变压器保护差动保护毕业设计
三绕组变压器纵差动保护的设计与仿真
摘要目前国内电力工业得到良好的发展成果,特高压输电线路创建完成,超大容量发电机组也开始产生,其中跨地区电网互联时期随之到来。
现在,电网系统更加复杂,综合规模稳步扩张,对电力系统稳定运作提出更加严苛的要求。
在电网中作为最重要的电力系统装置之一,变压器承担了电力系统中功率调节的功能,提升变压器保护的灵敏度和可靠性尤为关键。
但与其他一次性设备如母线等相比,变压器保护误动次数处于较高水平。
随着智能电站项目内开始使用电子变压器,我们也开始寻找到全新分析角度。
尤其是为此领域纵差保护的研究提出了一个新的方向。
关键词:三绕组;变压器;继电SummaryWith the development and progress of electric power in our country, the continuous construction of UHV transmission lines, the increase of super-capacity units, the era of interconnection between regions has been gradually realized, and the complexity of power grid is gradually deepening.And the scale expands unceasingly, put forward the new request to the safe operation of the electric power system. As one of the most important electrical equipment in power system, transformer is carrying the role of power porter in the power network, so it is very important to improve the sensitivity and reliability of transformer protection. However, compared with other disposable equipment such as busbar, the statistics of misoperation times of transformer protection has always been at a relatively high level, and with the gradual use of electronic transformers in intelligent power plant projects, This brings a new research idea to transformer protection, especially the research direction of transformer longitudinal differential protection.Key words: three windings; Transformer; Relay目录摘要 (1)1 变压器保护Θ (5)1.1 励磁涌流 (7)2 继电保护装置原理 (9)2.1 纵差动保护 (9)2.2 变压器瓦斯保护 (9)2.3 平行双回线路横联方向差动保护 (9)2.4 复合电压启动的过电流 (10)2.5 变压器中性点直接接地零序电流保护工作原理 (10)2.6 过电流保护的构成及工作原理 (11)3 短路电流计算 (12)3.1 基本参数 (12)3.2画出短路等值电路 (13)3.3短路电流计算的过程 (14)3.4保护装置的配置 (15)4 各保护装置的整定计算 (16)4.1纵差保护的整定计算 (16)4.2 110kV侧复合电压启动过电流保护整定计算 (18)4.3 38.5kV侧方向过流保护 (18)4.4 110kV零序过电流保护 (19)4.5 变压器气体保护的整定 (19)5 差动元件基本原理 (20)5.1 差动元件的动作方程 (20)5.2 差动电流及制动电流的取得 (21)5.3 电流互感器二次接线进行相位补偿(外转角) (22)5.4 用保护内部算法进行相位补偿(内转角) (22)5.5 CT二次断线 (25)5.6 逻辑构成框图 (26)第六章三相变压器的仿真 (29)6.1 三相变压器仿真的数学模型 (29)6.2电源电压的描述 (34)6.3铁心动态磁化过程简述 (34)7 三绕组变压器的仿真与分析 (38)7.1空载合闸 (38)7.2内部故障 (40)结论 (48)致谢 (48)三绕组变压器纵差保护的设计与仿真1 变压器保护变压器是电力领域内不容忽视的重要装备,甚至影响整个系统的正常发电,供电与平稳运作。
电力变压器保护设计大学毕设论文
错误!未找到引用源。
毕业设计设计题目电力变压器保护设计系(部)电力工程系学科专业供用电技术班级姓名学号指导教师二〇一四年四月二十三日新疆工程学院毕业设计任务书学生姓名杨志超专业班级供用电技术11-3班设计题目电力变压器保护设计接受任务日期2014-3.1 完成任务日期2014-4.26指导教师张尧指导教师单位新疆工程学院设计目标利用计算机控制技术实现对电力变压器的保护,了解三相电力系统电力变压器的保护方法,并分析电力变压器微机保护的特点,设计出保护装置的总原理图及模拟信号到数字信号的转换过程。
设计要求2014年3月1日选题2014年3月2日--16日查找资料与搜集数据2014年3月17日--4月14日设计报告2014年4月15日--4月26日修改报告教师指导过程记录2014年3月1日讲解各报告大纲分组2014年3月14日解答各组所遇到的问题2014年3月27日学生教师会面查看进度2014年4月12日查看所有人员报告,并提出修改建议。
2014年4月26日答辩参考资料【1】贺家李宋从距.电力系统继电保护原理.第三版【2】刘介才.工厂供电设计指导.【3】刘笙.电气工程基础.【4】何仰赞翁增银.电力系统分析.第三版新疆工程学院毕业设计成绩表学生姓名杨志超专业班级供用电技术11-3班设计题目电力变压器保护设计考核项目考核内容满分评分一、指导教师评分1、工作态度与纪律102、基本理论、基本知识、基本技能和外文水平103、独立工作能力、分析和解决问题能力104、完成任务的情况与水平(论文与实物硬件质量)10 指导教师签字:年月日二、评阅教师评分1、论文质量(正确性、条理性、创造性和实用性)152、成果技术水平(理论分析、计算、实验和实物性能)15 评阅教师签字:年月日三、答辩小组评分1、完成任务书所规定的内容和要求 52、论文与实物的质量 53、课题设计内容的讲述104、回答问题的正确性10 答辩组长签字:年月日四、答辩小组成绩评定:负责人签字:年月日五、答辩委员会意见:答辩委员会主任签字:年月日摘要电力变压器是电力系统中不可缺少的重要设备,他的故障给供电可靠性和系统的正常运行带来严重的后果,同时大容量变压器也是非常贵重的元件,因此,必须根据变压器的容量和重要程度装设性能良好的、动作可靠的保护元件。
变压器差动保护实验报告
变压器差动保护实验报告1#主变差动保护试验报告继电保护检验报告设备名称: 主变差动保护安装地点: 继保室负责人: 刁俊起检验性质: 新安装检验试验日期: 2012.11.24开关编号: 510、410检验单位: 山东送变电工程公司试验人员: 王振报告编写:校核:审核:刁俊起风雨殿风电场RCS-9671CS变压器差动保护装置检验报告(新安装检验)试验日期: 2012年11月24日3绝缘及耐压试验:按下表测量端子进行分组,采用1000V摇表分别测量各组回路对地及各组回路之间的绝缘电阻,绝缘电阻值均应大于10MΩ。
在保护屏端子排处将所有电流、电压及直流回路的端子连在一起,并将电流、电压回路的接地点解开。
