后服务技术员以外的人拆卸和修理。
以免引起火灾、触电或伤害。
另外,以免产生超出质保范围的问题。
电源切断后5分钟之内不能作业。
防水因机内的高压充电部分(电容器)5分钟内放电未结束,此时作业会有触电的危险。
请不要撒水,不能让其沾水。
以免有短路和触电的危险。
设备不能在开盖的状态下运转不能在外壳和电机及电气部件盖板取下的状态下运转。
会有触电的危险。
必须执行必须执行禁止必须执行连接接地线禁止必须执行禁止分解禁止禁止禁止警告配线根据规定实施冷媒泄漏时必须对室内充分通风配线应遵照各国的配线规范实施。
否则,有燃烧和火灾的危险。
发生大量冷媒泄漏时,应遵照冷媒MSDS(产品安全数据单)的规定进行处理。
DAIKIN 商品说明书:UAT150CGXY1 UAT180CGXY1 UAT240CGXY1 U
ModelUAT150CGXY1 UAT180CGXY1 UAT240CGXY1 UAT300CGXY1 UAT150CGXY19 UAT180CGXY19 UAT240CGXY19 UAT300CGXY19150.01251.01390.01965.01988.0497.01748.0125.0700.094.01800.094.082.51800.082.5165350.050.048.01630.01710.0994.0652.0684.0652.0830.0412.0CONTROL BOX1965.0150.01988.01390.01800.082.51800.094.0700.0125.050.0350.0165.082.594.01748.01251.0497.01630.048.0855.0 142.0994.0CENTER OF GRA VITYCONTROL BOX652.0684.0652.0E n g l i s hModel: UAT180CModel: UAT150CO r i g i n a l I n s t r u c t i o n677.01076.0677.0160.02104.02110.0149.0151.02110.0158.0162.02030.048.0407.088.0138.0768.0245.01371.0770.02141.02410.01650.02430.0150.01215.0456.0456.01981.0158.0150.01251.01690.01965.01076.01988.01905.0770.02021.0147.01672.0147.0158.01672.0158.061.0200768.0170484.048.0994.0 CENTER OF GRA VITYCONTROL BOXCONTROL BOX 1045.01000.0Model: UAT300CModel: UAT240CSAFETY PRECAUTIONSE n g l i s h INSTALLATION MANUALThis manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.Special adjustment may be necessary to suit local requirements.Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.NOTICEDisposal Requirement Dismantling of the unit, treatment of the refrigerant, oil and other parts must be done in accordance with the applicable legislation.! W ARNING ! CAUTION• Installation and maintenance should be performed byqualified persons who are familiar with local codeand regulation, and experienced with this type ofappliance.• All field wiring must be installed in accordance withthe national wiring regulation.• Ensure that the rated voltage of the unit correspondsto that of the name plate before commencing wiringwork according to the wiring diagram.• The unit must be GROUNDED to prevent possiblehazard due to insulation failure.• All electrical wiring must not touch the refrigerantpiping, or any moving parts of the fan motors.• Confirm that the unit has been switched OFF beforeinstalling or servicing the unit.• Disconnect from the main power supply beforeservicing the air conditioner unit.• DO NOT pull out the power cord when the power isON. This may cause serious electrical shocks whichmay result in fire hazards.• Keep the indoor and outdoor units, power cable andtransmission wiring, at least 1m from TVs and radios,to prevent distorted pictures and static. {Dependingon the type and source of the electrical waves, staticmay be heard even when more than 1m away}.Please take note of the following important points when installing.• Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates around the unit, it may cause fire ignition.• Ensure that drainage piping is connected properly. If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.• Do not overcharge the unit. This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.• Ensure that the unit’s panel is closed after service or installation. Unsecured panels will cause the unit to operate noisily.• Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places.• Before turning off the power supply, set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not done, the unit’s fans will start turningautomatically when power resumes, posing a hazardto service personnel or the user.• Do not operate any heating apparatus too close tothe air conditioner unit.• Don’t use joined and twisted wires for incomingpower supply.