西门子消防报警系统标准技术方案
基于PLC消防报警系统设计
基于PLC的消防报警系统设计摘要火灾对国民经济和人民生命造成了巨大危害,但国外发达国家对火灾的预防及应对上我国和国外发达国家仍存在较大差距,因此,设计出一种可靠高效的消防报警控制系统是非常迫切的。
本设计完成了利用主要核心控制部件西门子SIMATIC S7-300型PLC对消防报警控制系统的设计。
首先,根据具体的控制对象选择合适的 S7-300 系列 CPU,这是控制系统的核心部件,在选择了一些火灾探测器的类型,探测器的选择好坏关系到报警及其它后续系列动作的关键。
其次,选择与S7-300相匹配的扩展模块,如数字 I/O 模块、模拟 I/O 模块、电源模块等。
最后,完成了控制系统的整体设计,达到了控制目标。
关键词:PLC;控制系统;消防报警PLC Based Fire Alarm System DesignABSTRACTFire on the national economy and people's lives caused great harm, but developed countries for fire prevention and the response to our country and abroad, there is still a wide gap between the developed countries, therefore, to design a reliable and efficient fire alarm control system is very urgent the.The main advantage of this design is completed the core control unit Siemens SIMATIC S7-300 PLC type of fire alarm control system design.Key first, depending on the control object to select the appropriate S7-300 series CPU, which is the core component of the control system, the choice of some type of fire detector, the detector alarm related to the choice of good or bad, and other follow-up action series . Second, select the S7-300 to match the expansion modules, such as digital I / O modules, analog I / O modules, power modules. Finally, to complete the overall design of the control system to achieve the control objectives.Key Words:Programable Logic Control;Control System;The Fire Fight Report To The Police目录第一章绪论 (1)1.1 课题研究的目的和意义 (1)1.2 课题背景 (1)1.3 国内外消防报警系统的现状及发展情况 (1)1.3.1火灾消防报警系统发展历程 (1)1.3.2消防火灾报警系统在国外的发展情况 (2)1.3.3消防火灾报警系统在国内的发展情况 (2)1.4 消防火灾报警系统的分类 (3)第二章系统的传感器的选型及其特性 (4)2.1 烟感器、液位传感器 (4)2.2 感烟器的选择 (4)2.3 液位传感器的选择 (5)第三章系统的硬件设计 (6)3.1 消防报警系统的要求、原理图设计 (6)3.1.1控制要求 (6)3.1.2消防报警系统工作原理图 (6)3.2 PLC相关模块的选择 (7)3.2.1 PLC的CPU模块的选择 (8)3.2.2 电源模块的选择 (8)3.2.3 变速频率调节器 (8)3.2.4 系统的硬件列表 (8)3.3 系统的电气回路图 (17)3.3.1 消防水泵单相交流电机电气回路图 (17)3.3.2 排烟风扇单相交流电机的电气回路图 (18)3.3.3 防火卷帘门三相交流电机的电气回路图 (19)3.3.4 储水水箱的PID控制的三相交流电机的电气回路图 (20)3.3.5 系统输入输出点: (21)第四章控制系统的软件设计 (25)4.1 系统的软件程序流程 (25)4.2 STEP7编程软件 (26)4.2.1 STEP7介绍 (26)4.2.4 组合硬件和软件 (27)4.3 STEP7硬件组态 (28)4.3.1 消防报警控制系统的PLC模块在STEP中的选择 (29)4.3.2 控制主程序 (29)4.4 用组态王监控软件组态监控消防控制系统 (35)4.4.1 组态王简介 (35)4.5 在组态王中建立监控消防报警控制系统 (35)4.5.1 新建一个工程项目 (35)4.5.2 选择与PLC S7-300 作为连接设备具体过程如下 (36)4.5.3 在数据词典中定义变量 (38)4.5.4 所要监控的具体的输入输出量为下图: (38)4.5.5 在编完程序后,在VIEW中演示的结果为 (39)参考文献 (40)致谢 (41)第一章绪论1.1 课题研究的目的和意义火灾早就成为危害我国的重大灾害之一。
火灾自动报警系统施工方案设计和技术措施方案
火灾自动报警系统施工方案设计和技术措施方案火灾自动报警系统是一种能够自动检测火灾并发出警报的安全设备,其施工方案设计和技术措施方案需要满足火灾报警系统的性能要求,并确保系统的可靠性和稳定性。
以下是火灾自动报警系统的施工方案设计和技术措施方案。
1.设计方案:(1)进一步了解建筑物的结构和布局,确定火灾自动报警系统的安装位置和报警设备的布置方案。
(2)根据建筑物的特点和使用要求,选择适当的火灾自动报警设备,包括火灾探测器、报警按钮、烟雾探测器、温度探测器等。
(3)确定火灾自动报警系统的布线方案,确保电缆的稳定性和可靠性。
(4)设计可靠的火灾自动报警系统供电方案,确保系统在停电时依然能够正常工作。
2.技术措施:(1)选择具有高灵敏度和抗干扰能力的火灾探测器,能够及时准确地检测到火灾的发生。
(2)使用可靠的数据库和报警记录系统,记录每次报警的时间、地点和相关信息,以便后续的火灾管理和事故调查。
