10KV电力系统短路电流整定计算表格
工程中短路电流实用计算表
小方式大方式小方式有名值(Ω)标幺值有名值(Ω)(三相短路)(二相短路)1北滘0.270.240.5622.458.932陈村0.340.310.4517.8311.113道教0.30.270.4120.2112.24东辉0.320.290.3918.9412.825东平0.410.370.4614.7910.876富安0.30.270.420.2112.57广教0.350.320.5617.328.938桂洲0.280.250.4121.6512.29红岗0.290.260.4220.911.910华容0.260.240.423.3212.511鸡洲0.350.320.517.321012建丰0.340.310.4717.8310.6413锦湖0.30.270.420.2112.514均安0.310.280.5119.569.815乐从0.30.270.4220.2111.916勒流0.280.250.4321.6511.6317龙江0.30.270.3720.2113.5118龙山0.330.30.4818.3710.4219伦教0.310.280.4619.5610.8720马宁0.370.340.516.381021南江0.280.250.421.6512.522容奇0.310.280.4219.5611.923顺峰0.350.320.4617.3210.8724上涌0.30.270.3720.2113.5125石洲0.370.340.4516.3811.1126文登0.30.270.3820.2113.1627五沙0.370.340.4716.3810.6428西华0.360.330.4916.8410.229新隆0.290.260.4320.911.6330杏坛0.30.270.4320.2111.6331羊额0.330.30.4318.3711.6332涌口0.360.330.4516.8411.1133元基0.380.340.4615.9510.8734中兴0.280.250.3521.6514.2935群力0.240.220.3525.2614.2936霞石0.370.340.4816.3810.4237博深0.370.340.4416.3811.3638泰安0.370.340.5216.389.6239宏图0.350.320.4217.3211.9110kV变电站变电站母线归算阻抗及短路电流序号站名10kV母线归算阻抗X1(S B = 100MVA, U B = 10.5kV)10kV母线短路电流(kA)大方式220kV变电站1南海0.330.30.4318.3711.63 2都宁0.30.270.420.2112.53大良0.240.220.3525.2614.29 4吉安0.270.240.3522.4514.29 5藤沙0.30.270.3520.2114.29 6旭升0.250.230.3124.2516.13说明:本表计算依据为市局2010年3月发布的《2010年佛山地区电网继电保护整定方案》中的顺德区220kV、110kV变电站10kV母线归算阻抗。
10KV配电线路继电保护整定计算方案
35KV塘兴变电站10KV生活临建区线开关继电保护定值整定计算编制:——张亮——审核:———————审定:———————2013年04月28日10KV生活临建区线开关继电保护定值整定计算1.整定计算说明1.1项目概述本方案是为保证海南核电有限公司35KV塘兴变电站10KV生活临建区线安全、连续、可靠供电要求而设的具体专业措施,10KV生活临建区线为双电源1019开关和1026开关供电,所带负荷为7台箱变,其中1019开关取自10KV I段母线,1026开关取自10KV II段母线。
正常运行时电源一用一备,箱变一次系统采用手拉手接线方式,电缆连接,箱变之间可通过箱变间联络开关灵活切换,最高带7台箱变,最低带1台箱变,现1019和1026开关保护装置型号均为WXH-822A微机保护,电流互感器为三相完全星形接线方式。
箱变进线及联络开关为真空负荷开关,无保护功能,仅作为正常倒闸操作使用,变压器高压侧采用非限流型熔芯保护,低压侧为空气开关,带速断、过流及漏电保护。
1.2参考文献1)电力系统继电保护和安全自动装置整定计算2)电力系统继电保护实用技术问答3)电力系统分析4)电力网及电力系统5)电力工程电力设计手册6)许继微机保护测控装置说明书2.线路及系统设备相关参数2.1回路接线图2.2系统设备参数表2.2.1开关参数表10KV开关参数表开关名称1019 1026 1013/1023/1053 1043/1073 1063/1033 安装地点变电站变电站1#/2#/5#箱变高压室4#/7#箱变高压室3#/6#箱变高压室开关型号CV1-12 CV1-12 XGN15-12 XGN15-12 XGN15-12开关类型真空断路器真空断路器真空负荷开关真空负荷开关真空负荷开关保护类型微机综保微机综保熔断器熔断器熔断器额度电流A 1250 1250 125 80 100 额度电压KV 12 12 12 12 12短路开断电流KA25 25 31.5 31.5 31.5 短路持续时间S4 4 4 4 4出厂日期2009年4月2009年4月出厂编号制造厂家常熟开关常熟开关福建东方电器福建东方电器福建东方电器备注1011/1012/1021/1022/1031/1032/1051/1052/1041/1042/1071/1072/1061/1062开关无保护,仅具有控制和隔离作用0.38KV开关参数表开关名称0401/0402/0405 0404/0407 0406/0403 安装地点1#/2#/5#箱变低压室4#/7#箱变低压室6#/3#箱变低压室开关型号MT20H1 MT20H1 MT20H1保护类型数字智能数字智能数字智能额度电流A 