广东某别墅中央空调系统设计论文
浅谈别墅中央空调系统的设计与应用
![浅谈别墅中央空调系统的设计与应用](https://img.taocdn.com/s3/m/15bc0a1502020740be1e9bb7.png)
浅谈别墅中央空调系统的设计与应用摘要:以特定业态—别墅为例,针对几种常见的中央空调设计方案,经过对其系统设置、工程造价及运行费用等方面比较,分析其优缺点,总结了在别墅中央空调系统设计时应考虑的问题。
关键字:中央空调;冷、热源;系统形式;优、缺点Abstract: in a specific format-villa as an example, this paper several common central air-conditioning design, through the system Settings, the project construction cost and operation cost, compares and analyzes their advantages and disadvantages, and summarizes the villa in the central air conditioning system design should be considered when the problem.Key words: the central air conditioning; Cold, heat source; The system form; Advantages and disadvantages中图分类号:TU831.3+5文献标识码:A文章编号:经济的快速腾飞发展,在提高人们的物质生活水平的同时,也在不断改善人们的住房条件。
大面积多居室的住宅拔地而起,别墅作为其奢侈品应运而生。
现今人们对居室装潢布置提出要求的同时,对居住环境的舒适性也提出了更高的要求,因此,现中央空调已成为别墅的必需品。
一、别墅中央空调的几种形式与应用分析别墅与一般住宅不同,针对整个别墅园区来说,具有入住率极低、同时使用系数极低的特点。
基于此特点并根据别墅所处位置的外界条件、工程初投资情况、建筑层高、业主要求等条件,大致可将别墅中央空调分为二大类:氟机与水机。
户式中央空调论文:风管式系统在别墅中应用中的几点心得
![户式中央空调论文:风管式系统在别墅中应用中的几点心得](https://img.taocdn.com/s3/m/64f7ac40312b3169a451a444.png)
户式中央空调论文:风管式系统在别墅中应用中的几点心得摘要:本文以风管式中央空调为分析对象,结合笔者几年的工作经验,提出了一些在设计及施工中应注意的问题。
关键词:户式中央空调风管系统气流组织引言: 近年来, 随着国民经济的发展,高档次住宅和别墅区越来越多,于是,户式中央空调系统便逐渐占据了别墅空调市场,常见的户式中央空调可以分成三种形式:风系统(以空气为输送介质)、水系统(以水为输送介质)、制冷剂系统(以制冷剂为输送介质)。
这里,笔者就风管系统在别墅工程中的应用总结几点心得体会。
一、风管式系统的简介风管式系统以空气为输送介质,其原理与大型全空气中央空调的原理基本相同,是一个小型的全空气中央空调系统。
它利用室外主机集中产生冷/热量,对室内回风进行冷却/加热处理,再送入室内,达到消除室内负荷的目的。
室外主机均采用水冷方式,也可采取风冷方式。
二、别墅中应用的几点心得1、机器的选型问题空调负荷计算为合理选择设备容量提供了依据,空调负荷计算包括夏季冷负荷计算,在方案设计阶段,一般采用负荷估算指标进行负荷计算。
值得提出的是,由于采用的是户式风管式中央空调系统,故估算的负荷值应包含新风负荷。
机组选型:户式风管式中央空调单机容量一般在9kw~35kw左右。
故机组的选型的合理性就相当重要,一般来讲300-500平米左右的别墅地下室和一层多为公共区,二层、三层多为休息区。
因此,一般建议公共区和卧室等休息区分开配置,这样有利于节省能耗。
2、新风问题大多数户式中央空调设计,新风量不足,有的甚至没有新风。
造成此原因大致因为:(1)由于系统形式限制(主要指水系统及多联机系统),不愿增加新风机组,以降低初投资;(2)受传统思想的影响,没有意识到新风系统对提高室内空气品质的重要性。
而风管系统集中对空气进行处理,因此较易引入新风。
新风可单独处理后送入空调房间,也可送入空调箱尾部,与回风混合后统一进行处理。
此外在非空调季节,还可通过新风系统进行通风换气,有效地提高了室内舒适度。
某别墅地源热泵空调系统毕业设计(论文)
![某别墅地源热泵空调系统毕业设计(论文)](https://img.taocdn.com/s3/m/9818902a7375a417866f8f30.png)
