Functional Specification for AHU11
Table of contents
1.Base (3)
2.Introduction (3)
3.Interfaces to other Systems (3)
3.1.Time switching functions (3)
3.2.Dependencies (3)
3.3.Energy management (4)
3.4.Emergency power assignments (4)
3.5.Topology of automations, operating system (4)
er access (4)
4.Control functions (5)
4.1.Safety functions (5)
4.1.1.Temperature (5)
4.1.2.Pressure (5)
4.1.3.Humidity (6)
4.1.4.Fire (6)
4.1.5.Gas (7)
4.1.6.Special function (7)
4.2.Standard functions (8)
4.2.1.Start-up (8)
4.2.2.Shut-down (8)
4.2.3.Manual operation of Electric panel (9)
The detailed function specification will be described in FS PLC and electric control system.9
4.2.4.Special functions (9)
5.Regulating (9)
5.1.Control loops (9)
5.1.1.Temperature (9)
5.1.2.Pressure (10)
5.1.3.Humidity (10)
5.1.4.Special functions (10)
Revision History
1. Base
This Functional Description is based upon the User Requirement Specification (BJMC_MRS_HVAC_AHU11/12_URS_1.0) for HVAC Systems and P&ID drawing (BJMC_02_01_AHU11_PID ) i n it current version and describes all automation functions belonging to the PLC for this installation. Furthermore the OQ functional tests of the installation will be based upon this document.
2. Introduction
This description defines the required measurement, control and regulating functions of the Air Handling Unit, AHU11.
3. Interfaces to other Systems
3.1. Time switching functions
3.2. Dependencies
3.3. Energy management
3.4. Emergency power assignments
3.5. Topology of automations, operating system
3.6. User access
Every login, logout and all changes are logged in a log file; all dedicated people are mentioned in the authorization list. All access will be automatically reported, except the “everybody” access for information without action (resetting, parameter and software changes). The following levels of user access to the system will be provided:
4. Control functions
4.1. Safety functions
4.1.1. Temperature
4.1.2. Pressure
4.1.2.1. Supply duct pressure
4.1.2.2. Differential pressure of pre-filter G4
4.1.2.3. Differential pressure of fine-filter F7
4.1.2.4. Differential pressure of final-filter H13
4.1.3. Humidity
4.1.4. Fire
4.1.
5. Gas
4.1.6. Special function
4.1.6.1. Frequency converter for supply fan (with integrated overheating sensor)
4.1.6.2. Frequency converter for return fan (with integrated overheating sensor)
4.1.6.3. Power Failure
4.1.6.4. Building Shut Down
4.2. Standard functions
4.2.1. Start-up
4.2.1.1. Supply, return and exhaust fans
4.2.2. Shut-down
4.2.3. Manual operation of Electric panel
The detailed function specification will be described in FS PLC and electric control system.
4.2.4. Special functions
5. Regulating
5.1. Control loops
5.1.1. Temperature
5.1.1.1. Room temperature
5.1.1.2. Return temperature
5.1.1.3. Supply temperature
5.1.2. Pressure
5.1.2.1. Room pressure
5.1.3. Humidity
5.1.3.1. Room humidity
5.1.3.2. Supply humidity
5.1.4. Special functions
BJMC Document Number and Revision: Functional Description for AHU11 Page 11 of 11。