2000 1250 2000额度电压KV 1 1 1短路开断电流KA 65 65 65短路持续时间S 1 1 1 出厂日期出厂编号制造厂家上海施耐德上海施耐德上海施耐德备注控制单元0401/0402/0405 0404/0407 0406/0403 型号Micrologic 2.0E Micrologic 2.0E Micrologic 2.0E 保护类型完全选择型完全选择型完全选择型瞬时动作倍数In 8 8 6瞬时动作时间S 0 0 0短延时动作倍数In 2.5 2.5 2短延时动作时间S 0.3 0.3 0.3长延时动作倍数In 1 1 0.9长延时动作时间S 1 1 1接地动作倍数640A 640A 640A接地动作时间S 0.2 0.2 0.2备注低压开关的整定原则是低压侧短路时其穿越电流不会引起高压侧动作,计算方法略2.2.2变压器参数表变压器参数表变压器名称主变箱变编号1# 2# 3# 4# 5# 6# 7#变压器型号SCB-1250/10SCB-1250/10SCB-1000/10SCB-800/10SCB-1250/10SCB-1000/10SCB-800/10额度电流(A)72.2 72.2 57.7 46.2 72.2 57.7 46.2额度电压(KV) 10KV接线组别Dyn11调压方式无励磁调压空载损耗KW) 1.88 2.113 1.769 1.472 2.147 1.794 1.483 负载损耗(KW) 1.01 10.35 8.369 7.15 10.27 8.436 7.187 空载电流(%) 0.19 0.23 0.22 0.23 0.27 0.24 0.23 短路阻抗(%) 5.82 5.9 5.79 5.8 5.94 5.78 5.91出厂日期2010.12.152010.1.82011.11.152011.11.42011.8.2 2011.8.9 2011.8.16出厂编号210120060211110192211080053211108009211080117制造厂家海南威特电气集团公司计算采用值基准容量SjMVA 100基准电压Uj2KV 10.5基准电压Uj3KV 0.4基准电流Ij2KA 5.5基准电流Ij3KA 144.34电抗有名值 4.656 4.72 5.79 7.25 5.94 5.78 7.39 电抗标幺值 4.656 4.72 4.632 4.25 4.752 5.78 7.388 备注2.2.3电缆电缆参数表电缆参数表电缆名称1#进线2#进线3#进线4#进线5#进线6#进线7#进线3#4#联络电缆路径1019-1# 1026-2# 7#-3# 5#-4# 6#-5# 1#-6# 2#-7# 4#-3# 电缆型号YJV22电缆长度(米)545 560 163 265 131 135 205 130额度电压(KV)10电缆相数3*240出厂日期出厂编号制造厂家计算采用值基准容量SjMVA 100基准电压Uj1KV 10.5每公里电抗Ω0.08电抗标幺值0.04 0.041 0.012 0.02 0.01 0.01. 0.015 0.01备注1019-1026电缆总长度2.134KM,带7台箱变时运行电流有效距离为2.134-0.545=1.589KM2.2.4电流互感器参数表主设备名称线路线路线路线路型号LZZBJ9-10A5G LZZBJ9-10A5G TY-LJK120 TY-LJK120 安装地点1019开关1026开关1019开关1026开关额定电压12 12 12 12变流比200/5 200/5 100/5 100/5保护类型相间相间接地接地接线方式三相完全星形三相完全星形三相穿心式三相穿心式准确度等级10P25/0.5/0.2S 10P25/0.5/0.2S 10P/510P/5额定容量15VA 15VA10VA 10VA出厂日期2009年4月2009年4月2010年1月2010年1月出厂编号A03415/B03452/C03414 A06485/B03425/C03442 21332135制造厂家大连第二互感器厂大连第二互感器厂北京华星恒业北京华星恒业备注2.2.5系统电抗参数表系统电抗参数表(有名值Ω)南石站35KV母线昌城站35KV母线南塘线35KV线路昌塘线35KV线路塘兴站1#主变塘兴站2#主变塘兴站10KV母线最大运行方式 2.94 8.64 25.84 31.54 最小运行方式8.25 11.25 31.15 34.15 计算电抗13.7 11.76 9.2 9.2 南塘线供电昌塘线供电等值电抗连结方式Y/D-11 Y/D-11备注南塘线距离32.6KM,昌塘线距离28KM,其中南石站母线和昌城站35KV母线电抗由昌江供电局提供系统电抗参数表(标幺值)最大运行方式0.215 0.631 1 0.86 0.749 0.745 1.96 2.239 最小运行方式0.6 0.822 2.345 2.429 基准容量100基准电压Uj1 37 37基准电压Uj2 10.5 10.5 基准电流Ij1 1.56 1.56基准电流Ij2 5.5 5.5 基准电抗13.69 13.69 1.1 1.1备注系统电抗计算见10KV母线系统电抗计算表3.计算电路图4.回路阻抗计算解:确定基准值Sj=100MV A,Uj1=10.5KV, Uj2=0.4KV。
10kV变配电所短路电流的计算
10kV变配电所短路电流的计算(二)发布日期:2008-11-27 14:00:59 作者:杨蓉师科峰程开嘉来源:《电气&智能建筑》杂 ...浏览次数:0 文字大小:【大】【中】【小】1 变压器低压侧出线口的短路电流计算经计算得知,各型变压器容量在315kVA以上,其电阻值仅占总阻抗的4%~5%左右,用变压器电抗代替总阻抗计算误差在5%内,这样略去电阻对短路电流的影响可简化短路电流的计算。