江苏科技大学本科毕业设计(论文)二零一二年六月江苏科技大学本科毕业论文香格里拉一别墅地源热泵空调系统设计Shangri-La villa ground -source heat pump air conditioning systemdesign摘要地源热泵是一种利用浅层和深层的大地能量,包括土壤、地下水、地表水等天然能源作为冬季热源和夏季冷源,然后再由热泵机组向建筑物供冷供热的系统,是一种利用可再生能源的既可供暖又可制冷的新型中央空调系统。
地源热泵通过输入少量的高品位能源(如电能),实现由低温位热能向高温位热能转移。
通常地源热泵消耗1kw的能量,用户可以得到4kw以上的热量或冷量。
本课题主要是研究地源热泵空调系统对南京某别墅夏季制冷,冬季供热的设计方案。
本方案地下换热器埋管方式采用垂直U型埋管,解决了传统空调运行效率低、耗电量大、运行费用高、噪音大、维护费用高及会产生霉菌污染、使用寿命短等缺点。
真正做到了高效、节能、环保、舒适的要求。
关键词:地源热泵;空调系统;垂直埋管AbstractGround source heat pump is a kind of shallow and deep earth energy, including soil, groundwater, surface water and other natural energy sources as the winter heat and summer cooling source, and then by the heat pump unit to the building cooling and heating system is akinds of renewable energy both heating but also cooling the new central air conditioning system. Ground -source heat pump heat transfer by entering the small number of high-grade energy (eg electricity), to achieve by the low level heat energy to the high-temperature bit. Usually ground source heat pumps consume 1kw of energy, the user can get more than 4kw heat or cold.The main topic is the design of the study of ground source heat pump system to Nanjing for a villa in summer cooling and winter heating. This program the ground heat exchanger pipe way vertical U-shaped pipe to solve the low operating efficiency of conventional air conditioning, power consumption, high operating costs, noise, maintenance costs and will have mold contamination, short life shortcomings. It can achieve efficient, energy saving, environmental protection, comfort requirements.Keywords:Ground source heat pump; air-conditioning systems; vertical pipe目录第一章绪论 (1)1.1研究背景 (1)1.2地源热泵发展简史 (2)1.2.1国外地源热泵发展 (2)1.2.2国内地源热泵发展 (3)1.3地源热泵的发展趋势 (4)1.4地源热泵的优点 (5)第二章空调系统设计依据 (7)2.1室外气象参数 (7)2.2 室内设计参数确定 (7)2.3 设计范围 (7)2.4 设计原则 (8)第三章负荷计算 (9)3.1 冷负荷计算 (9)3.1.1 外墙和屋面瞬变传热引起的冷负荷 (9)3.1.2 内围护结构冷负荷 (9)3.1.3 外玻璃窗逐时传热形成的冷负荷 (10)3.1.4透过玻璃窗的日射得热形成的冷负荷 (10)3.1.5 设备散热形式的冷负荷 (10)3.1.6 照明散热形式的冷负荷 (10)3.1.7 人体散热形成的冷负荷 (11)3.2 