整个回路对地施加工频电压为1000V、历时为1分钟的介质强度试验,试验4工作电源检查(1)直流电源缓慢上升时的自启动性能检验。
直流电源从零缓慢升至80%额定电压值,此时逆变电源插件应正常工作,逆变电源指示灯都应亮,保护装置应没有误动作或误发信号的现象,(失电告警继电器触点返回)。
检查结果合格(2)拉合直流电源时的自启动性能。
直流电源调至80%额定电压,断开、合上检验直流电源开关,逆变电源插件应正常工作(失电告警继电器触点动作正确)。
检查结果合格(3)工作电源输出电压值及稳定性检测保护装置所有插件均插入,分别加80%、100%、110%的直流额定电压,电源监视指示灯、液晶显示器及保护装置均处于正常工作状态,测量电源输出电压值如下: 5初步通电检查(1)打印机检验:检查结果合格(2)键盘和液晶显示检验:检查结果合格(3)保护定值整定及失电保护功能检验:检查结果合格(4)时钟设置及失电保护功能检验检查结果合格(5)软件版本和程序校验码的核对6电气特性试验6.2开出检验6.3功耗测量:(记录功耗最大一侧的测量数据)6.4模/数变换系统检查:6.4.1零漂检查:利用人机对话打印出采样值的零漂(不加任何交流量时的正常采样值),电流、电压回路6.4.2电流通道刻度检查模拟量测量误差应不超过?5%。
10000KVA(35KV10KV)主变保护
存档日期:_____________________ 存档编号:______________________XXX 大学本科生毕业论文(设计)论文题目: 10000KVA(35KV/10KV)主变保护姓名:院系:机电工程系专业:电气工程及其自动化班级:指导老师:摘要电力变压器是电力系统中非常重要的电力设备之一,它的安全运行对于保证电力系统的正常运行和对供电的可靠性,以及电能质量起着决定性的作用。
随着电力系统的发展,特别是现代新材料、新工艺的发展,变压器容量不断增大,对变压器保护的快速性和可靠性也提出了更高的要求。
本文首先通过对电力变压器的故障类型和不正常工作状态进行分析,以容量为10000KVA、电压等级35KV变10KV主变压器保护为例,提出以瓦斯保护和差动保护为主保护,以复合电压启动的过电流保护和过负荷为后备保护,再配合如温度保护等非电量保护的保护方案。
介绍了上述方案的保护原理及保护装置。
再根据方案的原理及装置的选择,举例进行保护整定和计算。
本文最后对电气测量、控制、信号等回路,变压器二次回路图进行简单的介绍。
关键词:变压器保护,瓦斯保护,差动保护,后备保护AbstractThe electric power transformer is one of the count for much electric power equipments in the electric power system, it of safety circulate for assurance electric power system of normal circulate and to the credibility of the power supply, and the electric power quality contain decisive function. With the development of power system, especially with the evolution of the modern material, new crafts and the larger capability of power transformers, the requirement for transformers protection becomes much stricter.This paper firstly power transformer fault type and not normal working condition analysis and 10000KV A, voltage rating capacity as the main transformer protection consumers 10KV 35KV change as an example, this paper put forward the gas protection and differential protection primarily protection to compound voltage over current protection and start over load for backup protection, coupled with such as temperature protection non-electric quantity of protection scheme. Introduces the principle and the protection of the aforementioned program protective device. Again according to the scheme of principle and device choice, for example to protect setting and calculation.In the end the paper for electrical measurement, control, signal circuit secondary circuit diagram, transformer briefly introduced.Key words :transformer protection,gas protection ,differential protection,backup protection目录摘要 (II)Abstract (III)1 绪论 (1)1.1 概述 (1)1.2 变压器保护的发展与现状 (2)1.3 本课题的主要工作 (3)2 电力变压器的继电保护 (4)2.1 电力变压器的故障类型及保护措施 (4)2.2 电力变压器的瓦斯保护 (5)2.3电力变压器的纵联差动保护 (9)2.4 电力变压器相间短路的后备保护 (16)2.5 电力变压器过负荷保护 (21)2.5电力变压器的温度保护 (22)3 电力变压器保护方案及算例 (24)3.1电力变压器保护方案 (24)3.2差动保护整定计算 (26)4 电气测量回路 (29)4.1电气测量回路简介及要求 (29)4.2断路器控制回路 (30)4.3二次回路的操作电源 (35)5 电力变压器的二次回路图 (37)5.1 归总式原理图 (37)5.2 展开式原理图 (37)5.3 小母线布置图 (39)6 展望 (41)致谢 (43)参考文献 (44)1绪论1.1概述电力变压器是电力系统中非常重要的电力设备之一,它的安全运行对于保证电力系统的正常运行和对供电的可靠性,以及电能质量起着决定性的作用,同时大容量电力变压器的造价也十分昂贵。
22万变电站主变压器保护设计毕业设计(论文)...
宜宾职业技术学院毕业论文(设计)基于单片机的受控正弦信号发生器设计系部自动控制工程系专业名称发电厂及其电力系统班级电力1091 班姓名刘超学号 200912463指导教师王瑞2011年9月1日22万变电站主变压器保护摘要:变压器是电力系统的重要组成部分。
它的正常与否直接关系到电力系统的安全和经济运行。
本次设计是变压器继电保护的初步设计。
根据短路计算的结果,选择了短路器,隔离开关,母线电气设备。
为了保护变压器内部和引出线套管的故障,选择了纵联差动保护作为变压器的主保护。
影响差动保护可靠性是电路中由于各种原因产生的不平衡电流。
通过计算,选择躲过外部短路时产生的最大不平衡电流作为纵联差动保护的动作电流。
本设计还选择了瓦斯保护作为变压器油箱内发生故障时的主保护。
定时限过电流保护作为变压器纵联差动保护的后备保护。
本设计要保护的变压器是处在中性点直接接地的电力系统中,所以采用零序过电流作为变压器接地的后备保护。