• The equipment is not intended for use in apotentially explosive atmosphere.REFRIGERANT CIRCUIT DIAGRAMModel: UAT150/180/240/300CNote: UAT150/180/240/300C consists of 2 circuits in the system.42857633391No Item Description1Compressor 2High Pressure Switch 3Access Valve 4Outdoor Heat Exchanger 5Indoor Heat Exchanger 6Filter Dryer 7Thermal Expansion Valve (TXV)8Low Pressure Switch 9Subcool Circuit (Applicable to UAT150C (only)HEADER IN HEADER OUT HEADER DISTRIBUTORThermal ExpansionValve Sensor BulbINSTALLATION OF THE UNITE n g l i s h(A) Location For Installation I nstall the unit in such way that air distributed by the unit cannot be drawn in again (as in the case of short circuit of discharge air). Allow suf fi cient space for maintenance around the unit. W hen two or more units are installed in a location, they must be positioned such that one unit will not be taking the discharge air from another unit. E nsure that there is no obstruction of air fl ow into or out of the unit. Remove obstacles which block air intake or air discharge.The location must be well ventilated, so that the unit can draw and distribute plenty of air.The unit is recommended to install in:-A place capable of bearing the weight of the unit and isolating noise and vibration.A place where has adequate drainage.A place where the unit will not be buried in snow.A place where air outlet port is not exposed to strong wind.A place where the air discharge and operating sound level will not annoy the neighbours.The location where it is not accessible by general public.(B) Duct Construction T his unit are equipped with supply and return air openings. Duct connection to the unit should be made with duct fl anges and secured directly to the air openings with fl exible duct connectors to avoid normal noise transmission.To prevent air leakage, all duct seams should be sealed. Ducts in the spaces that not air-conditioned, must be insulated.Ducts exposed to the outside must be weather proofed. D ucts that entering building through the roof, the entering should be sealed with weather stripping to prevent rain, sand, dust etc, from entering the building.Correct size of fi lter must be installed at the return air duct.(C) Unit Lifting Holes at 4 corners of the unit base are used for unit lifting purpose.The spreader bar shall be slightly wider than the unit width.The insulation should be added at 4 corners of the chain to prevent the damage of the panel when lifting.Note:Unit shown in diagram is UAT300C. Other models will follow the same method in lifting.–––––••••••–––––––––Chain Lifting beamSpreader barLifting holes for shackle (4 corners)! CAUTIONDo not install the unit at altitude over 2000m(E) Space Required Around UnitRefer diagram below for the space required around the unit. Note that:-(a) All dimensions shown are in mm.(b) All space value shown are minimum clearance required for the unit.(c) Unit shown in the diagram is UAT300C. Other models shall follow the same clearance.(D) Drain PipingA 1" MPT condensate drain fitting is provided. The drain pipe can be led out at the front side. T he drain pipe must be provided with a trap on the outside of the unit and also installed at an incline for proper drainage, as shown in the right.T o prevent condensate formation and leakage, provide the drain pipe with insulation to safeguard against sweating.Upon completion of piping work, check that there is no leakage and that the water drains off properly.––––300012001200Evaporator coil & motor service, Air filter service 1200Condenser air inletThe drain piping should have a drain trap.Drain piping The drain pipe should extendbelow this level.Drain trap AB C Note: ESP = External Static PressureDrain trap for condensateA≥ 70mm B≥ 2C C ≥ 2 X ESP Evaporator coil, air filter service Condenser air inletCondenser air inletCondenser air outletCondenser air inlet Electrical control circuit service & compressor servicePHYSICAL DATAELECTRICAL DATAWIRE CONNECTIONE n g l i s hDescription ModelUAT150CUAT180C UAT240C UAT300C Power supply V/Ph/Hz380-415/3N~/50Max continuous current (Comp)A20.0/20.024.2/24.231.0/31.042.0/35.0Full load current (FLA, Comp)A13.7/13.716.8/16.822.3/22.331.0/25.0Locked rotor current (LRA, Comp)A100.0/100.0111.0/111.0118.0/118.0174.0/140.0*Min. circuit amps, MCA A48.057.072.585.0*Max. fuse amps, MFAA 63.063.080.0100.0PEab cdg e f All electrical work must be carried out by qualified electrician and accordance with local supply requirement and associate regulation.Before connecting the wire, consult the electric power company of jurisdiction.