人体散湿负荷 (11)3.3工程负荷统计 (12)第四章末端设备选型 (13)4.1风机盘管的选型 (13)第五章空调水系统水力计算 (14)5.1.1 空调水系统的设计原则 (14)5.1.2 空调供回水管的水力计算 (14)5.2 空调水系统的水力计算 (14)5.3 空调立管的水力计算 (19)5.3.1 计算依据 (19)5.3.2 计算公式 (19)5.3.3 计算结果(回水管同程系统) (19)5.4 冷凝水管道设计 (19)5.4.1 设计原则 (19)5.4.2 管径确定 (20)5.5 水系统安装要求 (20)第六章空调风系统设计 (22)6.1 风系统设计的一般原则 (22)6.2 新风机组的确定 (22)6.3 风口 (23)第七章地源热泵机组选择计算 (24)7.1 地源热泵机组选型计算 (24)7.2空调循环水泵设计计算 (24)7.2.1 水泵流量的确定 (24)7.2.2 水泵扬程的确定 (25)第八章地下埋管的设计与计算 (26)8.1 冬夏季地下换热量的确定 (26)8.2 确定地下换热器的埋管形式 (26)8.3 确定管路连接方式 (27)8.4 地下换热器埋管管材及管径的确定 (27)8.4.1 埋管管材的确定 (27)8.4.2 确定管径 (28)8.5 竖井埋管管长的确定 (28)8.6.1竖井数目的确定 (28)8.6.2 竖井间距的确定 (29)8.7 地下换热器系统的水利计算 (29)8.8地下换热器循环水泵的选型 (30)8.8.1 循环水泵的确定 (30)8.8.2 水泵配管布置 (31)8.9 阀门安装 (31)结论(或结语) (32)致谢 (33)参考文献 (34)第一章绪论1.1研究背景地热是一种可再生的自然能源。
中央空调毕业论文
![中央空调毕业论文](https://img.taocdn.com/s3/m/19b1456eb5daa58da0116c175f0e7cd184251882.png)
中央空调毕业论文中央空调毕业论文随着现代社会的发展,中央空调系统的应用越来越广泛,成为建筑物中不可或缺的一部分。
中央空调系统不仅能够为人们提供舒适的室内环境,还能有效地调节空气湿度和温度,提高室内空气质量。
因此,中央空调系统的设计、安装和维护成为了一个重要的研究领域。
首先,中央空调系统的设计是非常重要的。
一个合理的设计可以确保系统的高效运行和节能减排。
设计师需要考虑到建筑物的结构、使用需求和环境因素等多个方面。
例如,在设计过程中,需要根据建筑物的朝向和周围环境确定合适的冷热负荷,以确保系统的运行效果。
此外,设计师还需要选择合适的设备和材料,以提高系统的性能和可靠性。
其次,中央空调系统的安装也是至关重要的。
一个正确的安装可以确保系统的正常运行和长期稳定性。
在安装过程中,工程师需要遵循相关的安装规范和标准,确保设备的正确连接和定位。
此外,他们还需要进行系统的调试和测试,以确保系统的运行效果和安全性。
一个良好的安装工作可以有效地减少系统的故障率和维修成本。
最后,中央空调系统的维护和保养也是不可忽视的。
一个定期的维护计划可以延长系统的寿命和提高其性能。
维护工作包括清洁过滤器、检查管道和阀门、调整控制参数等。
此外,还需要定期检查系统的运行状态和性能,及时发现和解决问题。
一个良好的维护工作可以保证系统的正常运行,并减少能源消耗和维修费用。
总之,中央空调系统的设计、安装和维护是一个综合性的工作,需要多方面的知识和技能。
设计师、工程师和维护人员需要密切合作,共同努力,以确保系统的高效运行和用户的满意度。
中央空调系统的研究和发展还有很大的潜力,未来的研究可以从系统的智能化、能源节约和环境保护等方面展开,以进一步提高系统的性能和可靠性。
通过对中央空调系统的研究和论述,我深刻认识到了中央空调系统在现代社会中的重要性和应用价值。
在未来的工作中,我将继续深化对中央空调系统的研究,并努力为中央空调系统的设计、安装和维护提供更好的解决方案。
开题报告---某酒店中央空调系统设计
![开题报告---某酒店中央空调系统设计](https://img.taocdn.com/s3/m/99c40140aeaad1f346933fc0.png)
开题报告---某酒店中央空调系统设计毕业设计(论文)开题报告题目名称:广州某酒店中央空调系统设计学院名称:能源与环境学院班级:热动092学号: ************学生姓名:**指导教师:白静张超2013年3月能源与环境学院制一、文献综述(课题来源及目的、工程概况、国内外设计方法现状及趋势,要求详细列出参考文献)1.课程来源及目的:本课题题目为广州某酒店中央空调系统设计。