在本次设计中,我还选择了过负荷保护作为变压器的后备保护并对以上保护进行了整定。
目录第1章绪论........................................................2 1.1 变压器保护的历史及现状.......................................2 1.2变压器保护的发展趋势..........................................3 第2章 220KV主变压器微机型保护的双重化的探讨.......................4 2.1变压器保护双重化的意义........................................5 2.2双主双后主变压器保护电流回路接入方式..........................6 第3章3.1电力变压器的继电保护..........................................7 3.113.123.23.213.223.33.313.323.43.413.423.433.443.5第4章4.14.2第1章绪论1. 1 变压器保护的历史及现状追溯变压器保护的发展历史,以1931年R.E.Cordray提出比率差动的变压器保护标志着差动保护作为变压器主保护时代的到来。
变压器比率差动保护实验
实验三 变压器比率差动保护一、 实验目的1. 了解比率差动保护、增量差动保护的动作特性;2.熟悉变压器的接线钟点数,掌握各种接线形式的电流补偿方法; 3. 熟悉比率差动保护、差流速断保护、差流越限保护的原理; 4. 熟悉比率差动保护的逻辑组态方法。
二、实验原理及逻辑框图1.比率差动保护比率差动保护能反映变压器内部相间短路故障、高(中)压侧单相接地短路及匝间层间短路故障,该保护需要考虑励磁涌流和过励磁运行工况,同时也要考虑TA 断线、TA 饱和、TA 暂态特性不一致的情况。
由于变压器联结组不同和各侧TA 变比的不同,变压器各侧电流幅值相位也不同,差动保护首先要消除这些影响。
本保护装置利用数字的方法对变比和相位进行补偿,以下说明均基于已消除变压器各侧电流幅值相位差异的基础之上。
(1)比率差动动作方程⎪⎩⎪⎨⎧>-+-+≥≤<-+≥≤>eres e res res e op ope res res res res op op res res op op I I I I I I S I I I I I I I S I I I I I I 6),6(6.0)6(6),(,0.0.0.0.0.0.0.当当当 (3-1) opI 为差动电流,0.op I 为差动最小动作电流整定值,res I 为制动电流,0.res I 为最小制动电流整定值,S 为比率制动系数整定值,各侧电流的方向都以指向变压器为正方向。
对于两侧差动:..12|I +I |O P I = (3-2)..12|I I |2res I -=(3-3)1∙I ,2∙I 分别为变压器高、低压侧电流互感器二次侧的电流。
对于三侧及以上数侧的差动:...12k |I +I +I |O P I =+(3-4)...12k max |I ||I ||I |resI ⎡⎤=⎢⎥⎣⎦,,,(3-5)式中:43<<K ,...12k I I I ,,,分别为变压器各侧电流互感器二次侧的电流。
变压器保护及其整定计算毕业论文设计
摘要变压器是一种常见静止的电气设备,是电力部门中最关键的一次设备。
变压器的保护是变压器发生非正常运行状态和不正常运行状态时采取的保护措施,是变压器安全运行的有力保证;变压器的整定讣算是为满足电力系统选择性,速动性,灵敬性,可幕性基本要求,对电网参数,短路点的讣算及灵敏度的校验,是电力系统正常运行的前提条件。
关键词:变压器保护整定计算Take toSummary of tra nsformer is a comm on static electrical equipme nt, in the electric power sector is one of the most critical devices. Transformer protect!on is non・healthy state and not the normal operation of transformer protect!on measures taken by the State, is a guarantee of safe operation of transformer; setting calculation of transformers is to meet power system choice of liquid, sensitivity, and reliability requirements,network parameters, sensitivity of short circuit calculation and verification, Is the precondition for the normal operation of the power system.Keywords: transformer protect!on setting calculation目录1. 绪论1、1本人叙述1、2电力变压器的概述1、2、1变压器的工作原理仁2、2电力变压器的额左容量和过负荷能力乙变压器保护的配置方案2、1电力变压器保护槪述2、1、1继电保护的发展史2、1、2电力变压器保护的目的2、1、3电力变压器保护设计的基本要求2、2电力变压器的保护装置的配置原2、3电力主变压器选择2、4故障分析及应对措施2、4、1故障分析2、4、2应对措施2、4、3注意事项2、5电力变压器的保护措施3. 参数及其短路计算3、1短路的形式、原因及后果3、2电网情况及参数计算3、3短路计算4. 电力变压器保护的整泄计算4、1继电保护整定计算4、1、1继电保护整定计算的目的4、1、2继电保护整Nil•算的基本任务4、1、3整立计算运行方式的选择原则4、2压器保护的整定计算方法4、3电力变压器保护装置的选择及整定计算4、3、1电力变压器纵联差动保护4、3、2电力变压器瓦斯保护4、3、3电力变压器电流速断保护4、3、4电力变压器后备保护5. 变压器保护在应用中的问题分析5、1电力变压器励磁涌流5、2电力变压器TA二次回路异常对差动保护的彫响结束语致谢参考文献1、1本人叙述本设计为SL7-800kVA/35kV电力变压器保护设计及整定计算,毕业设计这是在全部的理论课程及完成各项实习的基础上进行的一项综合性训练环节,设计的目的有是:(1)巩固和扩大所学的专业理论知识,在毕业设计中得到灵活的应用;(2)学习和掌握变压器的保护设计的基本方法,树立正确的设计思想;(3)培养分析和解决问题的工作能力及解决实际工程设计的基本技能;(4)学习查阅有关设计手册•规范及其他参考资料的技能。
变压器保护整定中的差动保护的整定与校验方法
变压器保护整定中的差动保护的整定与校验方法在变压器保护装置中,差动保护是一种常见且重要的保护方式。
为了确保差动保护能够发挥其应有的保护作用,需要对差动保护进行整定和校验。
本文将从整定和校验两个方面介绍变压器差动保护的相关方法。
一、差动保护的整定方法差动保护的整定是为了确保在变压器正常运行时不发生误动作,同时能够在发生故障时能够准确可靠地动作。
以下是差动保护整定的一般步骤:1. 确定保护区域:根据变压器的接线图和实际情况,确定差动保护所要覆盖的保护区域。
通常情况下,保护区域应包括变压器的高压侧和低压侧。
2. 确定整定电流:根据变压器的额定电流和负载情况,确定差动保护的整定电流。
整定电流一般设置为变压器额定电流的百分之几,具体数值根据实际情况而定。
3. 确定动作特性:根据差动保护的动作特性曲线,确定差动保护的整定参数。
常见的动作特性曲线有梯形曲线、平板曲线等,具体选择应考虑变压器的性能和运行要求。
4. 确定整定参数:根据变压器的特性、接线方式和运行要求,确定差动保护的整定参数。