(1)变压器电抗的计算式(1)中:Sbe—变压器额定容量(MVA);Sj—变压器基准容量,取100MVA;Ud%—变压器短路阻抗百分值,可从相应容量的变压器产品样本及设计手册查得。
一般常用变压器(油浸型、干式型)电抗计算例:已知干式变压器额定容量为500kVA,Ud%=40,标准容量Sj=100MVA,计算变压器的电抗值。
用式(1)计算:(2)用基准电计算,取Sj=100MVA,Uj=0.4则(3)系统短路容量取35MVA,10kV出线开关遮断容量的短路电流计算:例:已知系统短路容量为350MVA的电抗值为0.286,电缆线路为1km的电抗值为0. 068,变压器额定容量500kVA的电抗为8.0,Ij=144.5kA。
用式(2)计算:各类型变压器的低压侧出线口短路电流计算见表3~表8。
2 高压电器及电缆的热稳定校验高压电器及电缆应能承受在短路电流持续时间内短路电流的热效应而不致损坏,则认为是热稳定,且应满足《低压配电设计规范》第4.2.2条规定的热稳定校验公式进行校验。
(1)当短路持续时间大于5s时,绝缘导体的热稳定应按式(3)进行校验式(3)中,S—绝缘导体的线芯截面(mm2);Id—短路电流周期分有效值即均方根值(A);t—在已达到允许最高持续工作温度的绝缘导体内短路电流持续时间(s);K—热稳定系数.短路电流持续时间t与断路器的断开速度有关(见表9),当断路器的全断开时间小于0. 08s时为高速,0.08~0.12s为中速,大于0.12s为低速,当主保护为短路瞬动无延时保护,其短路电流的持续时间t可由表10选定,当有延时保护装置时,则应为表中数据加延迟时间。
地面10KV高压短路电流计算含计算公式
配电盘名称
613#井下动力一回 614#瓦斯抽采二回 615#瓦斯抽采一回 616#井下局扇 617#抽风机一回 618#井下动力二回 620#瓦斯发电厂 622#备用 抽风机房配电室
G1#1#风机进线柜 G2#1#电容 G3#风井绞车 G4#压风机一回 G5一回进线 G6#联络 G7#二回进线
0.85 162.4 0.8 0.8 0.85 0.8 405.0 420.0 24.0 230.4
27.1 47.0 5.3
2.57 2.57 2.57
30.8 51.3 30.8
307.9 307.9 307.9
1.53 1.53 1.53
4.98 4.98 4.98
0.85 205.2
瓦斯发电厂
AH1#1#变压器进线柜 AH2#2#变压器进线柜 AH3#3#变压器进线柜 AH4#4#变压器进线柜 AH5#高压出线柜 1 1000KW机组进线柜 9 1000KW机组进线柜 10 1000KW机组进线柜
29.0 5.6 8.2 5.4 7.6 7.3 7.6
289.7 56.5 48.9 32.6 303.8 292.5 303.8
8.5 3 7 5 7 7 7
1.53 1.53 1.53 1.53 1.53 1.53 1.53
5.3 27.1 31.3 47.0 5.0 5.2 5.0
2.57 2.57 2.57 2.57 2.57 2.49 2.57
# # #
72.2 72.2 72.2 72.2 280 72.2 72.2 72.2
100 100 100 100 400 100 100 100
20 20 20 20 80 20 20 20
1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
10kv变压器电流值计算表格
U
cosΦ
400
0.8
400
0.8
400Leabharlann 0.84000.8
400
0.8
400
0.8
400
0.8
400
0.8
400
0.8
400
0.8
400
0.8
400
0.8
400
0.8
根号3
1.732 1.732 1.732 1.732 1.732 1.732 1.732 1.732 1.732 1.732 1.732 1.732 1.732
道理应该选500/5的电流互感器,实际工作中考虑到其负荷达不到80%,也可以选400/5 的;10kVA变压器由于其电流值只有十几安,所以一般都采取直接式,实际工作不会安装
互感器。
电压互感器为1000:100 等效电阻R=R1R2/(R1+R2) 失压记时仪、电压补偿器管理办法
三相四线制电能表误接后的电能补退分析
各相功率表达式:P1=UuIucos(180o-φ);P2=UvIvcosφ;P3=UwIwcosφ 当三相负荷平衡时,有Uu=Uv=Uw=U;Iu=Iv=Iww=I
总功率P′=P1+P2+P3=-UIcosφ+UIcosφ+ UIcosφ= UIcosφ 正确接线时,P=3UIcosφ
当三相负荷平衡时,有Uu=Uv=Uw=U;Iu=Iv=Iww=I 总功率P′=P1+P2+P3=-UIcosφ+UIcosφ+ UIcosφ= UIcosφ
P=根号3*UIcosΦ,可以计算出电流值了。一般变压器都不允许满容量供负荷,取80%,U 取400V,cosΦ取0.8,于是得出315kVA变压器电流值
10kV配电工程继电保护整定计算
电力系统继电保护专题答疑之继电保护整定计算说明:本专题所用例题主要选自《电力系统继电保护整定计算》(许建安、王凤华编,中国水利水电出版社)和《电力系统继电保护习题集》(张保会、潘贞存编,中国电力出版社)。
专题一:线路阶段式电流电压保护图 1 典型中低压电力网络图1、保护Ⅰ段整定(1)短路计算最大短路电流(系统最大运行方式下发生三相短路)3max .min .min ()==++⨯S SkB S AB S l ABE E I X X X x L最小短路电流(系统最小运行方式下发生两相短路)3min .max .max ()==++⨯S S kB S AB S l ABE E I X X X x L (2)Ⅰ段整定值3.1maxⅠⅠ()=rel set kB I K I .10set t =Ⅰ s(3)校验最小保护区min .max 1.11⎫=-⎪⎪⎝⎭S set L X x 最小保护区百分比为min100%15%~20%>()=⨯ABL m L说明:对于线路变压器组,变压器故障时,无论是2QF/3QF 动作跳闸还是1QF 跳闸,LD 都失去负荷,故允许保护1的Ⅰ段伸入变压器。
