File E88991 Vol. 1 Sec. 23 Page 1 Issued: 2000-08-11 and Report Revised: 2005-07-07 DESCRIPTION

PRODUCT COVERED:

USR, CNR: Component - Magnetic Motor Controllers, Model 812 may be followed by B, may be followed by W, may be followed by E, H or HT, followed by 1A, 1B or 1C; followed by C, S, or V, may be followed by additional letters and/or numbers, may be followed by B or F, may be followed by 3-60 V dc. GENERAL:

The devices are open-type magnetically operated, single-pole,

single-throw or double-throw relays, with normally open and normally closed contacts with single stable, one coil latching.

ELECTRICAL RATINGS:

General Type (812):

15 A, 125 Vac, General Use

10 A, 277 Vac, General Use

5 A, 30 Vdc

TV-5, 120 Vac (N.O. Contacts)

*

File E88991 Vol. 1 Sec. 23 Page 1A Issued: 2000-08-11

and Report Revised: 2006-08-04 High Power Type (812H):

20 A, 125 V ac, Resistive (NO Contacts, UL1950 Applications Only)

20 A, 125 V ac, General Use (NC Contacts, UL1950 Applications Only)

15 A, 125 V ac, General Use

12 A, 277 V ac, General Use, 85,000 cycles (NO Contacts)

12 A, 277 V ac, General Use, 60,000 cycles (NC Contacts)

10 A, 277 V ac, General Use

10 A, 277 V ac, General Use, 100,000 cycles (NO Contacts)

10 A, 277 V ac, General Use, 70,000 cycles (NC Contacts)

7 A, 30 V dc

TV-8, 120 Vac, (NO Contacts)

½ HP, 125 Vac, (NO Contacts)

½ HP, 125 Vac, 15,000 cycles (NC Contacts)

1 HP, 250 Vac, (NO Contacts)

1 HP, 250 Vac, 20,000 cycles (NC Contacts)

812H Ambient: 40ºC maximum @ 20 A maximum (Class A, B or F insulation)

55ºC maximum @ 20 A maximum (Class B or F insulation)

85ºC maximum @ 10 A maximum (Class A, B or F insulation)

85ºC maximum @ 12 A maximum (Class B or F insulation)

85ºC maximum @ 15 A maximum (Class F insulation)

105ºC maximum @ 10 A maximum (Class B or F insulation)

105ºC maximum @ 12 A maximum (Class F insulation) High Power Type (812H) – Additional Ratings:

16 A, 277 V ac, General Use (NO Contacts, UL1950 Applications Only)

10 A, 30 VDC, NO

1/4 HP (5.8 FLA), 125 V ac, 30K cycles, NO

1/4 HP (5.8 FLA), 125 V ac, 15K cycles, NC

1/4 HP (2.4 FLA), 277 V ac, 30K cycles, NO/NC

1/6 hp (4.4 FLA), 125 V ac, 30 k (N.C)

5 FLA, 120 V ac, 100K cycles, NO/NC

1000 VA, 120 V ac, Ballast, NC

16.8 VA, 700 mA, 24 Vac, pilot duty, 100K cycles, NO/NC

C300 pilot duty, NO/NC

File E88991 Vol. 1 Sec. 23 Page 1B Issued: 2000-08-11 and Report Revised: 2005-07-07 ELECTRICAL RATINGS (CONT.):

High Power Type (812E):

20 A, 125 V ac, General Use (UL1950 Applications Only)

15 A, 125 V ac, General Use

12 A, 125 V ac, Resistive 70°C

10 A, 250 V ac, Resistive 85°C (50,000 cycles, No Contacts)

7 A, 250 V ac, Resistive 85°C (50,000 cycles, Nc Contacts)

12 A, 277 V ac, Resistive 85°C

7 A, 30 V dc, Resistive

10 A, 250 V ac, General Use 85°C (100,000 cycles, NO Contacts)

10 A, 125 V ac, General Use 85°C (100,000 cycles, NC Contacts)

NC 5A / NO 7A, 240 V ac, 105°C100K cycles.

NO = Normally Open.

NC = Normally Closed.

1/4 hp, 5.8 FLA, 125 V ac (NO Contacts)

1/4 hp, 2.9 FLA, 250 V ac (NC Contacts)

1/4 hp, 250 V ac 85°C (30,000 cycles, NO Contacts)

1/6 hp, 250 V ac 85°C (30,000 cycles, NC Contacts)

1/8 hp, 3.8 FLA, 125 V ac (NO Contacts)

1/8 hp, 1.9 FLA, 250 V ac (NO Contacts)

1/8 hp, 125 V ac 85°C (30,000 cycles, NO Contacts)

1/10 hp, 125 V ac 85°C (30,000 cycles, NC Contacts)

5.0 FLA, 120 V ac (100,000 cycles)

TV-5 (NO Contacts)

Pilot Duty, 24 V ac, 700 mA, 16.8 VA, 100 kc

C300 Pilot Duty

1000 VA, 120 V ac, AC Electric Discharge Lamp (Ballast), (NC contacts)

812E Ambient: 85ºC maximum @ 12 A maximum

105ºC maximum @ 5 A maximum (Class B or F insulation) *