整定参数包括时间定值、灵敏系数等,可以根据经验值或者故障模拟等方法确定。
二、差动保护的校验方法差动保护的校验是为了验证整定参数的准确性和保护装置的可靠性。
以下是差动保护校验的一般步骤:1. 检查接线:首先,检查差动保护装置的接线情况,确保连接正确可靠。
同时,还应检查变压器主绕组和各侧绕组之间的连接,确保变压器内部电路的连通性。
2. 模拟故障:通过模拟故障的方式进行校验,例如在变压器的高压侧或低压侧接入故障电阻、故障电容等。
模拟故障时,需要记录差动保护的动作时间和动作电流,与整定参数进行对比。
3. 调整整定参数:如果校验结果与整定参数存在较大偏差,需要进行整定参数的调整。
可以通过调整灵敏系数、时间定值等参数来准确匹配差动保护的整定与校验结果。
4. 验证保护可靠性:校验完成后,需要进行保护可靠性的验证。
可以通过变压器的正常运行和模拟故障实验等方式来验证差动保护的可靠性和准确性。
电力变压器继电保护设计(设计) 学位论文
电力变压器继电保护设计(设计) 学位论文无需修改。
正文电力变压器是电力系统中十分重要的供电元件。
为了保证供电的可靠性和系统正常运行,必须根据其容量的大小、电压的高低和重要程度设置相应的继电保护装置。
本设计结合电力变压器运行中的故障,分析了电力变压器纵联差动保护、瓦斯保护及过电流保护等继电保护装置的配置原则和设计方案。
电力变压器的纵联差动保护是一种常见的继电保护装置。
其基本原理是将变压器的高压侧和低压侧的电流进行比较,当两侧电流差值超过设定值时,继电器动作,切断变压器的电源,从而保护变压器。
在配置纵联差动保护时,应根据变压器的容量和结构特点确定保护区域和保护范围,同时还要考虑保护装置的灵敏度和可靠性。
瓦斯保护是针对油浸式变压器的一种继电保护装置。
其原理是通过检测变压器油中的瓦斯浓度,当瓦斯浓度超过设定值时,继电器动作,切断变压器的电源,从而避免变压器发生火灾或爆炸。
在配置瓦斯保护时,应根据变压器的容量和使用环境确定瓦斯浓度的警戒值和动作值,以保证保护装置的准确性和可靠性。
过电流保护是一种常见的继电保护装置,可以用于保护电力变压器和电力系统中其他设备。
其原理是通过检测电流的大小和时间,当电流超过设定值和时间时,继电器动作,切断电源,从而保护设备。
在配置过电流保护时,应根据设备的额定电流和使用环境确定保护装置的额定电流和动作时间,以保证保护装置的准确性和可靠性。
综上所述,电力变压器的继电保护装置是保障电力系统正常运行的重要组成部分,应根据变压器的特点和使用环境选择合适的保护装置,并合理配置,以保证电力系统的安全稳定运行。
1.概述本文将介绍电力变压器的基本概念、故障和不正常运行状态以及保护配置。
同时,本文还将详细介绍___电力变压器继电保护的设计。
1.1 变压器的基本概念变压器是电力系统中常见的一种电气设备,用于改变交流电的电压等级。
变压器的基本原理是利用电磁感应的原理,通过电磁感应作用将电压从一个电路传递到另一个电路中。
变压器保护差动保护毕业设计
变压器保护差动保护毕业设计一、选题背景及意义变压器作为电力系统中的重要设备之一,起着电压变换和功率传递的作用。
在变压器运行过程中,存在着各种故障风险,如内部绕组短路、外部短路等。
这些故障不仅会导致电力系统中断,还可能给设备带来损坏和安全隐患。
因此,保护变压器的安全运行至关重要。
差动保护是变压器常用的保护方式之一、它基于变压器的输入输出电流差值原理,通过比较绕组各相电流的差值来判断是否存在故障,并进行相应的保护措施。
差动保护可以实时监测变压器的工作状态,对变压器发生故障时及时做出响应,保护变压器及其周围设备的安全运行。
因此,本毕业设计旨在设计一种可靠、稳定的差动保护装置,提高变压器的保护性能,保证变压器的安全运行。
二、方案设计1.系统框架设计差动保护系统由测量单元、传输单元和计算单元组成。
其中,测量单元用于采集变压器各相电流信号,传输单元用于将采集到的信号传输给计算单元,计算单元负责对电流信号进行差动计算,并与预设的保护动作参数进行比较,判断是否进行保护动作。
2.信号采集与传输设计为了准确采集变压器各相电流信号,采用合适的传感器进行测量,并将测量结果转换成数字信号。
常见的电流传感器有电流互感器和霍尔效应传感器等。
选择合适的传感器对变压器的电流进行测量,并通过模数转换器将模拟信号转换为数字信号。
为了实现信号的传输,使用合适的传输介质进行数据传输。
目前常用的传输介质有RS485总线、以太网等。
选择合适的传输介质,并设计相应的通信协议,将采集到的电流数据传输给计算单元。
3.差动计算与保护动作设计计算单元通过对接收到的电流数据进行差动计算,得到各相电流的差值。
根据预设的保护动作参数,与计算结果进行比较判断是否发生故障,并进行相应的保护动作。
常见的差动保护动作方式有差流动作和差动定时动作等。
根据具体情况选择合适的保护动作方式,并设计相应的保护动作逻辑。
4.界面设计为了方便操作和监测差动保护系统的状态,设计相应的人机界面。
50MW发电机变压器组继电保护毕业设计
沈阳工程学院毕业设计(论文)摘要由于大型电厂的母线、发电机和变压器的结构比较复杂,在运行过程中都可能会发生各种各样的故障和异常运行状态,为了确保在保护范围内发生故障,都能有选择性的快速切除故障,需要配置多种继电保护装置,必要时进行多重化配置,从而将电厂中重要设备的危害和损失降到最小,对电力系统的影响最小。
发电厂和变电所母线是电力系统中的中的一个重要组成部件,发电机的安全运行对保证电力系统的正常工作和电能质量起着决定性的作用;而变压器是电力系统十分重要的供电元件再者,发电机、变压器本身就是十分贵重的电气元件,所以,继电保护装置对大型电厂的正常运行起着至关重要的作用。
本设计共包括五章,分别对电力系统、发电机、变压器的继电保护进行详细介绍,并给出相关的整定计算,画出主接线图。
本文主要通过分析原始资料中主要设备的参数,首先,需要对电力系统保护原理进行全面系统的复习、查阅相关资料,加深理解;其次,结合相关参数和各种继电保护原理,确定适用于大型电厂的保护方案,最后,分别对发电机和变压器进行整定计算和配置,并且画出系统一次设计图及其配置图和一般原理图。
关键词:电厂、继电保护、发电机、变压器。
50MW发电机变压器组继电保护设计AbstractBecause of large power plants bus bar, generators and transformers structure is more complex, in operation process of all may be all kinds of faults and abnormal operating condition, in order to ensure that the protection range in failure, all can have selective swift removal, need configuration fault diversified relay protection device, necessary in the multiple configuration, so as to will be important in power plant equipment to minimize harm and loss of power system, affect the minimum.Power plant and substation bus in power systems is one of the important components of the generator, the safe operation of the power system to guarantee the normal work and power quality plays a decisive role; And the transformer is power