LD图 2 线路变压器组2、保护Ⅱ段整定保护1的Ⅱ段不超过保护2的Ⅰ段.1set.2ⅡⅡⅠ=rel set I K I相邻母线有多个元件时,取set.2ⅠI 中较大者。
如何确保选择性?.1.2ⅡⅠ=+∆set set t t t说明:分支系数问题分支系数定义:相邻下一级线路保护Ⅰ段末端短路时,流过故障线路的短路电流与保护安装处的短路电流之比。
(1)助增情况(不考虑助增情况,保护缩短) (2)外汲情况(不考虑外汲情况,保护伸长).1.21ⅡⅡⅠ=relset set b I K I k 保护校验 Ⅱ段只做近后备在系统最小运行方式下,线路末端发生两相短路时,最小灵敏系数2min.11.5()Ⅱ>=kB senset I K I 3、保护Ⅲ段整定最大负荷电流max =L I (此处0.95是考虑到启动时电压可能低于额定电压5%,故取0.95U ) Ⅲ段整定值rel .1max ⅢⅢ=ss set L reK K II K{}.1.max ⅢⅢ=+∆set set next t t t灵敏度校验1)作线路AB 的近后备2min .11.5()ⅠⅢ>=senkB set I K I 2)作相邻线路BC 的远后备2min .max ()=kC S AB BCI2Cmin.11.2()ⅡⅢ>=senk set I K I【例题1】如图所示35kV 单侧电源放射状网络,AB 和BC 均设有三段式电流保护。
短路电流及开关整定计算
短路电流及开关整定计算一、胶带大巷五联巷移变概况:胶带大巷五联巷安装1台KBSGZYZ-630/10/1.2型移动变电站,主要为三采运输上山、2301N上巷掘进通风及排水,三采回风上山、北胶大巷、北回大巷、辅二下山皮带工区排水系统,辅二大巷准备工区排水系统及挖掘机,北胶大巷安装工区照明,辅二北郊五联巷至二采辅一下山段安装工区照明供电。
二、胶带大巷五联巷移变负荷三、短路电流计算10kV母线最小短路容量为140.9MVA,最大短路容量为214.59MVA,S j=100 MVA,电缆按0.08,架空线按0.4, 按现行供电系统接线方式计算。
三相短路电流周期分量计I d=(1/XΣ)×I j , U j=10.5kV,I j=100/(1.732 ×10.5)=5.5kA 110kV,变电站10kV系统母线电抗基准标幺值为X Xj*=S j/ S d=100/140.9=0.71地面变电所至一采区变电所高压电缆长度为3.55km,X L*=X O L(S j/U P2)= 0.08×3.55×(100/10.52) =0.2576;故XΣ=0.71+0.2576=0.9676三相短路电流周期分量:Id=(1/XΣ)×I j=(1/0.9676) ×5.5 = 5.68kA三相短路容量:Id=(1/XΣ)×S j=(1/0.9676) ×100= 103.3MVA二相短路电流:5.68×0.866 =4.9kA1、胶带大巷五联巷630KVA变压器二次出口端的短路电流Id1计算变压器二次电压1200V,容量630KVA,系统短路容量按100MVA 计算;查表得,系统电抗Xx=0.0144Ω;10KV电缆Lg=0.6km(图纸移变电源电缆长度);查表得,R0=0.3Ω/km,X0=0.08 Ω/km.高压电缆电阻、电抗:Rg=0.3*0.6=0.18ΩXg=0.08*0.6=0.048Ω变压器电阻、电抗:Rb1=0.0167ΩXb1=0.1246Ω∑R=Rg/K2b+Rb1=0.18/52+0.0167=0.0239Ω∑X=Xx+Xg/ K2b+Xb1=0.0144+0.048/5 2+0.1246=0.14092Ω2、2301上巷18.5KW潜水泵电机处短路电流Id2计算MYP 3*95型电缆的电阻、电抗:Lz1=677m查表得:R0=0.247Ω,X0=0.075ΩR Z1=0.677*0.247=0.16722X Z 1=0.075*0.677=0.05078MYP 3*70型电缆的电阻、电抗:Lz1=755m查表得:R0=0. 345Ω,X0=0.078ΩR Z2 =0. 345*0.755=0.26048X Z2 =0.078*0.755=0.05889∑R=0.0239+0.16722+0.26048=0.4516Ω∑X=0.14029+0.05078+0.05889=0.249963、辅二大巷巷道挖掘机处短路电流Id3 计算MYP 3*70型电缆的电阻、电抗:Lz1=50m。
10kv线路短路电流计算
66KV系统参数 电抗标么值 1.2683
主变压器参数 短路阻抗Uk(%) 容量MVA 电抗标么值
电阻标么值 0.4804
并列运行电抗标么 值
电抗标么值 电阻标么值 阻抗标么值
18.094849 24.061516 三相短路电流 30.106147 两相短路电流
电抗标么值
1.4428571 1.3286 导线电阻
0.422
0.595
0.823
1.131
电阻标么值 0.4804
并列运行电抗标么 值
0.69167894
电抗标么值 电阻标么值
7.34606803 5.90734694 1.020226757 1.110049887 8.63521088 9.52539683 2.209596372 3.210911565
电抗标么值 电阻标么值
I*w
0.0332
Iw(最小运行方式) 0.1826 (KA)
K(2)
0.1582 (KA)
7.34606803 5.90734694 1.020226757 1.110049887 8.63521088 9.52539683 2.209596372 3.210911565