(3)设置系统自动复位和手动复位功能,确保系统在发生误报警时能够及时恢复正常。
(4)设置火灾自动报警系统与消防控制中心的联动功能,能够实时传输火灾报警信息,便于消防部门的及时处置。
(5)对火灾自动报警设备进行定期的维护和检测,确保设备的可靠性和稳定性。
(6)设置适当的防护措施,防止系统被非法破坏或损坏。
3.其他注意事项:(1)施工过程中要按照相关的技术规范和标准进行操作,确保施工质量。
(2)施工人员需经过专业培训,具备相关的技术和安全意识。
(3)在系统安装和调试完成后,需要进行全面的测试,确保系统的性能和可靠性。
(4)施工方案设计和技术措施方案需根据具体的场所和需求进行调整和完善。
(5)及时更新系统的软件和硬件,以适应技术的发展和更新换代的需求。
在火灾自动报警系统的施工方案设计和技术措施方案中,设计方案要考虑建筑物的结构和布局,选择适当的报警设备,并制定相应的布线和供电方案。
技术措施包括选择高性能的探测器和数据库,并设置自动复位、联动、防护等功能。
西门子S11火灾报警系统
2. 应急操作系统出现故障,此时的火警在操作显示盘上以“非编址火警”(无具体的地址)方式显示。
这由系统中的应急操作电路来完成。
在应急操作方式下会减少报警信息。
—非编址报警在操作显示盘上(视和听)—警笛被驱动,在操作显示盘上可以消音。
—通过CPU板的触点来驱动远程火警。
—探测器上的指示灯闪亮(非编址探测器除外)。
C-总线上的应急操作电路(外部的)—包括“非编址火警”和“警笛消音”功能。
—在“E3X101”和“B3Q600”之间另加3根应急操作线。
—可以对应急操作线进行监视。
—如果不使用“监视”功能,通过“SWE11”设定为无效。
—两个独立的站之间,应急操作电路被设计成专用系统。
I-总线上的应急操作电路(内部的)—在各种I-总线功能卡中都含有“应急报警”和“警笛消音”功能。
—结合在I-总线扁平电缆内(因此有2个线头通过所有功能卡连到E3X101)。
2.1. 回路功能卡E3M060和E3M071中的应急操作—“应急操作”模式下的报警判定通过应急操作处理器和探测器中的“应急操作”来完成。
—应急火警在操作显示盘B3Q600上显示“非编址火警”,并且探测器上的指示灯闪亮。
—回路短路和回路处理器故障时没有“应急火警”显示。
—应急火警显示盘报警输出(插口ST10)只在应急火警模式下才有用。
2.2. 回路功能卡E3M080中的应急操作—应急操作的报警判定通过硬件比较器来完成。
—应急火警在操作显示盘B3Q600上显示“非编址火警”,探测器上的指示灯不亮。
—可选功能“短路报警”也是通过应急报警来实现。
—相应的应急火警显示盘报警输出(插口ST10)只在应急火警模式下才有用。
2.3. 回路功能卡E3M111中的应急操作—“应急操作”模式下的报警判定通过应急操作处理器来完成。
—应急火警在操作显示盘B3Q600上显示“非编址火警”,且探测器上的指示灯闪亮。
—回路短路和回路处理器故障时没有“应急火警”显示。
2.4. 灭火功能卡E3G080中的应急操作a) 控制器出现故障(E3X101或B3Q600)灭火功能卡E3G080的功能是独立的。
西门子FS18消防报警系统CRT编制方法分享(铁汇项目)05.13【1.0】(1)-1_141989
——沈阳铁西万象汇项目
目 录
Part1项目介绍 Part2编制背景 Part3CRT编制过程
Part4效果呈现
PART 1 项目介绍
总建筑面积:28.67万平方米 购物中心面积:14.35万平方米 写字楼面积: 3.83万平方米 车库车位:1500个
商铺数量:304个
编制背景
基于上述情况和问题,我们准备对万象
汇CRT功能完善进行立项请示。后续我
们在与西门子厂家的多次约谈中,一直 无法达成价格上的共识。经过了多轮约 谈后最终厂家给予的最低定价为28万元。
对此我们多次上会进行讨论,因为随着商业经营不 断扩大,场内业态布局不断发展与更新,只有消防 系统设备的定义与CRT不断的更新才能满足与现场 的一致性。因此如果我们无法自己掌握西门子系统 消防CRT的制作方法,未来此项工作的费用将是 “无底洞”。最终我们决定尝试独自解决此项问题, 攻克厂家的技术垄断和制约。
功接近。具体的过程有:
1、【定义修改】
首先我们通过测试及研究,掌握了FXS1800编程软 件更改信息及主机录入的方法,并通过1个月的时间,
将消防报警设备地址描述根据现场实际情况完成了更
新。
PART 3 CRT编制过程
2、【底图制作】
之后我们开始尝试FMS8000西门子CRT软件的编制方法,首先制作前期需进行底图的制作。要通过CAD绘制 好最新版建筑底图以防火分区为单位进行重新划分,以防火分区为最小单元进行CRT的图文制作。过程中我们 没有考虑到清晰度的问题,对于较大的防火分区截图太小,放大后无法清晰识别底图准确位置。再经过多次尝 试后,输出矢量图能够很好的解决上述问题,为了展现最佳效果,我们决定将已经完成的135个防火分区截图
西门子消防报警系统操作指导书
西门子消防报警系统操作
一、出现警报找着报警点
1.当出现火警时,消防主机会有报警声,同时在消防电脑上会出现如下图1所示,该示例是一手报报警.
图1
2.点击上图1所圈的图标,出现下图2的画面,单击图示的搜索查找按钮,系统自动寻找报警点
图2
3.如图3所示报警点,示例为地下室西车道
消防中心接处警操作程序
(一)当中央总控制台报警后
1、按消音键消音;
2、用对讲机或内线电话向报警指示区域的保安问清报警原因;
3、如是其他原因报警或误报,即通知保安按复位键复位;
4、总控制台复位;
5、如复位后再发生连续三次误报,则由消防中心派员查明原因并采取相应的措施。
(二)当确认发生火灾后:
什么物质在燃烧等情况;
2、立即将联动控制键打到自动状态,联动启动消防设施扑救火灾;
3、迅速向科文领导和物业处报告火情和失火部位,并向消防支队报警:(报警要讲清失火单位名称和地点、失火部位、火势大小、燃烧物性质等五项要素);
4、通知工程部迅速关闭新风机和空调系统,切断相应部位的电源;
5、检查设备联动情况,立即手动开启未联动的消防设备,组织人员疏散和扑救工作;
图3
二、联动操作与强启水泵
1.系统自动(系统联动)
消防系统联动启动按钮在中间消防主机的第二个联动控制盘上,如图4所示
图4
下图5是该控制盘
图5
(1)将该控制盘设置成手动状态:顺序按下ABA,允许手动灯亮,如图6.取消手动按B
图6
(2)如图5,在该控制盘手动状态下,按下消防系统联动(自动)按钮,整个系统即在联动状态.停止联动,请按下相应的停止按钮.