system is of great power supply components again, generator, transformer itself is very expensive electrical components, so, relay protection device of large power plants to the normal operation of the play a crucial role.This design including five chapters, respectively for power system, generator, transformer of relay protection, and gives a detailed introduction of related setting calculation, draw the Lord the wiring diagram.This paper mainly through the analysis of original data of the parameters of the main equipment, first of all, need to power system protection principle of full system review and access relevant information, deepen understanding; Secondly, in conjunction with the relevant parameters and all kinds of relay protection principle, sure used in large power plant protection scheme, then respectively, the generator and transformer in setting calculation and configuration, and draw the system design and its a configuration diagram and the general principle diagram.Key word: power plant, relay protection, generator, transformer.沈阳工程学院毕业设计(论文)目录中文摘要 (I)Abstract (II)引言 (1)第1章电力系统继电保护简论 (2)1.1 继电保护的作用 (2)1.2 继电保护的基本要求、原理、构成与分类 (2)1.2.1 基本要求 (2)1.2.2 基本原理 (3)1.2.3 构成 (4)1.2.4 分类 (4)第2章主变压器保护设计 (6)2.1 变压器保护重要性 (6)2.2 变压器的故障类型和不正常运行状态 (6)2.3 变压器保护配置原则 (6)2.4 变压器纵联差动保护 (7)2.4.1 构成变压器纵差动保护的基本原则 (7)2.4.2 变压器差动保护的不平衡电流 (8)2.5 变压器后备保护 (9)2.5.1 低电压启动的过电流保护 (9)2.5.2 变压器零序电流保护 (10)2.5.3 过负荷保护 (11)第3章发电机保护设计 (12)3.1 发电机故障及不正常运行状态 (12)3.1.1 发电机故障类型 (12)3.1.2 不正常运行状态 (12)3.2 发电机保护的配置原则 (13)3.3 发电机纵差保护 (13)3.3.1 工作原理 (13)第4章短路计算 (14)4.1 发电机出口短路计算 (14)4.2 后备保护短路计算 (15)50MW发电机变压器组继电保护设计第5章整定计算 (19)5.1 发电机纵差动保护整定 (19)5.2 发电机横联差动保护整定 (20)5.3 发电机定子绕组过负荷保护整定 (20)5.4 发电机复合电压启动的过电流保护整定 (20)结论 (23)致谢 (24)参考文献 (25)附录 (26)A1.1 全厂电气主接线图A1.2 50MW发电机保护展开图A1.3 50MW发电机保护交流展开图A1.4 50MW发电机保护直流展开图沈阳工程学院毕业设计(论文)引言本次毕业设计的主要内容是针对电力系统中可能出现的各种不正常状态和故障状态,对大型电厂的发电机、主变压器的保护配置及继电保护设计,参照《电力系统继电保护》及《电力工程电气设备手册》,并依据继电保护配置原理,对所选择的保护进行整定从而来确定方案中的保护是否适用来编写的。
变压器保护设计范文
变压器保护设计范文一、保护原理变压器的保护原理主要有过电流保护、差动保护和绝缘保护等。
1.过电流保护:变压器输电过程中,会出现短路和过负荷等故障,导致变压器温升过高,从而损坏变压器。
过电流保护通过检测变压器的输入电流和输出电流,当电流超过额定值时,保护装置将切断电源。
过电流保护段也分为瞬时过电流保护和过电流时间保护两种。
2.差动保护:差动保护主要用于检测变压器的绕组是否有短路故障。
差动保护原理是通过检测变压器的输入和输出电流的差值,当差值超过设定的阈值时,保护装置将切断电源。
3.绝缘保护:绝缘保护是为了防止变压器的绝缘击穿故障。
绝缘保护主要通过检测变压器的绝缘电阻,当绝缘电阻低于设定的阈值时,保护装置将切断电源。
二、保护装置1.保护继电器:保护继电器是变压器保护系统中最关键的部分。
保护继电器负责接收和处理变压器的输入和输出信号,并根据预设的保护逻辑进行判断,当检测到故障时,保护继电器将输出信号给保护开关,切断电源。
2.保护开关:保护开关主要负责切断电源。
保护开关可通过机械方式或电磁方式实现切断电源的功能。
三、保护策略1.主保护:主保护是指主要保护装置,包括差动保护和过电流保护。
差动保护是最常用的主保护方式,它能有效检测变压器的内部短路故障。
过电流保护则能有效检测变压器的过负荷故障。
2.备用保护:备用保护是指备用的保护装置,主要用于当主保护故障或失效时起到备份的作用。
备用保护可以是另一组差动保护或过电流保护,也可以是绝缘保护等。
保护策略还应考虑到变压器的特殊情况和运行环境,比如变压器的类型、容量和工作环境等,以提高变压器保护的准确性和可靠性。
四、总结变压器保护设计是确保变压器运行安全和可靠的关键环节。
通过合理的保护原理、保护装置和保护策略,可以有效地保护变压器免受故障和事故的影响。
在实际的工程实施中,还需要根据具体的项目情况,采取相应的方案和措施,确保变压器保护设计的成功实施。
变压器的纵联差动保护
变压器的纵联差动保护众所周知,纵差保护是一切电气主设备的主保护,它灵敏度高、选择性好,在变压器保护上运用较为成功。
它可以用来反映变压器绕组的相间短路故障、中性点接地侧绕组的接地故障以及引出线的相间短路故障、中性点接地侧引出线的接地故障。
但是变压器纵差保护一直存在励磁涌流难以鉴定的问题,虽然已经有几种较为有效的闭锁方案,又因为超高压输电线路长度的增加、静止无功补偿容量的增大以及变压器硅钢片工艺的改进、磁化特性的改善等因素,变压器纵差保护的固有原理性矛盾更加突出。
纵差保护还受到互感器采集不平衡电流的影响,在本章将研究纵差保护的基本原理、不平衡电流的产生及克服方案。
1变压器纵差保护基本原理按照反应电流和电压量变化构成的保护装置,测量元件限于装设在被保护元件的一侧,无法区别被保护范围末端和相邻范围始端的故障。
为了保证动作的选择性,在整定动作参数时必须与相邻元件的保护相配合,一般采用缩短保护区(降低灵敏度)或延长动作时限(降低速动性)的方法来获得选择性。
但从保证系统稳定运行和减轻故障变压器的损失及避免扩大事故的要求来看,希望能快速切除被保护范围内任意地点发生的故障。
如果保护装置的测量元件能同时反应被保护设备两端的电量时,就能正确判断被保护范围区内和区外的故障。
被保护元件发生内部和外部故障时,其各侧功率方向或电流相位是有差别的,因而根据比较被保护元件各端电流大小和相位差别的方法而构成的纵联差动保护,获得了广泛的应用。