10kv****线末端最大运行方式三相短路电流
1#主变 2#主变 10kv导线参数 LGJ—70 LGJ—50 LGJ—35
LGJ—25
9.09
0
6.3
0
长度(KM) 22.56
导线电抗
0.359
17.65 0.369
2.96 0.38
3.13 0.391
1.4428571 ห้องสมุดไป่ตู้##### 导线电阻
10KV继电保护整定计算
继电保护整定计算一、10KV 母线短路电抗已知10母线短路参数:最大运行方式时,短路容量为MVA S d 157)3((max)1.=,短路电流为KA U S I e d d 0647.91031573)3((max)1.)3((max)1.=⨯=⋅=,最小运行方式时,短路容量为MVA S d 134)3((min)1.=,短路电流为KA U S I e d d 7367.71031343)3((min)1.)3((min)1.=⨯=⋅=,则KA I I d d 77367.7866.0866.0)3((min)1.)2((min)1.=⨯==。
取全系统的基准功率为MVA S j 100=,10KV 基准电压KV U j 5.101.=,基准电流为KA U S I j jj 4986.55.10310031.1.=⨯=⋅=;380V 的基准电压KV U j 4.02.=,基准电流是KA U S I j jj 3418.1444.0310032.2.=⨯=⋅=二、1600KV A 动力变压器的整定计算(1#变压器, 2#变压器)已知动力变压器量MVA S e 6.1=,KV 4.010,高压侧额定电流A U S I He eH e 38.9210316003..=⨯=⋅=,低压侧额定电流 A U S I L e eL e 47.23094.0316003..=⨯=⋅=,变压器短路电压百分比%5.4%=s V ,电流CT 变比305150==l n ,低压零序电流CT 变比0n 。
变压器高压侧首端最小运行方式下两相断路电流为KA I d 38.6)2((min)2.=1、最小运行方式下低压侧两相短路时流过高压的短路电流折算到高压侧A I d 1300)`2((min)3.=2、最大运行方式下低压侧三相短路时流过高压的短路电流折算到高压侧A I d 1500)`3((max)3.=3、高压侧电流速断保护电流速断保护按躲过系统最大运行方式下变压器低压侧三相短路时,流过高压侧的短路电流来整定,保护动作电流 A n I K K I l d jxk j dz 6530150013.1)`3((max)3..=⨯⨯== 对应值75A 保护一次动作电流 KA K n I I jx l j dz dz 95.113065.=⨯== 电流速断保护的灵敏系数按系统最小运行方式下,保护装置安装处两相短路电流校验227.395.138.6)2((min)2.>===dz d lm I I K 电流速断保护动作时限取0秒。
10kV保护定值计算明细表
80 标准大于 返回系数Kf = 0.9 2 1.2 2
9.63 满足 7.67 满足 满足 灵敏系数按最小运行方式下线路未端d2二相短路电流来校验 灵敏系数按变压器低压侧d4二相短路电流来校验
灵敏系数校验 1.2 1
(2)
do
最大负 荷电流 = I I
(2) d2
灵敏系数校验 一 灵敏系数校验 二 过流保护 1.2 1
保护二次动作值 备注 I
dzj
3365.34 灵敏系数校 验= 0.47
42.07 2 不满足 18.10 2 不满足
按躲过线路未端d2短路时最大三相短路电流整定 灵敏系数按最小运行方式下线路始端d0二相短路电流来校验 按躲过相邻线路元件未端d4短路时最大三相短路电流整定 灵敏系数按最小运行方式下线路始端d0二相短路电流来校验
10kV雅拌线911开关保护定值重新计算过程表
可靠系数 保护名称 Kk 1.3 速断保护 灵敏系数校验 1.3 1 I I I
(2) do
接线系数 短路电流 Kjx 1 I
(3) d2
保护一次动作值 I 2588.72 1587.30 1114.13 1587.30
dz
电流比 80 80 标准大于 80 标准大于
标准大于 标准大于
(2)
d4
下面按变压器满载情况下的60%进行整定 最大负 荷电流 = I I
(2) d2
276.06 1582.18 818.05
368.08 灵敏系数校 验= 灵敏系数校 验= 4.30 2.22
返系数Kf =
0.9 2 1.2
4.60 满足 满足 灵敏系数按最小运行方式下线路未端d2二相短路电流来校验 灵敏系数按变压器低压侧d4二相短路电流来校验
220kV低压10kV短路电流计算
0.159889559 0.383222222 1.079524228 5.419683508 16.25905052 41.46057884 16.25905052 3.48728879 2.361323385
2.015962204 10.12101149 1.541693831 15.60350098 39.7889275 11.00990353 2.361436364 1.598982833
6.211180124 15.59141964 6211.180124 15.59141964
39.75812008 6211.180124
2.609452015 13.10058977 2609.452015 13.10058977 33.40650391 2609.452015
0.472222222 1.218439044 66.9967724 1218.439044 66.9967724 170.8417696 1218.439044 0.343004096 18.86033404 3.601543012 18.86033404 48.0938518