图9
西门子消防报警系统说明书2002-OP820感烟探测器
Fire Safety S1151系统产品说明北京西门子西伯乐斯电子有限公司1/2西伯乐斯生命财产的保障DO1152A/OP820 交互式光电感烟探测器特点●最新型式的光电感烟结构,对不同类型的火灾烟雾响应一致。
●内部具有微处理器,可独立进行高智能的信号处理。
●可靠性高:交互式智能火灾分析模式。
通过控制器可将特定应用的信号处理算法存储在探测器内,远距离调整探测器特定的响应行为,真正消除误报。
●稳定性高:抗灰尘附着,抗电磁干扰,抗温度影响,抗潮湿,抗腐蚀。
●每只探测器内有带特定标识码的识别模块(相当于身份证,起部件识别作用)。
与底座内的识别模块相配合,控制器能唯一确认该探测器及其地理位置。
●探测器有自检功能,并且控制器和探测器能互相交换信息并反复核实。
●采用自适应编址方式,探测器不设编址开关,避免人为造成差错。
●控制器电路(甚至微处理器)出现故障的情况下,也能应急报警。
●探测回路为环形两总线,且每个DO1152A/OP820探测器内部都有短路隔离开关。
当回路中任一点发生短路时,短路点两边的隔离开关自动将其隔开,确保系统正常运行;并能准确地判断短路点。
应用●用于建筑物内部空间的早期火灾探测,并通过控制器进行报警与消防联动。
应用于火灾产生烟(包括黑烟)的场合。
●探测器满足国家标准GB4715“点型感烟火灾探测器技术要求及试验方法”,探测器的应用设计遵照国家标准GB50116“火灾自动报警系统设计规范”。
●探测器安装在底座DB1151A/SO820上,通过底座与控制器FS1120相连。
设计●两总线环形回路(也可采用干型回路),标准采用双绞线,特殊情况可采用平行线、电缆、屏蔽电缆。
环形回路布线最长不超过2000米。
●每条回路最多128个探测器,其中可自由加入分支而无需分支模块。
●探测器可做防振、防潮、防盗、保护式安装(文件2001)。
●每个探测器的门灯输出端可外接门灯AI300、AI340(文件3002a)显示其报警状态,并且能自由编程使门灯显示其它探测器报警状态。
西门子S1131消防产品手册
组成,且备有足够种类的功能卡,可以进行多种功能扩展。 ● 自动诊断系统故障。故障状态下火警优先,甚至在主 CPU 故障
情况下也能报应急火警。 ● 控制器面板采用液晶中文显示、菜单操作方式,可显示并自动存
储运行的各种信息达 1000 条。
设备外观
4
S1131 产品手册
类型
S11 Auxiliary Extension Unit
功能描述 / 技术参数
S11 Auxiliary Extension Unit 消防辅助设备扩充机柜 (上柜式) (中国生产)
● 适用 AlgoRex 系统控制器辅助功能设备的安装。 ● 可安装于 BCH1950 双琴台或 Rack/WG 带玻璃门立柜。
AC220V,± 15%,50/60Hz DC24V,24AH 0 ~ 50℃ - 20 ~ 60℃ ≤ 95%(40 ± 2℃) IP30 RAL 7035 淡灰色 434 X 735 X 300(mm)
基本配置:
CI1142 控制面板终端
1个
E3M111 回路卡(4 回路)
*
1块
B2F020 电源(DC29V/6A)
带玻璃门立柜。 ● 其它特性同 FS1120 CI1142/A/Rack 控制器。
主电源 浮充备用电池 工作温度 贮存温度 工作湿度 保护等级 色标 尺寸
AC220V,± 15%,50/60Hz DC24V,38AH 0 ~ 50℃ - 20 ~ 60℃ ≤ 95%(40 ± 2℃) IP30 RAL 7035 淡灰色 434 X 1120 X 240 (mm)
部件号 99506067
DO1131A
西门子18消防报警系统(环路)
Page 15
FD181系列现场设备 – 输入输出模块 系列现场设备
FDCI181- 输入模块( 输入) FDCI181-2 输入模块(2输入)
Page 18
FC18系列控制器 – 壁挂型控制器 系列控制器
控制器(252点 504点 FC18 控制器(252点 / 504点)
“即插即用”式软件编址技术,自动读入回路 即插即用”式软件编址技术, 总线上现场设备并投入使用 两线制无极性自由布线结构回路总线, 两线制无极性自由布线结构回路总线,传输距 离环路可达2500 2500米 支路可达1500 1500米 离环路可达2500米,支路可达1500米 5.7英寸320×240背光式液晶显示屏 英寸320 背光式液晶显示屏, 5.7英寸320×240背光式液晶显示屏,可通过 控制器编写用户程序 全中文Windows风格菜单操作, Windows风格菜单操作 全中文Windows风格菜单操作,快捷右键菜单 控制器自带8路多线联动盘, 控制器自带8路多线联动盘,用于重要设备的 自动或手动操作 控制器带有2路可编程输入/输出, 控制器带有2路可编程输入/输出,可以通过编 程设置为总报警和总故障输出 插拔式接线隔离保护板,可靠防护, 插拔式接线隔离保护板,可靠防护,安装方便
Page 17
FD181系列现场设备 – 火灾显示盘 系列现场设备
FT1810 火灾显示盘
液晶点阵(192×64)中文显示,最多支持252条 液晶点阵(192×64)中文显示,最多支持252条 (192 中文显示 252 事件信息 支持火警和故障信息显示 独立通讯总线,通讯稳定, 独立通讯总线,通讯稳定,响应快速 支持控制器范围内的跨回路显示 每台控制器支持最多32 32个楼层显示器 每台控制器支持最多32个楼层显示器 体积小巧, 体积小巧,美观大方
西门子FS18火灾自动报警系统介绍
西门子FS18火灾自动报警系统介绍西门子FS18系统是基于西门子在消防安全领域超过160年的专业经验,采用了全球的领先技术。
产品和系统设计理念秉承安装、维护和使用全方位的简便原则使安装调试最简化。
FS18系统是西门子前几代系列产品的创新品,在15年内保证备品备件的正常供应。
系统稳定,故障率低,较强的防误报能力,系统反应速度快系统采用源自欧洲的全新传输协议,保证信号可靠传输,误报率减至最低,超强的抗电磁干扰能力,长距离现场总线仍可保持信号稳定。
所有现场设备都内置先进的微处理器,通讯控制可靠。
系统易于安装,开通调试简易,系统低维护率两线制无极性回路总线,接线方便,回路自由拓扑结构,支持环路和任意分支,控制器接线端子均为插拔式,方便安装调试,可控制器直接编程,可脱离PC的编程调试,高效的编码标签安装调试方法。
创新性的快捷右键操作,操作更加方便快捷。
创新替换功能,更换损坏设备后无需请厂家技术人员到现场进行编程或使用编码器编码,主机自动识别,大大降低了后期维护的便利性及成本。
国际品牌高品质产品全球的统一品质标准,国际规模化元件采购,国内生产基地本地化生产,优化产品成本。
齐全的现场设:所有现场设备均为西门子同一品牌;迅捷的探测反应:探测器的报警反应时间仅为0.5秒,远远超过国标要求;智能的探测算法:该系统沿用西门子独有的智能DA火灾探测算法,保证对火灾的精确判断;电路板防潮蜡封涂装保护:所有现场部件均使用蜡封涂装保护有效提高设备防潮能力及使用寿命。
该系统自上市以来,在国内外大量使用,为楼宇提供可靠地保护,目前在成都地区使用的项目有:航天大厦(成都市最高的大楼)中汇广场;川投大厦康弘药业西区工厂富士康西区工厂新城大厦成都艾特制造中心核工业部生产基地成都安全电子有限公司2011年3月11日。
西门子消防报警系统说明书S1151 CI11控制器
Fire Safety S1151系统产品说明北京西门子西伯乐斯电子有限公司1/4西伯乐斯生命财产的保障S1151 CI1142 控制器特点●标准H38壁挂式机箱。
●整机采用组合式硬件与软件结构,标准型控制器由若干种功能卡组成,且备有足够种类的功能卡,可以进行多种功能扩展。
因此,可根据工程需要,以非标准方式对控制器的功能进行多样化配置。
●选择特定应用的信号处理算法存储在探测器的微处理器内,远距离调整探测器特定的响应行为,真正消除误报。
●和探测器一起,随时对现场火灾参数和探测器使用状态进行交互式智能化分析,并根据控制器特定的编程条件得出以下情况,给出相应的信息/警报:—探测器应用状态:正常;正常(略有异常);不适配;故障。
—探测器报警状态:正常;正常(提请注意);有险情;严重险情。
●自动诊断系统故障。
故障状态下火警优先,甚至在主CPU故障情况下也能报应急火警。
●能转换交互式探测器等部件的工作模式:即使在建筑装修、调试期间仍能探测、分析火灾。
●控制器面板采用液晶中文显示、菜单操作方式,可显示系统运行的各种信息、自动存储信息记录达1000条。