采用差动继电器作保护的测量元件,用来比较被保护元件各端电流的大小和相位之差,从而判断保护区内是否发生短路。
由于纵联差动保护只在保护区内短路时才动作,不存在与系统中相邻元件保护的选择性配合问题,因而可以快速切除整个保护区内任何一点的短路,这是它的可贵优点。
但是,为了构成纵联差动保护装置,必须在被保护元件各端装设电流互感器,并将它们的二次线圈用辅助导线连接起来,接差动继电器。
由于受助导线条件的限制,纵向连接的差动保护仅限于用在短线路上,对于发电机、变压器及母线等,则可广泛采用纵联差动保护实现主保护。
变压器零序差动保护
第四节 变压器零序差动保护1.概述通常的差动保护用在N Y ,d 接线的三项变压器,当N Y 侧单相接地短路时灵敏度不高,故提出零序差动保护方案。
单相式超高压大型变压器绕组的短路类型主要是绕组对铁芯(即地)地绝缘损坏,即单相接地短路,相间短路(指箱内故障)可能性极小,因此认真对待变压器绕组地单相短路故障保护,十分必要。
2.原理2.1 普通变压器的零序差动保护先看图1(a)所示N Y ,d 变压器,N Y 侧电源断开,该侧发生金属性单相接地短路,短路点距中性点的长度占全绕组总长的%α,电流Y I 和∆I 如图所示,变压器的电抗为0.10,∆侧接于无穷大电源。
变压器差动保护的电流互感器二次接线为常规方式(即变压器Y 接,互感器二次侧∆接;变压器∆接,互感器二次侧Y 接)。
输入变压器差动保护的电流是∆I ,当短路点靠近中性点时,即0→α,电流0→∆I ,注意到∆I 中只有正、负序分量,不包含零序分量,所以∆I 总是小于Y I ,使通常的差动保护灵敏度不高且有动作死区。
再看图1(b)的两侧电源N Y ,d 变压器,单相接地短路将Y 绕组分为两部分(1W 和2W ),各自流过电流1Y I 和2Y I ,如果有1Y I 1W >2Y I 2W ,则∆I 的正向将如图所示,这时1Y I 和∆I 将呈现穿越特性,通常的差动保护灵敏度低,或者根本不动作。
对于上述单相短路灵敏度低的问题,如果在N Y 侧三相电流互感器二次侧接成零序滤过器方式,再与中性点互感器二次组成差动接线,就构成了变压器的接地零序差动保护。
这种零序差动保护,无论图1(a)或(b),都能反应全部短路电流Y I (=1Y I 和2Y I ),灵敏度大大提高。
2.2 自耦变压器的零序差动保护按照相间短路差动保护互感器二次侧接线惯例,自耦变压器高中压侧电流互感器二次必为∆接线,差动继电器中不流过零序电流,所以这种差动保护对接地短路的灵敏度低,而对中高压侧中性点均直接接地的自耦变压器,单相接地是其主要故障形式之一,加装零序差动保护将提高自耦变压器内部接地短路的灵敏度。
电力变压器保护毕业设计论文
===================================== 电力变压器保护毕业设计=====================================摘要本文主要通过分析原始资料中主要设备的参数,首先,需要对电力系统继电保护原理进行全面系统的复习、查阅相关资料,加深理解;其次,结合相关参数和各种继电保护原理,确定适用于变压器的保护方案,最后,分别对变压器的进行各种保护整定和配置计算,并且根据系统一次设计图给出部分二次设计及其配置图和一般原理图。
本次设计中主要采用的保护有瓦斯保护、变压器纵联差动保护、低电压起动的过电流保护、过负荷保护、温度保护。
继电保护是电力系统设计有关事故时减小停电范围、限制事故对设备损害的这样一个领域。
电力系统继电保护的设计与配置是否合理,直接影响电力系统的安全运行,故选择保护方式时,满足继电保护的基本要求。
选择保护方式和正确的整定计算,以保证电力系统的安全运行。
关键词继电保护,变压器保护,灵敏度校验,短路电流计算,整定计算AbstractThis paper mainly through the analysis of the original material of main equipment of parameters, first of all, need for transformer protection principle of comprehensive system review, refer to the relevant material, deepen understanding; Secondly, in conjunction with the relevant parameters and all kinds of relay protection principle, determine suitable for transformer protection scheme, then respectively, the transformer protection setting and configuration of calculated according to the system, and gives some secondary design drawings once its configuration diagram and general principle diagram. This design mainly adopts a transformer protection of gas protection, longitudinal league differential protection, over current protection, overload protection, temperature protection.The Relay protection is electrical system design relevant accident reduce outage scope, limit the damage of equipment accidents such a field. Power system protection design and configuration whether reasonable, directly affecting the safe operation of the power system, so choose protection way, meet the basic requirements of the relay protection. Choose the right protection mode and setting calculation, to ensure the safe operation of the power system.Key Words relay protection,transformer protection,sensitivity check,short-circuit current calculation,setting calculation目录摘要 (1)Abstract (2)引言 (3)1.1 课题背景 (3)1.2 课题研究的目的和意义 (3)2系统设计方案研究 (4)2.1变电所主变压器基本情况介绍 (4)2.2系统运行方式分析 (5)2.2.1系统运行方式分析原则 (5)2.2.2煤矿变电所各种电气运行方式的分析 (5)2.3 变压器各种保护及其装设条件 (6)2.3.1瓦斯保护 (6)2.3.2 纵差动保护 (6)2.3.3过电流保护 (8)2.3.4过负荷保护 (8)2.3.5温度保护 (9)2.2继电保护规程中对相关保护的配置要求 (9)2.4针对本设计的规程要求 (10)2.4.1 同时性故障的配置方案 (10)2.4.2 对经电流互感器接入保护的要求 (10)2.4.3 关于远后备保护的规定 (10)2.4.4 系统振荡对保护的要求 (11)2.4.5 其他相关规定 (11)3短路电流的计算 (12)3.1标幺值归算 (12)3.2短路电流的计算 (13)4保护的整定计算及灵敏度检验 (24)4.1变压器主保护的整定计算及灵敏度检验 (24)4.1.1纵连差动保护的整定计算 (24)4.1.2差动保护的灵敏度校验 (28)4.1.3变压器瓦斯保护的整定 (29)4.2相间后备保护的整定及校验 (30)4.2.1过电流保护动作电流的整定 (30)4.2.2过电流保护灵敏度校验 (30)4.2.3过负荷保护 (32)4.2.4温度保护 (33)4.3变压器各个保护动作时限配合 (33)5设备的选型设计 (34)5.1电流互感器的选择 (34)5.2继电器的选择及参数介绍 (36)5.2.1各种继电器原理 (36)5.2.2 所选继电器参数介绍 (37)6总结 (41)致谢 (42)参考文献 (43)附录1 (44)附录2 (46)附录3 (48)附录4 (48)引言1.1 课题背景电力变压器是电力系统中的重要的电气设备,在发电、输电、配电环节中起着提高电压以便于远距离输送电能以及降低电压给负荷供电等关键作用。