0.167912041 0.161 2.041182734 5.123814786 15.37144436 39.19718312 15.37144436 2.240467746 1.889579983
0.243191696 4.1119825 10.3219748 1.500110402 15.48410176 39.4844595 7.579352745 1.104729976 0.931714216
(2).当110kV母线发生不对称短路时 I.单相接地故障 此情况的零序阻抗标幺值为Z0 正序阻抗可由三相短路计算可知Z1=Z2 Id(*) Id=Id(*)*Ij 短路点电流(3EA) 冲击值2.55* 中性点电流为3Id Id''为110kV侧中性点电流 Id'为220kV侧中性点电流 II.两相短路 同第一种情况完全相同
10KV继电保护整定计算
继电保护整定计算一、10KV 母线短路电抗已知10母线短路参数:最大运行方式时,短路容量为MVA S d 157)3((max)1.=,短路电流为KA U S I e d d 0647.91031573)3((max)1.)3((max)1.=⨯=⋅=,最小运行方式时,短路容量为MVA S d 134)3((min)1.=,短路电流为KA U S I e d d 7367.71031343)3((min)1.)3((min)1.=⨯=⋅=,则KA I I d d 77367.7866.0866.0)3((min)1.)2((min)1.=⨯==。
取全系统的基准功率为MVA S j 100=,10KV 基准电压KV U j 5.101.=,基准电流为KA U S I j jj 4986.55.10310031.1.=⨯=⋅=;380V 的基准电压KV U j 4.02.=,基准电流是KA U S I j jj 3418.1444.0310032.2.=⨯=⋅=二、1600KVA 动力变压器的整定计算(1#变压器, 2#变压器)已知动力变压器量MVA S e 6.1=,KV 4.010,高压侧额定电流A U S I He eH e 38.9210316003..=⨯=⋅=,低压侧额定电流 A U S I L e eL e 47.23094.0316003..=⨯=⋅=,变压器短路电压百分比%5.4%=s V ,电流CT 变比305150==l n ,低压零序电流CT 变比0n 。
变压器高压侧首端最小运行方式下两相断路电流为KA I d 38.6)2((min)2.=1、最小运行方式下低压侧两相短路时流过高压的短路电流折算到高压侧A I d 1300)`2((min)3.=2、最大运行方式下低压侧三相短路时流过高压的短路电流折算到高压侧A I d 1500)`3((max)3.=3、高压侧电流速断保护电流速断保护按躲过系统最大运行方式下变压器低压侧三相短路时,流过高压侧的短路电流来整定,保护动作电流 A n I K K I l d jxk j dz 6530150013.1)`3((max)3..=⨯⨯== 对应值75A 保护一次动作电流 KA K n I I jx l j dz dz 95.113065.=⨯== 电流速断保护的灵敏系数按系统最小运行方式下,保护装置安装处两相短路电流校验227.395.138.6)2((min)2.>===dz d lm I I K 电流速断保护动作时限取0秒。
10kv保护整定计算
金州公司窑尾电气室10kv 保护整定1. 原料立磨主电机(带水电阻)整定接线方式:A 、B 、C 三相式S=3800kWIn=266ANct=400/5保护型号:DM-100M 珠海万力达1.1保护功能配置?速断保护(定值分启动内,启动后)?堵转保护(电机启动后投入)?负序定时限电流保护?负序反时限电流保护零序电压闭锁零序电流保护?过负荷保护(跳闸\告警可选,启动后投入)?过热保护?低电压保护?过电压保护?工艺联跳(四路)?PT 断线监视1.2电流速断保护整定1.2.1高值动作电流:按躲过电机启动时流经本保护装置的最大电流整定:Idz'.bh=Krel ×Kk*In式中:Krel----可靠系数,取1.2~1.5Kk 取值3所以Idz'.bh=Krel ×Kk*In/80=1.2×3.5×266/80=13.97A延时时间:t=0s 作用于跳闸1.2.2低值动作电流Idz'.bh=Krel ×Kk*In/Nct=1.2×2*266/80=7.98A延时时间:t=0s 作用于跳闸1.3负序电流定时限负序保护Iop=2.4A延时时间:T=1s 作用于跳闸1.4负序电流反时限负序保护(暂不考虑)1.5电机启动时间T=12s1.6低电压保护U *op=Krel st.min *U Un=(0.5~0.6)Un 取0.6Un 故U *op=60V延时时间:t=0.5s 作用于跳闸1.7零序电压闭锁零序电流保护I0=10A/Noct=0.17A延时时间:t=0.5s 作用于跳闸1.8过电压保护Uop=k*Un=115V 作用于跳闸延时时间:t=0.5s1.9负序电压U2op=0.12In=12V1.10过负荷保护电流电流Idz'.bh=Krel ×In/Nct=1.1×266/80=3.63A 取3.63A延时时间:t=15s 作用于跳闸二、差动保护MMPR-320Hb电机二次额定电流Ie=264/80=3.3A1、 差动速断电流此定值是为躲过启动时的不平衡电流而设置的,为躲过启动最大不平衡电流,推荐整定值按下式计算: t s k dz I K I tan ⋅=,k K :可靠系数,取1.5t s I tan 为电流启动倍数取2In则:=⋅=⋅l t s k j dz n I K I tan 1.5*2*264/80=9.9A 作用于跳闸2、 比率差动电流考虑差动灵敏度及匝间短路,按以下公式整定dz I =0.5In/Nct=1.65A作用于跳闸3、 比率制动系数:一般整定为0.5。