●通过编程可满足各种复杂的联动逻辑关系。
应用●用于交互式可编址两总线火灾报警联动系统中,做为S1151系列火灾探测器及其它现场可编址部件的监视/控制装置。
这些可编址部件可以是:—光电感烟探测器DO1152A/OP820;感温探测器DT1152A/HI820;复合感烟感温探测器DOT1151A;—手动报警按钮MT820,消火栓手动报警按钮MT830;—输入模块DO1157-AA(三路);—输出模块DC1156-AA(三路);—专用输入输出模块DC1192;●在系统中除利用可编址输出模块控制现场消防设备外,还可由控制器直接控制若干个输出设备。
●满足国家标准GB4717“火灾报警控制器通用技术条件”与GB16806“消防联动控制设备通用技术条件”,其应用设计遵照国家标准GBJ116“火灾自动报警系统设计规范”。
XXX项目西门子报警系统的消防联动调试重难点汇总
若采用西门子报警主机,报警回路必须做成一个大环,大环上单点可以引出一路分支,坚决不能一点引出两路分支,分支不能形成环路,分支尽量小,分支上不能再引分支,即不能支上支。商铺回路与公区报警回路最好分开设置,若不能,将公区设为总环路,每个店铺单独设为分支。
1、先拆除卷帘信号线,让卷帘单位先单机调试,消防单位在未插信号线的情况下进行消防联动,并逐个检查模块是否动作。
2、卷帘单层单机调试完成,消防单层联动模块动作正常后,由卷帘单位将信号线插回,进行单层中庭联动下降。
3、1-4层逐层联动完成后,在首层进行整体个中庭联动。
尽量少采用组合式卷帘
6
6、大面积采用电动挡烟垂壁
要求业主变更未桥架
在风机房内风机数量较多的情况下,多线敷设应采用桥架敷设。
9
卷帘、挡烟垂壁采用有源信号控制,24V电源取自消控室,造成末端电压不足,无法启动。
改为无源信号
改为无源信号
10
消防电话噪音大,听不清。电话线未采用屏蔽线。
将电话线改为屏蔽线
将电话线改为屏蔽线
1、要求西门子厂家驻场。
2、提供原始编码表后,要求厂家2天内提供程序。每天追问厂家程序进度。
3、安排个分包限时提供数据给消防单位,包括风机服务区域等。
4、分楼层出数据及程序。
1、如项目不大,建议安装前先抄ID码,并给设备贴上安装位置,工人现场按预先确定的位置进行安装。这样可以提前完成ID码回收。
2、防排烟、卷帘尽量放在消防单位实施,避免推诿扯皮。
XXX项目西门子报警系统的消防联动调试重难点汇总
序号
重难点描述
我们的解决方法
西门子消防报警系统操作指导书
消防中心接处警操作程序(一)当中央总控制台报警后1、按消音键消音;2、用对讲机或内线电话向报警指示区域得保安问清报警原因;3、如就是其她原因报警或误报,即通知保安按复位键复位;4、总控制台复位;5、如复位后再发生连续三次误报,则由消防中心派员查明原因并采取相应得措施。
(二)当确认发生火灾后:1、立即用消防专线电话向发生火灾区域得员工问清失火部位、火势大小、什么物质在燃烧等情况;2、立即将联动控制键打到自动状态,联动启动消防设施扑救火灾;3、迅速向科文领导与物业处报告火情与失火部位,并向消防支队报警:(报警要讲清失火单位名称与地点、失火部位、火势大小、燃烧物性质等五项要素);4、通知工程部迅速关闭新风机与空调系统,切断相应部位得电源;5、检查设备联动情况,立即手动开启未联动得消防设备,组织人员疏散与扑救工作;6、坚守值班岗位,听从科文领导进一步指示。
西门子消防报警系统操作一、出现警报找着报警点1.当出现火警时,消防主机会有报警声,同时在消防电脑上会出现如下图1所示,该示例就是一手报报警、图12、点击上图1所圈得图标,出现下图2得画面,单击图示得搜索查找按钮,系统自动寻找报警点图23、如图3所示报警点,示例为地下室西车道图3二、联动操作与强启水泵1.系统自动(系统联动)消防系统联动启动按钮在中间消防主机得第二个联动控制盘上,如图4所示图4下图5就是该控制盘图5(1)将该控制盘设置成手动状态:顺序按下ABA,允许手动灯亮,如图6、取消手动按B图6(2)如图5,在该控制盘手动状态下,按下消防系统联动(自动)按钮,整个系统即在联动状态、停止联动,请按下相应得停止按钮、2.强启水泵消防水泵(喷淋泵、雨淋泵、消防栓泵)启动按钮在左边消防主机得第一个联动控制盘上,如图7所示图7下图8就是该控制盘,共有三组水泵,从上倒下依次为喷淋泵、雨淋泵、消防栓泵,同时每组泵都有相应独立得启动与停止按钮,见图中标识、启动、停止图8(1)将该控制盘设置成手动状态:顺序按下ABA,允许手动灯亮,如图9、取消手动按B图9(2)如图8,在该控制盘手动状态下,按下需要开启水泵得启动按钮,即将水泵强制启动、需停止水泵时,按下相应得停止按钮。
西门子S1151系统应用设计指南2
联动控制盘
9341A 设备操作盘与控制器一起用于报警及联动控制系统中。主要 用于控制柜及琴台上。共有相互独立的 8 路输出。 “自动”状态下,接收系统(控制器或其它设备)发出的“请求” 信号后直接控制消防设备,此时“请求”指示灯亮。 “手动”允许时,可以通过键盘发出启动及停止命令(手动时需要 操作软件锁 ABA 键)。此时相应路的“启动”指示灯亮。 设备启动后信号返回时“联动”指示灯亮。“请求”、“启动”和“故 障”信号在显示板上显示并用不同类型的声音报警。 有“试灯”和“消音”功能。 标准的 3U 面板。
西门子火警系统终端与设备数据手册说明书
SiemensData Sheet 9803Smart Infrastructure – Building Products/fireThe Fire Terminal and equipment connects to C-WEB network that can be configured for system-global view or specific-panel local view.This configuration allows the operator for system control to ‘acknowledge’ events; control system notification appliances circuits (NACs), and reset the system.The Fire Terminal and equipment allows for connection to the Remote Peripheral Module (Model FCA2018-U1) and / or the Remote Terminal Displays (Models FT2014-U3 / R 3, FT2015-U3 / R 3).The Fire Terminal contains the site-specific program configuration which is created in the custom-configuration programming tool.☐Contains the following system components:▪ Operating unit (Model FCM2018-U3or Model FCM2019-U3)▪ Fire Terminal Module (ModelFTI20001-U1)▪ C-WEB Module (Model FN2001-U1) ▪ One-height-unit back box (ModelsFHB2001-U1 / R1▪ One-height-unit outer door(FHD2001-U3 / R3)▪ Inner door (Model FHD2005-U1) ☐Multi-use, main-system interface modules▪ Power, Alarm, Supervisory, Silenced,Ground Fault, Audibles On, and Trouble system-status LEDs ─ with Alarm as having a larger, distinctive LED▪ Partial system disable LED▪ Audible Status LEDs (‘On’ and ‘Silenced’) ▪ 10 usable LEDs▪ Model FCM2019-U3 contains one (1)set of 48 light-emitting diodes(LEDs) ☐System-control menus▪ Context-sensitive ‘Help’ menu ▪ Four-way navigation buttons andextended-views capability ☐User-prompted large softkey buttons for multi-programming options and system-control operating sequence▪ Seven (7) spare user-programmablebuttons▪ Slide-in labels appear adjacent tosystem-operation buttons ☐FTI-2001connects to 24VDC power source via screw terminal▪ Ribbon cables connect to theoperating unit ☐Display shows eight [8] lines, 40 characters per row▪ Plain-text display with two (2) lines ofinformation per Alarm event ▪ Context-sensitive soft keys▪ Additional display of location-specificreaction texts can be stored ▪ Several events are displayedsimultaneouslyModelFHB2001-U1ModelFHD2001-U3☐ Operating access for full-systemoperation, via password▪ Several operator terminals are possiblefor each fire-detection system [up to 16 nodes, max.] ☐ Optional accessories available:▪ Auxiliary power supply▪ RS ─485 module (Model FCA2016-U1) ▪ Remote terminal display (ModelFT2014-U3 / R3)▪ Remote terminal display with control(Model FT2015-U3 / R3)▪ Remote peripheral module (ModelFCA2018-U1) ☐ 2”─x ─ 4-3/4”, back-lit LCD☐ Style 4 and Style 7 wiring configuration☐ Requires the C-WEB module (ModelFN2001-U1) for C-NET connection☐ Ethernet-port connectivity for systemconfiguration and Firmware-software transfers▪ Compatible with built-in EEPROMfirmware ☐ Can be configured for system global viewand control ☐ Global annunciation and control capability ☐ System operation and indication ☐ Convenient, context and status-sensitiveoperation via soft keys ☐ Alphanumeric pad☐UL 864 9th Edition Listed, ULC Listed☐ FM, CSFM and NYC Fire Dept. ApprovedModel FTI2001-U1ModelFCM2018-U3NOTICE – The information contained in this data-sheet document is intended onlyas a summary, and is subject to change without notice.The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information.Copies of install-type, instruction sheets – as well as the General Product Warning and Limitations document, which also containsimportant data, are provided with the product, and are available from the Manufacturer.Data contained in the aforesaid type of documentation should beconsulted with a fire-safety professional before specifying or using the product.Any further questions or assistance concerning particular problems that might arise, relative to the proper functioning of the equipment, please contact the Manufacturer.The Fire Terminal (Model FT924) consists of the Fire Terminal Board (Model FTI2001-U1), the Operating Unit (Model FCM2018-U3 or Model FCM2019-U3), and a one-height-unit enclosure.Each Fire Terminal contains one (1) 2” –x – 4-3/4” Video Graphics Array (VGA) monochrome LCD screen and LEDs for displaying system status. An audible will sound when there are unacknowledged events on the system.The display is surrounded by keys that are used to control the displayed information, and to navigate through these screens. Keys are also provided to obtain ‘H elp’ and to enter into the menu features of each operating unit.The display of each operating unit categorizes events by type, providing a separate event tab for Alarm, Gas Alarm, Supervisory, and Trouble events. The quantity of active events of each type is listed in each event tab. The display provides two (2) full lines of text message for each event.Each event can have a 40-character custom message describing the location for a given event. In addition to the text message, the system displays the category of the active event: (e.g. Automatic Alarm, Water Flow, Manual , etc.) the category means more to responding officials than model numbers. Up to two (2) events can be displayed at a time. When more than