变压器保护差动保护毕业设计综述
目录第一章:变压器保护概述 (2)1.1国内外变压器差动保护研究发展现状 (2)1.2 课题内容及意义 (2)1.3 设计电站的原始资料(地区电网系统接线图) (3)第二章:变压器的继电保护介绍 (4)2.1 变压器原理介绍 (4)2.2 电力变压器的故障类型、异常工作情况 (5)2.2.1 变压器的故障类型 (5)2.2.2 变压器的异常工作情况 (5)2.3 变压器继电保护方式 (6)2.4 变压器保护的基本要求 (6)第三章变压器差动保护 (7)3.1 国内外差动保护综述 (7)3.2 变压器的差动保护 (8)3.2.1 变压器差动保护的基本原理 (8)3.2.2.变压器差动回路不平衡电流的分类 (9)3.3 各种变压器主保护的讨论 (11)第四章短路电流的计算 (15)4.1 短路计算基本说明及步骤 (15)4.1.1 短路计算程序运行前的准备工作 (15)4.1.2 短路计算程序运行步骤 (16)4.2 短路计算结果 (17)第五章主变差动保护整定计算过程及计算结果表 (18)5.1 主变差动保护基本原理说明 (18)5.2 主变差动保护整定计算过程 (19)5.2.1 计算各侧一次额定电流、差动保护TA变比、二次额定电流及平衡系数. 195.3 整定计算结果一览表 (21)第六章集成电路型过电流继电器电子电路设计 (22)6.1 构成方框图及其说明 (22)6.1.1 构成方框图 (22)6.2 典型模块电路及其仿真 (22)6.2.1 全波整流电路及其仿真 (22)6.2.2 滤波电路及其仿真 (24)6.2.3 延时电路及其仿真 (27)6.2.4 展宽电路及其仿真 (28)6.3 整体过电流继电器电子电路及其仿真 (30)6.3.1 过电流继电器整体电子电路 (30)6.3.2 整体电子电路仿真步骤及仿真结果 (30)第七章总结 (31)参考文献 (32)变压器主保护——差动保护设计第一章:变压器保护概述随着电力系统的出现,继电保护技术就相伴而生。
微机型电力变压器差动保护装置设计
微机型电力变压器差动保护装置设计微机型电力变压器差动保护装置是电力变压器运行中必不可少的一种保护装置。
它主要用于检测和保护变压器中的低压侧绕组,以防止由于线路短路或变压器故障引起的过电流、过载、短路等故障。
在传统电气系统中,通常采用继电器保护方案。
然而,随着微机技术的发展,微机型电力变压器差动保护装置成为了一种更为先进和可靠的保护手段。
1.传感器:传感器是差动保护系统的核心部件之一,用于感知电流和电压信号,并将其转化为电信号进行处理。
常用的传感器有电流互感器和电压互感器。
电流互感器通过测量变压器绕组的电流大小和相位差,来判断变压器是否存在故障。
电压互感器则用于测量主变压器的输入和输出电压,以提供足够的电压供给其他部件。
2.信号处理:信号处理是微机型电力变压器差动保护装置的核心任务之一、它包括信号采集、滤波、放大、波形识别等过程。
信号采集是指将传感器采集到的模拟电信号转化为数字信号,以便计算机进行处理。
滤波则是对采集到的信号进行滤波处理,去除噪声和干扰,以提高差动保护装置的灵敏度。
波形识别是指对采集到的波形进行分析和识别,以判断电流是否越过预设的阈值,从而触发保护操作。
3.差动判据:差动判据是微机型电力变压器差动保护装置的最核心部分之一、它通过对变压器输入和输出电流进行差分运算,判断变压器是否存在故障。
常用的差动判据有整流方程和压降方程等。
整流方程是根据电流的输入和输出关系,进行波形识别和计算,判断电流的差分值是否超过预设的阈值。
压降方程则是通过计算变压器绕组的电压降值,判断电流是否存在异常。
4.保护装置操作:当差动判据检测到变压器故障时,微机型电力变压器差动保护装置需要及时采取保护措施,以避免进一步损害变压器。
常见的保护操作包括断开故障电路、切断电源供给、发出警报信号等。
这些操作需要通过接触器、继电器、断路器等电气元件来实现,以确保装置的可靠性和稳定性。
总之,微机型电力变压器差动保护装置设计是一个涉及电气、电子、通信等多学科知识的复杂任务。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
变压器保护差动保护毕业设计Prepared on 22 November 2020目录变压器主保护——差动保护设计第一章:变压器保护概述随着电力系统的出现,继电保护技术就相伴而生。
与当代新兴科学技术相比,电力系统继电保护是相当古老了,然而电力系统继电保护作为一门综合性科学又总是充满青春活力,处于蓬勃发展中。
之所以如此,是因为它特别注重理论与实践并重,与基础理论、新理论、新技术的发展紧密联系在一起,同时也与电力系统的运行和发展息息相关。
电力系统自身的发展是促进继电保护发展的内因,是继电保护发展的源泉和动力,而相关新理论、新技术、新材料的发展是促进继电保护发展的外因,是电力系统继电保护发展的客观条件和技术基础。
国内外变压器差动保护研究发展现状随着超高压、远距离输电在电力系统中的应用越来越广泛,大容量变压器的应用日益增多,对变压器保护的可靠性、快速性提出了更高的要求。
电力变压器在空载合闸投入电网或外部故障切除后电压恢复时会产生数值很大的励磁涌流,同时波形严重畸变,容易造成差动保护误动作,直接影响到变压器保护的可靠性。
差动保护一直是电力变压器的主保护,其理论根据是基尔霍夫电流定律,对于纯电路设备,差动保护无懈可击。
但是对于变压器而言,由于内部磁路的联系,本质上不再满足基尔霍夫电流定律,变压器励磁电流成了差动保护不平衡电流的一种来源。
当前变压器差动保护的主要矛盾仍然集中在励磁涌流和内部故障电流的鉴别上。
近十多年来,国内外许多学者致力于变压器继电保护的研究,提出了不少判别励磁涌流的新原理和新方法。
课题内容及意义根据以上的分析及对目前应解决问题的研究,得到本课题所作研究的目的:运用小波原理,探求新的励磁涌流与内部故障判别方法。
其意义在于通过研究新判据,尝试以小波分析方案完善目前的励磁涌流判据,提高差动保护的可靠性。
设计电站的原始资料(地区电网系统接线图)第二章:变压器的继电保护介绍变压器原理介绍变压器主要是用来输变电的,变压器能量传递是通过电磁感应而实现的,所以分析变压器电磁关系要根据有关电和磁的规律。
每台变压器必须有电路和磁路,而电路和磁路又是电场和磁场的简化,但是在遇到一些细致的问题时,我们还是必须要用场的方法来解决。
一般变压器的电路是由绕组构成,而磁路是指定的磁通所通过的部分。
(1)电路分析:对于普通电力变压器,就是指那些单相、三相、双绕组和三绕组电力变压器,由于他们绕组的联结方式不同,所以绕组电流,线电流,相电流的计算公式都是不一样的。
但都可以用表达式φU KP I a =来表示。
其中K 是比率系数,P 是额定容量,φU 是额定电压。
而绕组的匝数取决于铁心心柱截面的大小。
因为当铁心采用某一牌号硅钢片以后,磁密B 基本上是一个变化范围很小的量;而且在某一相电压作用下,绕组每匝电势e 与该绕组匝数W 的乘积也是一个常量,所以铁心柱截面A 大时,绕组每匝电势e 也大,则该绕组匝数减小。