地面10KV高压短路电流计算含计算公式
鲁班山北矿地面变电所10KV配电柜2016年1月整定计算表
电流 电
额定 电流 (A)
互器 一次 侧电 流
流 互 感 器
(A 变
变 压 器 变 比
保护 装置 的可 靠系 数
保护 装置 的接 线系 数
电流 继电 器的 返回 系数
最大负 荷电流
(A)
过流保 护整定
(A)
过流保护整定(A)
第 1 页,共 3 页
配电盘名称 613#井下动力一回
鲁班山北矿地面变电所10KV配电柜2016年1月整定计算表
电流 电
额定 电流 (A)
互器 一次 侧电 流
流 互 感 器
(A 变
变 压 器 变 比
保护 装置 的可 靠系 数
保护 装置 的接 线系 数
电流 继电 器的 返回 系数
最大负 荷电流
(A)
616#井下局扇
270 150 30
1.2 1 0.8 405.0 10.1 303.8 7 1.89 6.2 2.49 34.8 1044.6 1.89 1.81
617#抽风机一回 280 300 60
1.2 1 0.8 420.0 5.3 315.0 7 2.08 6.6 4.14 24.8 1489.1 2.08 1.39
G3#风井绞车
43.3 30 6
1.2 1 0.85 34.6 8.2 48.9 7 1.53 31.3 2.57 51.3 307.9 1.53 4.98
G4#压风机一回
28.9 30 6
1.2 1 0.85 23.1 5.4 32.6 5 1.53 47.0 2.57 51.3 307.9 1.53 4.98
10KV短路电流计算
0.12
0.35
0.40
0.90 0.90 0.95 0.95 0.96 0.96 1.03 1.03 1.02 1.02 1.00 1.00 1.05 1.05 1.03 1.03
系统 0.36 0.46 0.36 0.46 0.36 0.46 0.36 0.46 0.36 0.46 0.36 0.46 0.36
常用基准值
建业龙城短路电流计算
基准电流(Ij)
10KV
35KV
5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50 5.50
1.56
电缆每千米电抗 (X)
(Ω/km)
10KV
35KV
0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080
中 23区住宅
21.57 12.37 21.27 12.27 21.21 12.25 20.80 12.11 20.86 12.13 20.97 12.17 20.69 12.07 20.80 12.11
并列 分列 并列 分列 并列 分列 并列 分列 并列 分列 并列 分列 并列 分列 并列 分列
21区公司 21区公司 21区公共 21区公共 21区住宅 21区住宅 22区公共 22区公共 22区住宅 22区住宅 23区公司 23区公司 23区公共 23区公共 23区住宅 23区住宅
序号
1 2 3 4 5 6 7 8 9 10 11 12 13
14
15
16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
10KV系统短路电流整定计算表格
假定电网短路容量为300MVA,基准电压Uj=10KV,基准电流Ij=9.16KA,冲击系数Kch.s取1.8. 各元件有效电阻较小,短路电路中总电阻不大于总电抗的1/3,不予考虑. 10KV|---2.0Km 3X300电缆------10KV变配电所SS2 |F1--------2.5Km 3X185电缆--------F4|SS1 10/0.4KV变压器|F5 b |---SS2 10/0.4KV变压器|F2 |---- 0.8Km 3X70电缆----10KV电机|F6 b |----1.5Km 3X70电缆----10KV电机|F3 b |----------1.5Km 3X185电缆--------F7|SS3 10/0.4KV变压器|F8 b |----1.0Km 3X70电缆----10KV电机|F9
短路点F5 SS1变压器低压侧 7 短路点F6 8 短路点F7 SS3Байду номын сангаас10KV母线 9 SS1-10KV电机
短路点F8 SS3变压器低压侧 10 短路点F9
ich.s= I1= 1.414*Kch.s*I" I2/(1.732*nl)
1 2
电网 进线电缆
短路点F1 SS2 10KV母线 3 SS2变压器(基准电 压10KV)
短路点F2 SS2变压器低压侧 4 短路点F3 5 短路点F4 SS1 10KV母线 6 SS1变压器(基准电 压10KV) SS2-10KV电机
序号 电路元件 变压器/电网 电缆 容量SrT/Sks 长度 MVA Km 300 YJV-3X300 10 2 变压器 Uk% 阻抗 /Km X1*=Sj/Sks 0.079 X2*=L*X(Sj/Uj^2) Xjs1*=X1*+X2* 0.63 4.50% X3*=(Uk%/100)*(Sj/SrT)*(0.4 ^2/10^2) Xjs2*=X1*+X2*+X3* YJV-3X70 YJV-3X185 0.8 2.5 0.071 X4*=L*X(Sj/Uj^2) Xjs3*=X1*+X2*+X4* SS2-SS1电缆 0.063 X5*=L*X(Sj/Uj^2) Xjs4*=X1*+X2*+X5* 0.25 4.50% X6*=(Uk%/100)*(Sj/SrT)*(0.4^ 2/10^2) Xjs5*=X1*+X2*+X5*+X6* YJV-3X70 YJV-3X185 0.8 1.5 0.071 