two (2) events are present, the up-and-down arrow keys allow the end-user to scroll up and down the list of events. A progress meter on the side of the list indicates the size of the list of events and the location in the list. New, ‘unacknowledged’ events are indicated by a flashing exclamation point ('!').Each interface also provides a completed menu for running system status reports (with a ‘Print Preview’ feature directly on the screen before sending the report to the printer).The Maintenance menu is accessed by password. When the end-user enters this mode, the LCD will be enabled, prompting the user to enter a password. System control within the maintenance menu uses easy-to-read touch buttons.The Fire Terminal and equipment are FM (#3010), CSFM (#7165-0067:0259) and FDNY (#6104) Approved.ProductData Sheet Number Fire Terminal Enclosures andEquipment9807® PROSiemens Industry, Inc.Smart Infrastructure - Building Products 2 Gatehall Drive • Parsippany, NJ 07054Tel: (973) 593-2600March - 2023(Rev. 4)Temperature and Humidity RangeProducts are UL 864 9th Edition listed for indoor dry locations within a temperature range of 120+/ 3°F ( 2°C) to 32+/ 3°F (0+/ 2°C) and a relative humidity of 93+/ 2% at a temperature of 90+/ 3°F (32+/ 2°C).Related Documentation。
西门子消防产品选型
涂装车间应用产品指导性意见一、消防火灾自动报警系统1.系统总体技术要求1.1本系统所选用的产品必须符合我国现行国家标准和规范的要求,产品生产制造企业必须具有经国家消防产品质量检测中心测试合格并具备有效证书。
1.2应完全遵循国家(国际)的有关工程的设计和施工规范(标准)以及测试和验收规范。
1.3投标人必须确保本系统不因投标方提供设备本身的原因影响通过国家或地方消防主管部门的所有消防验收并达到国家验收优良工程的要求。
1.4火灾探测报警和联动控制系统按照我国现行的规范要求,整体系统应能保证在任何情况下不受外界干扰,可独立操作、运行和管理而完成火灾自动探测报警和联动控制。
1.5为了保证系统的正常运行,投标人所选火灾报警设备要求是国际著名品牌,在中国的工厂至少有15年的生产制造经验。
1.6要求火灾报警系统设备安装简便,操作简单,维护方便;1.7为保障人员、财产安全,要求火灾报警设备工作稳定可靠,不得因误报影响用户的正常工作秩序。
1.8火灾报警设备的零部件、易损部件应容易拆卸、更换,以便于降低维保工作的成本、难度。
1.9系统设备应在满足应用要求的基础上,遵循技术先进、设备优良、经济合理和质量优质的原则。
1.10为了适应未来的发展需要,系统应具有较强的可扩展性,保证用户的投资收益最大化。
2.火灾报警系统技术要求2.1为保证系统探测准确,避免探测设备发生误报、漏报,要求每个现场部件均自带16位微处理器,内置智能DA火灾探测算法,由探测器本身对采集数据进行智能分析判断,保证准确地分辨真伪火情。
2.2系统采用二总线,无极性;总线支持环形加分支、任意分支的布线方式。
2.3探测总线采用Φ1.5 mm2双绞线时,传输距离最远点达4000米,回路总长(含分支)5000米。
2.4为保证系统的灵活性,要求每个探测回路最多可接252个设备,探测器、手报按钮、模块可混合连接,其中探测器每个回路不低于200个。
2.5系统设备编码采用软件自动编址方式,在底座与探测器上不应有任何手动拨码编码。
消防火灾自动报警系统设计方案
3 消防火灾自动报警系统3.1概述依纳太仓(中国)厂房扩建工程项目位于原厂房与办公楼之间,占地面积12600平方米,3层厂房,包括新扩建厂房、辅助用房、仓库和公共设施。
为了给该建筑考虑设置一套能够保证其财产及人员安全的可靠性极高的火灾自动报警系统,我们根据国家消防有关规范及用户的要求并结合本工程的特点,使用西门子智能型火灾自动报警系统及相关配套产品,该产品完全符合产GB4717-93[火灾报警控制器通用技术条件]和GB16806-97[消防联动控制设备通用技术条件]的国家标准。
系统采用消防中心集中控制方式,整个系统的组成是:火灾自动报警系统控制器;智能型感烟探测器、智能型感温探测器、手动报警按钮(具有消防电话功能)、火灾警铃、联动控制用模块、终端器等;模块收容箱、消防集中供电电源;消火栓联动控制系统;防排烟联动控制系统;火灾事故广播联动控制系统;防火卷帘门控制系统;电梯控制系统;非消防电源控制系统;3.2设计依据《火灾自动报警系统设计规范》GB50116-98《民用建筑电气设计规范》JGJ/T16-92《高层民用建筑设计防火规范》GB50045-95《火灾自动报警系统施工及验收规范》GB50166-92《建筑设计防火规范》GBJ116-923.3系统原理该火灾报警系统是一个多优先点到点式网络控制系统,与智能式系统设备及其控制设备使用数字式通讯协议。
火灾报警系统组成:火灾报警控制盘(MFAP)消防中心,包含有LCD液晶显示屏手动报警按纽声光报警器火焰探测器风管感烟探测器3.4具体设计思路3.4.1系统布置本设计方案根据本建筑的功能,在消防中心设置琴台式消防报警主机,可对整个的报警情况进行监控。
在消防中心设联动控制盘,遇紧急状态时,可直接通过操作面板进行手动操作,执行相应的外部设备联动动作,进而消灭火险。
在消防中心设置对厂房广播系统的强切功能,实现火警时的消防广播。
本系统的BDS051智能烟感探测器,主要用于办公室和机房等环境烟尘较小的场所。
基于PLC消防报警系统设计
基于PLC的消防报警系统设计摘要火灾对国民经济和人民生命造成了巨大危害,但国外发达国家对火灾的预防及应对上我国和国外发达国家仍存在较大差距,因此,设计出一种可靠高效的消防报警控制系统是非常迫切的。
本设计完成了利用主要核心控制部件西门子SIMATIC S7-300型PLC对消防报警控制系统的设计。
首先,根据具体的控制对象选择合适的 S7-300 系列 CPU,这是控制系统的核心部件,在选择了一些火灾探测器的类型,探测器的选择好坏关系到报警及其它后续系列动作的关键。
其次,选择与S7-300相匹配的扩展模块,如数字 I/O 模块、模拟 I/O 模块、电源模块等。
最后,完成了控制系统的整体设计,达到了控制目标。