既然绕组的匝数完全取决于每匝电势e ,当f=50Hz 时,5110450⨯=BA e ,根据每匝电势和外加电压我们就可以计算出各绕组的匝数。
当发生匝间短路时,绕组匝数ω将变小,电势E 也将变小,而电流分量将增大,引起变压器差动保护动作。
(2)磁路分析铁心是变压器的磁路,变压器是由电能输入侧,即一次绕组侧励磁的。
在一次与二次绕组间建立起交变磁通的电流,称为励磁电流或磁化电流。
具有磁性铁心的变压器,交变磁通大部分在铁心中流通,该磁通叫做主磁通。
双绕组变压器负载时的磁式方程为MF F F =+21 (2-1) 或 32211W I W I W I M =+ (2-2)将上式改写为:HT M M I I W W I I I 11221 +=⎪⎪⎭⎫ ⎝⎛-= (2-3) 式中,HT I 1 —次电流的负载分量。
由上式可以看出,一次电流乃是励磁电流mI 与一次电流负载分量I AHT 的矢量和,HT I 1等于运用一二次匝数比折算的二次电流,并取负号,即21221I W W I I HT -=-= (2-4)于是,变压器的磁场可以看作两个部分,一是由励磁磁势1W I F M M =建立;二是由其和等于零的二次电流和一次电流负载分量的磁势01122=+W I W I HT 所建立的。
这个由合成磁势所建立的磁场,按照全电流定律,不可能包含与变压器的两个绕组都铰链的磁通,仅可能包含与一个绕组逐次或完全铰链的磁通。
这个磁场,就叫做变压器的漏磁场。
如果变压器在空载和负载时,一次绕组端所施加的电压是相等的,则变压器的空载电流和负载时的励磁电流二者在大小、相位与波形上相差很小。
由公式 1111Z I E U +-= (2-5) 式中 1U —外加电压V;1E —由主磁通产生的电势V;21Z I —次绕组的阻抗压降V 。
电力变压器的故障类型、异常工作情况电力变压器是电力系统普遍使用的重要电气设备。
它的安全运行直接关系到电力系统供电和稳定运行,特别是大容量电力变压器一旦因故障而损坏,造成的损失就更大。
因此必须针对电力变压器的故障和异常工作情况,根据其容量和重要程度,装设动作可靠、性能良好的继电保护装置。
变压器的故障类型变压器故障包括变压器油箱内部故障和油箱外部故障。
变压器油箱内部故障包括绕组的相间短路、匝间短路和中性点接地系统侧的接地短路。
这些故障由于短路电流产生的高温电弧不仅烧坏绕组绝缘和铁芯,而且将绝缘材料和变压器油分解产生大量气体,使变压器油箱局部变形,甚至引起爆炸。
变压器油箱外部故障主要是变压器绝缘套管和引出线上发生的相间短路和接地短路。
变压器的异常工作情况变压器的异常工作情况由外部短路引起的过电流、过负荷;油箱漏油造成的油面降低或冷却系统故障引起的油温升高;外部接地短路引起的中性点过电压;过电压或系统频率降低引起的过励磁等。
变压器继电保护方式变压器保护的任务就是反应上述故障和异常工作情况,通过断路器切除故障变压器或发出信号采取措施消除异常情况,并能作为相邻元件(如母线、线路)的后备保护。
根据有关规定,变压器应该装设以下继电保护装置。
(1)反应变压器油箱内部各种短路故障和油面降低的瓦斯保护。
对容量在及以上油浸式变压器应该装设瓦斯保护。
(2)反应变压器绕组或引出线相间短路、中性点直接接地系统侧绕组或引出线的单相接地以及绕组匝间短路的纵差动保护。
对及以上厂用工作变压器和并列运行的变压器,10MVA及以上厂用备用变压器和单独运行的变压器以及2MVA及以上用电流速断保护灵敏系数不能满足要求的变压器,应装设纵差保护。
对高压侧电压为330kV以上的变压器,可以装设双重差动保护。
(3)反应变压器外部相间短路并作为瓦斯保护和纵差动保护后备的过电流保护。
当过电流保护灵敏系数不满足要求时,可采用低电压和复合电压起动的过电流保护、复序电流保护、低阻抗保护等。
(4)反应中性点直接接地系统中变压器外部接地短路的零序电流保护。
该保护同时作为变压器内部接地的后备保护。
对于中性点可接地或不接地运行地变压器需增设零序过电压保护。
(5)反应变压器对称过负荷地过负荷保护。
(6)反应高压测电压为500KV的变压器由于工作磁通量密度过高引起过励磁的过励磁保护。
变压器保护的基本要求对变压器保护的基本要求有三个方面:(1)在变压器发生故障时应将它与所有的电源断开;(2)在母线或其它变压器相连的元件发生故障,而故障元件由于某种原因(保护拒动或断路器失灵等)其本身短路器未能断开情况下,应使变压器与故障部分分开;(3)当变压器过负荷、油面降低、油温过高时,应发出报警信号;对于变压器本身和各侧引线、套管的故障,为了限制故障扩大,通常采用电流速断、差动及重气体保护,快速将变压器的电源切断。
第三章变压器差动保护国内外差动保护综述迄今为止,差动保护己经广泛的应用于变压器保护当中,并且微机型保护已其巨大的优越性被广大用户所认可,所以微机变压器差动保护迎来一个快速发展的春天。
根据有关文献本文大致将差动保护目前的情况叙述如下。
目前,各个继电器生产厂家都将二次谐波制动原理作为主要的涌流闭锁方案。
其次是间断角原理以及近来兴起的模糊识别原理。
特别是当电力部规程要求220KV以上电压等级的变压器保护都必须配备不同原理的差动保护之后,间断角原理和模糊识别原理发展较为迅速,并且在实践中得到较多的运用和改善。
总之,这三种原理的差动保护己经可以称它们为主流,不管是国内还是国外的设备都可以提供这三种原理的保护。
这三种原理从本质上来看是相同的,都是基于波形识别的原理。
随着计算机水平的发展,CPU等主要芯片运算速度和精度的提高,必将会使得这三种原理的保护日趋完善和可靠。
但是这三种原理都有其固有的瑕疵。
因为它们都是基于对励磁涌流的一种基本认识:含有祸次谐波、存在波形间断、波形偏向时间的上半轴等等。
而对于励磁涌流的这种认识虽然得到目前的公认,但精确的量化却很难做到,所以具体到保护的判据,则存在某种经验的数据,所以也带来误动的可能。
同时,以上三种算法非常依赖于计算的精度,所以对计算的采样要求较高,特别是对于间断角原理。
同时这种依赖于波形识别(特别是影响波形的不确定因素较多)的原理也存在灵敏度不满足要求的问题,例如对于匝间短路。
计算机技术以及数学学科的发展为新的保护原理的具体应用和实现打下了坚实的物质基础。
归纳起来主要有以下几种:(1)变压器特殊运行状态及内部短路计算和数学仿真研究(2)具有虚拟三次谐波励磁涌流判别技术(3)基于回路方程算法的差动保护(4)基于电感倒数等效电路的的差动保护(5)基于励磁电抗(电感)数值大小的空载合闸涌流判据(6)小波变换在差动保护中的应用(7)基于参数辨识的差动保护(8)基于磁制动方案(9)等值电路参数鉴别法目前,这几种保护的方法尚在理论研究阶段,它们的突破将为变压器的保护开创新的天地。
差动保护目前主要有如下几种方式:(1)比率制动式差动保护(2)标积制动式差动保护(3)其它类型的差动保护:比如零序差动、分侧差动保护、不完全差动保护、差动速断保护等。
(4)基于比率制动式差动保护原理对于高电阻故障(即低故障电流)不灵敏,美国Mcclee:等提出新的△差动继电器方法,即将制动电流及差动电流中的故障前电流除出,这种保护在高阻故障时灵敏度较高。
变压器的差动保护变压器差动保护的基本原理对于构成理想变压器模型,差动保护在原理上只能反映被保护设备内部短路电流∑K I ,而不管外部有多严重。
(a) 两相变压器原理图 (b )三相变压器原理图 图3-1 变压器差动保护的原理接线由于变压器高压测和低压测的额定电流不同,因此,为了保证纵差动保护的正确工作,就必须适当选择两侧电流互感器的变化,使得在正常运行和外部故障时,两个二次电流相等。
例如图3-1(a)中,应使211122l l n I n I I I ''='=''=' 或 B l l n I I n n ='''=1112 (3-1) 式中 2l n —高压测电流互感器的变比; 1l n —低压测电流互感器的变比;B n —变压器的变比(即高,低压测额定电压之比)。