•• a.Power supply d.Unit b.Main switch/fuse (fi eld supply) e.Remote control/Thermostat f.Connection wiring for unit & remote controller c.Power supply wiring for unit g.Earth(1) The entire wiring diagram of unitDescription ModelUAT150CUAT180C UAT240C UAT300C Refrigerant R22Refrigerant charge kg4.6/4.6 6.0/6.08.0/8.010.6/10.6Evaporator air flow CFM4600650079008700L/S2171306837284106External static pressure mmAq12.5152025Pa123147196245Condenser air flow CFM9900138001223021500L/S 46726513577210149Control Mechanical Controller/Sequential ControllerCompressor (Type/Quantity)Scroll/2Air filter (Type/Quantity)Washable Saranet/2Air filter dimension (L x W x T)mm 895 x 685 x 4834 x 760 x 41040 x 750 x 4ModelPower cable (mm 2)Breaker capacity(A)Over current protection switch (A)Earth cable (mm 2)UAT150C16486316UAT180C25576325UAT240C3572.58035UAT300C 358510035Note:A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in fixed wiring in accordance with local and national legislation.The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse.F ix the power supply wiring to control module. Connect control wiring to control terminal block through the control box’s hole.Earth wiring must be connected.T he power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in protective tube.•••••Model: UAT150/180/240/300CControl wireTerminal blockPower cable CONTROLBOX(2) Wiring connection to unitRoute the power supply wires and control wire through the holes in the unit.Remove the service panels and connect the units power supply wires to terminal block inside the control box, as shown.Make use of push releasable cable ties which are located at the bottom of control box to hold the power supply wires properly•••Terminal block(3) Wiring Example And Selection Of Circuit BreakerNote:While installing the circuit breaker onto the unit, make sure that the screws do not damage the components (e.g. coil) inside the unit.•E n g l i s hRRS TF 1316AF 1315AN NN C1FZCZ1CZ2F2HN N C2F2H 123456STUL1L2L3NVWRSTUVW36857142144214! W ARNINGBefore working in this unit, isolate it from the power supply.Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate requirement of the local wiring code.••Observe the notes mentioned below when wiring to the terminal block. Precautions to be taken for power supply wiring.(Use a round crimp-style terminal for connection to the terminal block. In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction.)! CAUTIONWhen connecting the connection wires to the terminal block using a single core wire, be sure to perform curling. Problems with the work may cause heat and fires.•Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.•Stripping wire at terminal blockGoodWrongStrip wire end to this point.Excessive strip length may cause electrical shock or leakage.Round crimp-style terminalStranded wireNo.Item Description 1Contactor 2Capacitor 3Phase Protector 4Terminal Block 5Relay 6Fuse 7Transformer 8Timer9Control Module (4) Arrangement of terminal blocks and components for controller are shown as below: (a) Mechanical ControlModel : UAT150C! W ARNINGTransmission wire must be routed at least 50mm away from the power cable.Transmission wire should be a shielded wire.••R R F AS TS TUVWN N L1L2L3NN F2HN N F3HOUT FAN 3O NEUTRALDS4ID4ID3ID2ID1DS3DS2DS1ROOMTRANSFORMERLIVEOUT FAN 2OUT FAN 14WV 44WV 34WV 2IN FANCOMP 4COMP 3COMP 2COMP 14WV 1HEATER2HEATER1R S TUVWC1C23659142144121414963542L1L2L3NNNF2HNNF3H959896RSTU V WN R S TADS4DS3DS2DS1ROOM ID4ID3ID2ID1OUT FAN 3LIVEOUT FAN 2OUT FAN 14WV 44WV 34WV 2IN FANCOMP 4COMP 3COMP 2COMP 14WV 1HEATER2HEATER1NEUTRALTRANSFORMERModel : UAT180/240CModel : UAT300C(b) Sequential Control3649511141N R S TAN N NTB2OUT FAN 3OUT FAN 4NEUTRALDS4ID4ID3ID2ID1DS3DS2DS1ROOM TRANSFORMERLIVEOUT FAN 2OUT FAN 14WV 44WV 34WV 2IN FANCOMP 4COMP 3COMP 2COMP 14WV 1HEATER2HEATER1L1L2L3NRS U V WWA1A2WA1A2959896Model : UAT150C174145863542Model : UAT180/240CModel : UAT300C117114356844OPERATING RANGEPHASE PROTECTORE n g l i s hEnsure the operating temperature is within the allowable range, as stated in diagram below:Indoor WB temperature (°C)O u t d o o r D B t e m p e r a t u r e (°C )5452191419.423! CAUTIONThe use of the air conditioner outside the range of working temperature and humidity can result in serious failure.The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase protector operates, and the unit will not start. This device is located in the control box of the outdoor unit.The following table shows the LED indicator light for phase protector under normal operation and fault conditions.Notes : 1. “+” indicates additional functions for PP01 phase protector.2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 and relay 81 will cut off.LEDDescriptionPW (Red)P_R (Yellow)P_S (Yellow)P_T (Yellow)ActionsNormal operation -Reverse phase Switch off the unit. Check the 3 phase wiring.T phase missing Switch off the unit. Check the 3 phase wiring.S phase missing Switch off the unit. Check the 3 phase wiring.R phase missing Switch off the unit. Check the 3 phase wiring.S &T phase missing +Switch off the unit. Check the 3 phase wiring.Overload +High discharge temperature. Check the refrigerant system.Sensor missing +Switch off the unit. Plug in sensor.ONOFFFast Blink! W ARNINGTrouble shooting must be performed by qualified personnel.•TROUBLESHOOTINGSERVICE AND MAINTENANCEService PartsMaintenance ProceduresAir Filter- Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water(below 40°C) with a neutral cleaning detergent.- Rinse the filter well and dry before placing it back onto the unit.- Do not use gasoline, volatile substances or chemicals to clean the filter.- Clean the filter at least once every 2 weeks or more frequently if neccesary.Air filter position.Unit shown in the diagram is UAT300C. Other models shall follow the same method.Remove filter cover for filter service For any enquiries on spare parts, please contact your authorized dealer. If any malfunction of the air conditioner unit is noted, check the following fault conditions and causes for some simple troubleshooting tips.ProblemCausesActionUnit does not run.Power failure.Press the [ON/OFF] after power restore.Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.Power supply wiring phase incorrect.Modify the wiring phase.Compressor does not operate in 3 min after unit has started.Protection against frequent starting.Wait for 3 minutes for the compressor to start.Air flow is low .Filter is filled with dust and dirt.Clean the filter.There are some obstacles at the air inlet or outlet of the units.Remove pressor operate continuously .Dirty air filter.Clean the air filter.Temperature setting too low.Reset the temperature.No cool air delivered.Temperature setting too high.Set the temperature lower .If the fault persists, please call your authorized local dealer/serviceman.Air Filter Air FilterHead offi ce:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 JapanIn the event that there is any conflict in the interpretation of this manual and any translation of the same in any language, the English version of this manual shall prevail.The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior notification.••Zandvoordestraat 300, B-8400 Oostende, Belgium P.O.Box 18674, Galleries 4, 11th Floor,Downtown Jebel Ali, Dubai, UAE.。
大金 UWY_A_40-120AY使用说明书
火灾。
z 安装时,应按规定做好防风防震等防 范措施。
否则可能造成机组倾倒、坠落等事故。
z 安装选配件时应委托专业人员安装。
选配件使用时,应选用厂家指定产品, 自行选用不当易发生触电、火灾等事 故。
5
注意
z 机组不得安置于可能发生可燃性气体 泄漏之处。
一旦可燃性气体泄漏并聚集于机组周围将
可能会引发火灾。
z 机组外壳应接地。
接地线不能与气管、水管、避雷针或通 讯线路连接,接地方法错误会发生电击 事故。
z 应设置漏电断路器。
漏电断路器应按电气设备技术标准和内 线规程进行安装。错误安装将可能造成电 击事故。
z 机组禁止安装在恶劣环境中。
机组不能安装在靠近温泉、海岸地区或 多油的地域。这些自然环境对机组腐蚀 将导致电击或火灾。
■ 安装上的注意事项
为使设备发挥其最佳性能,逐条对照检查以下内容。若不符合规范,在机组运行之前务必 采取有效措施予以解决。
警告
z 安装工程应委托供货方专业安装人员 进行。
安装时,应得到大金厂方的技术指导。自 行安装不善,将导致泄漏、电击、火灾等 事故。
z 采用正确方法防止制冷剂泄漏。
在动力机房等地方安装冷水机组时应 有切实防止制冷剂泄露的措施。因为一 旦制冷剂浓度超过极限浓度,可能导致 缺氧事故。
风扇电机
重 量
机组安装 重量
机组运转
重量
kW×台数 kg kg
长度
mm
机组
尺寸
宽度
mm
高度
mm
UWA40AY UWA50AY UWA60AY UWA80AYA UWA100AY UWA120AY
18.2