X7*=L*X(Sj/Uj^2) Xjs3*=X1*+X2*+X5*+X7* SS2-SS3电缆 SS3变压器(基准电 压10KV) SS3-10KV电机 400kw 10KV电机 0.063 X8*=L*X(Sj/Uj^2) Xjs3*=X1*+X2*+X8* 0.5 4.50% X9*=(Uk%/100)*(Sj/SrT)*(0.4 ^2/10^2) xjs4*=X1*+X2*+X8*+X9* YJV-3X70 0.8 0.071 X10*=L*X(Sj/Uj^2) Xjs3*=X1*+X2*+X8*+X10* 17% X"d*=Xd"(Sj/Sed) 计算公式 短路电路总电抗 超瞬变短路电流KA 短路容量MVA Xjs 短路元件电抗 I"s=I0.2=Ik= (标值) Ij/Xjs* 0.333 0.143 0.477 0.0114 0.345 0.052 0.528 0.143 0.620 0.0288 0.648 0.052 0.671 0.086 0.562 0.0144 0.577 0.052 0.614 0.037 14.922 162.90 37.98 15.882 173.38 40.42 0.367 16.289 177.82 41.46 13.651 149.03 34.74 14.129 154.25 35.96 0.326 14.786 161.42 37.63 17.343 189.34 44.14 26.569 290.06 67.62 0.614 19.218 209.80 48.91 Ss"= Sj/Xjs* 短路全电流KA 折算到高压侧的 短路电流(KA)
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
I1=
1.414*Kch.s*I" I2/(1.732*nl)
1
电网
2
进线电缆
短路点F1 SS2 10KV母线
300 YJV-3X300
10
X1*=Sj/Sks
2 0.079 X2*=L*X(Sj/Uj^2)
Xjs1*=X1*+X2*
0.333 0.143 0.477
19.218
209.80
48.91
10KV电网短路电流计算
假定电网短路容量为300MVA,基准电压Uj=10KV,基准电流Ij=9.16KA,冲击系数Kch.s取1.8. 各元件有效电阻较小,短路电路中总电阻不大于总电抗的1/3,不予考虑.
10KV|---2.0Km 3X300电缆------10KV变配电所SS2 |F1--------2.5Km 3X185电缆--------F4|SS1 10/0.4KV变压器|F5
0.0144
0.577 0.052 0.614 0.037
14.129 13.651 16.289
15.882 14.922
154.25 149.03 177.82
173.38 162.90
35.96 34.74 41.46
40.42 37.98
0.326 0.367
0.25
Xjs2*=X1*+X2*+X3*
0.8 0.071 X4*=L*X(Sj/Uj^2)
Xjs3*=X1*+X2*+X4*
2.5 0.063 X5*=L*X(Sj/Uj^2)
Xjs4*=X1*+X2*+X5*
4.50%
ห้องสมุดไป่ตู้
X6*=(Uk%/100)*(Sj/SrT)*(0.4^ 2/10^2)
0.345 0.052 0.528 0.143 0.620
0.0288
26.569 17.343 14.786
290.06 189.34 161.42
67.62 44.14 37.63
0.614
短路点F5 SS1变压器低压侧
7
SS1-10KV电机
YJV-3X70
短路点F6
8
SS2-SS3电缆
YJV-3X185
短路点F7 SS3 10KV母线
9
SS3变压器(基准电 压10KV)
序号 电路元件
变压器
变压器/电网 电缆 Uk%
容量SrT/Sks 长度
MVA
Km 阻抗
/Km
计算公式
短路电路总电抗 Xjs
超瞬变短路电流KA
短路容量MVA
短路元件电抗 I"s=I0.2=Ik= (标值) Ij/Xjs*
Ss"= Sj/Xjs*
短路全电流KA
折算到高压侧的 短路电流(KA)
ich.s=
Xjs3*=X1*+X2*+X8*
4.50%
X9*=(Uk%/100)*(Sj/SrT)*(0.4 ^2/10^2)
xjs4*=X1*+X2*+X8*+X9*
0.8 0.071 X10*=L*X(Sj/Uj^2) Xjs3*=X1*+X2*+X8*+X10*
17% X"d*=Xd"(Sj/Sed)
0.648 0.052 0.671 0.086 0.562
3
SS2变压器(基准电 压10KV)
0.63
4.50%
X3*=(Uk%/100)*(Sj/SrT)*(0.4 ^2/10^2)
0.0114
短路点F2 SS2变压器低压侧
4
SS2-10KV电机
短路点F3
5
SS2-SS1电缆
短路点F4 SS1 10KV母线
YJV-3X70 YJV-3X185
6
SS1变压器(基准电 压10KV)
0.5
短路点F8 SS3变压器低压侧
10 SS3-10KV电机
YJV-3X70
短路点F9
400kw 10KV电机
Xjs5*=X1*+X2*+X5*+X6* 0.8 0.071 X7*=L*X(Sj/Uj^2)
Xjs3*=X1*+X2*+X5*+X7* 1.5 0.063 X8*=L*X(Sj/Uj^2)
b
|---SS2 10/0.4KV变压器|F2
|---- 0.8Km 3X70电缆----10KV电机|F6
b
|----1.5Km 3X70电缆----10KV电机|F3
b
|----------1.5Km 3X185电缆--------F7|SS3 10/0.4KV变压器|F8
b
|----1.0Km 3X70电缆----10KV电机|F9