关键词:PLC;控制系统;消防报警PLC Based Fire Alarm System DesignABSTRACTFire on the national economy and people's lives caused great harm, but developed countries for fire prevention and the response to our country and abroad, there is still a wide gap between the developed countries, therefore, to design a reliable and efficient fire alarm control system is very urgent the.The main advantage of this design is completed the core control unit Siemens SIMATIC S7-300 PLC type of fire alarm control system design.Key first, depending on the control object to select the appropriate S7-300 series CPU, which is the core component of the control system, the choice of some type of fire detector, the detector alarm related to the choice of good or bad, and other follow-up action series . Second, select the S7-300 to match the expansion modules, such as digital I / O modules, analog I / O modules, power modules. Finally, to complete the overall design of the control system to achieve the control objectives.Key Words:Programable Logic Control;Control System;The Fire Fight Report To The Police目录第一章绪论 (1)1.1 课题研究的目的和意义 (1)1.2 课题背景 (1)1.3 国内外消防报警系统的现状及发展情况 (1)1.3.1火灾消防报警系统发展历程 (1)1.3.2消防火灾报警系统在国外的发展情况 (2)1.3.3消防火灾报警系统在国内的发展情况 (2)1.4 消防火灾报警系统的分类 (3)第二章系统的传感器的选型及其特性 (4)2.1 烟感器、液位传感器 (4)2.2 感烟器的选择 (4)2.3 液位传感器的选择 (5)第三章系统的硬件设计 (6)3.1 消防报警系统的要求、原理图设计 (6)3.1.1控制要求 (6)3.1.2消防报警系统工作原理图 (6)3.2 PLC相关模块的选择 (7)3.2.1 PLC的CPU模块的选择 (8)3.2.2 电源模块的选择 (8)3.2.3 变速频率调节器 (8)3.2.4 系统的硬件列表 (8)3.3 系统的电气回路图 (17)3.3.1 消防水泵单相交流电机电气回路图 (17)3.3.2 排烟风扇单相交流电机的电气回路图 (18)3.3.3 防火卷帘门三相交流电机的电气回路图 (19)3.3.4 储水水箱的PID控制的三相交流电机的电气回路图 (20)3.3.5 系统输入输出点: (21)第四章控制系统的软件设计 (25)4.1 系统的软件程序流程 (25)4.2 STEP7编程软件 (26)4.2.1 STEP7介绍 (26)4.2.2 STEP7编程的各个步骤 (26)4.2.4 组合硬件和软件 (27)4.3 STEP7硬件组态 (28)4.3.1 消防报警控制系统的PLC模块在STEP中的选择 (29)4.3.2 控制主程序 (29)4.4 用组态王监控软件组态监控消防控制系统 (35)4.4.1 组态王简介 (35)4.5 在组态王中建立监控消防报警控制系统 (35)4.5.1 新建一个工程项目 (35)4.5.2 选择与PLC S7-300 作为连接设备具体过程如下 (36)4.5.3 在数据词典中定义变量 (38)4.5.4 所要监控的具体的输入输出量为下图: (38)4.5.5 在编完程序后,在VIEW中演示的结果为 (39)参考文献 (40)致谢 (41)第一章绪论1.1 课题研究的目的和意义火灾早就成为危害我国的重大灾害之一。
西门子 FC18 型火灾报警控制器(联动型) 说明书
自动转为屏幕保护状态,延长液晶屏的使用寿命;当有事件/操作发生时,液晶屏自动 点亮,控制器自动显示所发生的事件,按照逻辑关系联动相应设备。 z 控制器带有 2 路可编程输入/输出(输出:40mA@24VDC,可通过编程设置为总报警 和总故障输出;输入:干接点)。 z 控制器带有 1 路声光控制电路(0.5A @24VDC)。 z 控制器自带 8 路联动盘(输出:40mA@24VDC),用于重要设备的自动控制或手动操 作。 z 采用“组”编程方式, 同用途的设备可分配到同一个“组”中进行编程,简化逻辑关 系,节省编程时间。 z 单台控制器最大容量 504 点,可实现 8 台控制器组成网络。 z 网络总线(FCnet),最远距离 1000 米。 z 回路总线(FD18-Bus)为两总线无极性,建议使用Φ≥1.0 mm2 的阻燃双绞线,传输 距离环路可达 2500 米,支路可达 1500 米。 z 控制器有三种用户级别,分别为:1 级用户、2 级用户、3 级用户;在不同的用户级别 下可进行不同的操作,用户级别由密码保护。
西门子楼宇科技
消防与安防产品事业部
结构
接线端子 电源
回路卡 2 回路卡 1
电池
操作面板
z 接线端子均采用可插拔方式,每位端子上均有清晰标识,安装、调试、维修方便,快 捷。
z 自动映射设备。 z 可由控制器调整探测灵敏度,自动适应环境变化,使火灾报警可靠性大大提高。 z 既可以在控制器上现场直接编程,也可通过计算机快速编程。 z 现场部件标签上自带可撕式编码贴,方便工程调试。
安装过程: 安装要符合当地相关标准或规范。 1. 选择一个洁净干燥的、表面平整、牢固的墙壁。 2. 确定安装位置,要使得控制器的前门能自由地打开。 3. 在墙上标出 4 个安装孔的位置。 (见图 3) 4. 在安装孔的位置钻 4 个孔,并装上膨胀螺栓及螺钉(M6)。(记得在螺钉和墙壁之间留出一定的空 隙。) 5. 确定并打通控制器的进线孔。 6. 将控制器悬挂在螺钉上。 7. 将线穿进控制器。 8. 打开前面板,拧紧螺钉,使控制器牢固的固定在墙上。 9. 参考图 2-2、2-3、2-4、2-5、2-6、2-7、2-8 将电缆接到端子上。 10. 将电池安装到正确的位置。 11. 关上前面板,用专用工具锁好。将专用工具放在安全的地方。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
1.本方案是根据贵司提供的图纸及技术要求,并根据国家≤火灾自动报警系统设计规范≥结合我公司的设备特点,特别提供最新的AlgoRex®智能类比型火灾自动报警系统方案。
方案的组成为:•消防自动报警系统•消防联动控制系统•消防电话系统2.AlgoRex®智能类比型消防报警系统是瑞士西伯乐斯有限公司研制的新系统,自推入上海市场以来,已先后有三十多个项目签约,(88 层)浦东金茂大厦(凯悦大酒店)、上海红塔大酒店、上海华亭喜来顿酒店、上海东方明珠国际会议中心、金玉兰广场、虹桥机场、浦东国际机场、上海市黄浦江行人隧道等先后使用该系统。
此系统在每个探头中引入了计算机芯片,通过与主机的联络结合各种不同环境,采用不同的参数设置和系统的模糊逻辑判断,以使系统达到无误报状态,保证系统高度可靠运行。
AnalogPlus 是AlgoRex®系统的一部分,AnalogPlus是西伯乐斯以合理的价格推出的崭新的优质先进消防警报科技-AlgoRex®高智能可编地址码系统,是业内最先进的独立地址码式智能型消防探测系统之一,而其模块式结构及广泛的性能,更适用于不同规模的系统。
AnalogPlus拥有先进的功能,提供卓越的成本效益,还提供下列优秀功能:•分布式智能系统及卓越的紧急操作性能。
•装置于不适当环境下的自动警示功能。
•不受电磁干扰,强大的抗干扰功能。
•卓越的自我监控功能,使例行检查工作减至最低。
3.根据大酒店的规模和特点,在消防控制室设置了一套CS11高智能型主控机、一台CT11中文显示终端以及手动联动控制柜,并同时配置了LMS中央管理系统。
整个消防系统功能:•通过多个Bus总线连接各自楼层各类探测设备:烟感、温感、功能模块等,形成环形网络,以确保系统高度的可靠性。
•对各类探测器,实现各种环境的参数设置,以保证探测器无误报状态。
•系统自动以中文文字和图形显示大厦所有探测器状态及事件。
•很强的现场编程功能,以适应系统和环境的变化。
•实现各类联动的自动启动和手动启动,根据用户程序软件设定任意逻辑组合,自动输出相应的接点或发生控制指令,以实现外部设备的联动。
•在应急状态,可通过手动联动控制柜的操作面板实现对应手动操作,执行相应的外部设备动作,以达到灭火的效果。
4.在主楼消防控制室设置一套LMS中文中央管理系统以图形显示大酒店所有探测设备的报警状态,并为系统集成提供软件和接口支持。
5.本系统设置的智能型温感探测器DT1131,主要用于车库和部分机房,保护面积为 20-30 平方米。
6.本系统在机房等其它公共场所均设置DO1131智能型光电烟雾探测器,每一个探测器均有IC芯片并具有记忆存贮参数功能,对不同的环境具有不同的参数设置,最大程度保证探测器的无误报状态,确保该报警系统处于无误报状态。
7.在大面积空间,如车库均设置D2417传统型温感。
8.在主要道口设置DM1131地址码手动报警器,可直接接在探测总线回路上,用于人工手动报警时通过CS11控制机启动所需联动设备。
9.设置的DC1131讯号模块,有一个独立可编程输入信号点,主要接收水流指示器(压力开关,监控阀,消火栓按钮信号)并送入CS11控制机,以显示水流系统工作状态,按预先指令程序,自动启动喷淋泵。
10.在每层设置DC1136控制模块有输入/输出二个接点,用于消防外围设备的总线自动联动。
11.消防联动控制系统(1)火灾探测系统火灾探测系统由CS11控制机及各种类型的探测器组成。
控制机每一个Bus可接128个各种类型的探测器,信号模块,控制模块,并由二根1.0 - 1.5 mm2双绞导线环形联接而成,系统采用软地址计算机系统,各探测器均能报警到点。
任何一点的报警及故障都可以在CT11显示终端中用中文显示出来,并可通过专业通讯回路在打印机中实时记录。
根据预定的程序,CS11控制机可输出相应的联动信号,达到联动有关消防设备的目的。
注: 所有的I/O接点均为无源接点信号(2)防排烟控制系统当走道、电梯厅等处的烟感探测器发出报警讯号,CS11控制机通过软件预设发出指令输出联动信号,打开报警层及其下层排烟阀,同时开启排烟风机和正压送风机,进行机械排烟。
在消防中心手动控制柜上配有防排烟阀和风机的启停按钮,作紧急启停操作,并有运行故障显示。
(3)消防栓控制系统人工启动手动报警按钮(DM1131)之后,主机回路发出报警信号,确认后自动输出讯号控制消火栓泵开泵。
每台消火栓水泵的运行故障讯号可在消防控制及显示屏上显示,在紧急情况下,可在手动控制柜面板上对每台水泵进行手动控制和状态信号显示。
(4)自动喷淋控制系统喷淋泵的自动启动由压力开关和水流指示器联动控制,喷洒系统水流指示器的讯号通过DC1131送至CS11控制机,显示及打印机打印记录。
当报警确认后,由压力开关自动启动喷淋泵,在消控中心手动控制柜上反映泵的工作状态,并可进行直接应急手动启动和停止泵。
(5)电梯控制系统当发生火警烟感器报警时,CS11控制机按予先程序指令出信号给电梯控制盘,使全部电梯回降首层,其中一台消防电梯迫降至底层待命。
并在手动控制柜上配置手动迫降开关和状态显示。
(6)卷帘门控制系统当发生火警时,根据卷帘门两侧两组探测器不同的报警分区,CS11控制机可按预先程序设置,自动发出相应信号,使卷帘门降到离地面1.5米,当两组同时报警时,自动控制其下降到底。
(7)消防控制电源在消防中心设置一组24V DC控制电源,包括一台充电机和一组备用电池,作消防控制柜用控制电源,供扩大接点容量的继电器和24VDC的联动设备使用。
但在施工中需由施工单位将220V的消防电源送至消防控制机位置。
(8)消防广播控制系统当发生火灾报警时,CS11控制机按程序设置,自动发出切换指令给紧急广播系统,自动转换相应的报警分区及上下层,以使进入紧急广播状态,通过应急消防广播自动切换报警层及上下层的消防广播。
指挥人们疏散及救火,同时可用于各楼层呼叫或全区呼叫。
(9)其它联动控制系统当发生火灾报警时,CS11控制机按预先设定程序自动切断报警层及上下层非消防电源,新风机组,开启排烟风机,正压送风机,并在手动控制面板上配置手动启动按钮,以直接对该风机执行控制,并有信号返回。
(10)消防电话系统在消防中心控制室,设置一台消防主机电话,通过各层设置的电话插孔,巡逻人员手持消防电话筒可直接与消防中心联络,指挥救火和抢救。
(11)空调控制系统当发生报警时,由CS11主控制机发出指令,给相关楼层的控制模块或继电器模块,切断相应层及上下层的新风机。
12.火灾自动报警系统设备性能特点说明(1)系统特点说明*新系统的操作,完全由微型电脑处理器执行,通过分散控制与集中管理。
整个系统由位于消防指挥中心的AlgoPilot CT11火灾报警控制机操作显示终端监管及控制。
*AlgoControl-CC11火灾报警控制机,根据大厦的结构特点,可分别设置在不同的区域,连接AlgoPilot CT11火灾报警控制机操作显示终端,监察数据通讯网络。
*AlgoRex新系统,采用高度分散智慧的方式,一方面把所有的设备如中央控制终端、火灾报警机操作终端、火灾报警控制机等,连接到信息处理网络上。
另一方面,连接现场设备探测装置和联动设备,其操作情况不为其他设备所影响。
任何一方出现问题,都自动退出系统网络。
*西伯乐斯自从首创消防报警探测器以来,目前产品走在世界同类产品最前列,同时它又在操作软件技术上是最开放的,具有标准接口平台,可顺利与世界著名的楼宇自控厂家如:霍尼韦尔、兰吉尔、JOHNSON等联结,达到完美组合,同时消防报警的有关情况可在楼宇自控中得到二次监测。
这一切已在国内外无数大工程中得到体验。
(2)CS11消防报警控制机功能特点:CS11系统配置相当灵活,可根据工程需要进行最经济、合理的组合,从500点至6800点。
对火灾报警和事件有记忆功能,当控制机收到各类外围设备信息时,发出声光报警字符。
若同一时间有许多项事件发生,可逐项取阅有关的事故资料。
控制机发出故障的声光信号,故障类型除线路开路、短路、接地,还有外围设备的各种信息,如探测器肮脏、应用错误等。
控制机的遥距功能可对探测器作不断应用测试,以避免房间用途改变而造成误鸣,紧急操作系统在主机CPU损坏时,探测器依然能报警。
探测机有独立备用电源,失电时,可以维持系统24小时。
•系统采用总线制模拟类比型技术•区域控制机与操作终端分离式结构,使系统设计更为灵活•彻底汉化的系统软件•具有自动巡检功能•具有自动再生保护功能,即回路故障后系统自动由主机担任回路诊断功能、•回路容量留有10%以上的余量,以备将来系统的扩容•主机内置继电器联动输入输出,共有240个联动输入输出,并有0-99秒的延时可调•联动程序现场编程功能•多级密码操作功能•实时记录打印处理功能•系统维修软件提示功能(3)探测原理西伯乐斯AlgoRex火灾探测系统采用分布智能和神经网络算法以及专用集成电路(ASIC),主机对探测器所发送讯息进行统计评估(如同一探测区内有二个以上探测器时,领近探测器所发出的讯息亦列入评估范围内),再来确定是否发出火警警报。
同时控制机设有:有人值班和无人值班以及报警信号确认时间设定(0-600秒)。
*光电烟感探测器DO1131A:探测器内的微处理器储存已知的各种火警和非火警的资料。
在探测器内补偿了污染和温度对散射光传感器的影响并对信号的幅度、动态范围和持续时间等特征进行处理后,输出四种级别报警信号,由主机进行评估后发出报警信号,其主要应用场所设置在一般公共区域,办公室,机房,客房等处。
此探测器具有自学功能和自适应能力,并内置线路隔离器。
地址编码是软地址计算机自动编码方式,底座通用。
(4)手动报警按钮DM1131每一个手动报警器,都有微处理器,独立地址码内置线路短路隔离器,接入探测总线回路,并设置在走道及公共场所用于人工报警。
并内置测试状态。
(5)信号模块信号模块DC1131是一界面式输入模块,负责检查外置的常开无源触电,如水流开关、压力开关、闸阀、防火阀等。
内置式微处理器,不需额外电源供应,适用于潮湿的场所。
模块为二线制,可作明装。
内置线路隔离功能,每一个DC1131可接一个地址码信号的输入。
(6)控制模块控制模块DC1136是由一个输出、一个输入组成,用于外围设备的自动联动,并通过输入点接收外围设备的联动反馈信号。
每个DC1136都有内置式微处理器,线路隔离功能适用于潮湿的场所,模块为二线制连接。
(7)手动联动控制柜在消防中心的手动联动控制柜上设有大厦所有消防联动重要设备控制按钮。
如对消火栓泵、喷淋泵、消防补压泵、电源强切、电梯回归、排烟风机、正压送风机等采用直接控制方式,这样一旦消防报警控制机发生问题,这些重要消防设备可不受消防报警控制机的影响,直接在手动控制柜上控制,真正做到消与防的作用。