这次毕业设计的目的是完成酒店中央空调系统负荷的设计计算;分析并确定空调系统设计方案和主要设备(冷热源及末端设备)的选型;完成管路系统(风系统、水系统)的水力计算等;完成空调系统冷冻站的设计;完成规定要求的不少于八张工程图纸设计任务;书写设计及施工说明书。
将大学四年学习的专业知识系统的串联起来,形成完整的体系。
2.工程概况:该酒店是一所餐饮、住宿、娱乐、办公等多项功能为一体的综合性大楼,位于广东省广州市。
该工程共计十层总建筑面积约9000㎡,其中,一至三层每层高4.5m,四至十层每层高3.3m,总建筑高度102.6m。
3.国内外设计方法现状及趋势:目前国内外常用的中央空调系统的设计方式有很多,其中,传统的中央空调系统有:全空气系统,风机盘管+新风系统;而新型的中央空调系统有:辐射吊顶+独立新风机组,独立新风系统。
四种中央空调系统的特点与优劣:全空气系统:全空气系统是指室内负荷全部由经过处理的空气来负担的空调系统。
此种系统所需空气量多,因而风道断面尺寸较大。
集中式空调系统一般属于此类系统。
优点是有专门的过滤段,有较强的空气除湿能力和空气过滤能力;送风量大,换气充分,空气污染小;在春秋过渡季节可实现全新风运行,节约运行能耗;空调机置于机房内,运转、维修容易,能进行完全的空气过滤;产生震动、噪声传播的问题较少。
缺点是占用机房。
风机盘管+新风系统:风机盘管加新风空调系统是空气一水空调系统中的一种主要形式,也是我国民用建筑中采用最为普通的一种空调形式。
某别墅中央空调与供热系统设计的论文
![某别墅中央空调与供热系统设计的论文](https://img.taocdn.com/s3/m/7fae64100912a216147929fd.png)
某别墅中央空调与供热系统设计的论文摘要:本文介绍了该工程的空调与热水系统的设计。
以节能、舒适的角度出发,概要阐述了空气源热回收空调热水机组在别墅中的节能应用,以及增加新风换气系统所提高舒适度的作用。
关键词:空调;热水;新风换气;系统设置;舒适节能1工程概述位于鹤山市龙口镇的某小型别墅,总建筑面积约410㎡,空调面积169㎡,总层数为4层,其中-1层为车库和杂物间,建筑总高度,别墅周围设有面积约200㎡的中式花园。
别墅的空调和热水系统为集中式供冷和供热方式进行,机组则采用了由本公司自行设计装配的空气源热回收空调热水机组,制冷量为19kw,制热量为21kw。
末端设备则选用约克牌ygfc系列的多个型号风机盘管机组,新风排气设备均选用松下的高效节能产品,自控设备选用森威尔数码三速温控开关以及二、三通电磁阀。
该建筑物为现代化小型中档别墅,对空调的温度、舒适度、噪音以及送、回风格栅的选型、布置与室内装饰效果的密切配合均有很高的要求。
同时,考虑对系统的自控、调节、节能、管理、投资和少占空间等因素,所以,本工程的供冷、供暖系统参照了常规水系统中央空调的方式设计,而热水系统则釆用常压循环加热集中供应。
2设计参数室外设计参数室外计算参数参见广东地区气象参数,并对计算结果附加安全裕度,消除其不保证日。
室内设计参数空调冷负荷指标热水设计负荷根据业主所提供的要求和在冬季最大热水用量的估算,冬季每天平均热水用量为300l,所制备的热水温度为55℃,则冬季的热水热负荷约为14kw。
3空调设备的选型由于住宅空调的满负荷运行微乎其微,本系统的设计则结合用户对空调使用的要求和供电容量的实际情况,将首层的客厅等区域与卧室进行错锋运行,在满足两部份空调区域负荷的情况下,同时减少了46%的装机容量。
空调设备选型4系统设计(1)各个空调区域均采用卧式暗装风机盘管方式,风机盘管按照室内装饰要求安装在各厅房适合的天花扳上,同时根据天花的装饰效果设置条型送风口、铰式回风百叶等。
毕业设计--广州某酒店中央空调系统设计
![毕业设计--广州某酒店中央空调系统设计](https://img.taocdn.com/s3/m/ae5f2e1576c66137ee0619c3.png)
广州某酒店中央空调系统设计1 前言近年来,随着人民生活水平、生活质量的逐步提高,人们对空调的舒适性及空气品质的要求越来越高。
我国涉外宾馆,酒店和康乐中心建设速度较快,规模也较大。
这类新建的酒店建筑是我国民用建筑中最先进入现代化水准的建筑。
投资商建立这些场所的初衷是应市场需要给人们一个高档次的能休息和放松身心及缓解压力和疲劳的地方,同时从中得到良好的经济效益。
为了向顾客提供更优质的服务以在市场竞争中立足,他们不得不增加包括能源消耗在内的各项投资成本,因此,这些场所自然就成了能耗大户。
如今节能、环保成为当今空调系统设计的主题。
同时,经济的高速发展也是以牺牲环境为代价的,如今人们赖以生存的环境已不堪重负。
为此,国家确立了“节约与开发并重,节约优先”的能源方针,并提出“科学发展观”,“构建社会主义和谐社会”的全新发展理念。
因此,节能降耗理应成为全社会共同的责任,更是摆在每一家空调制造企业面前重大的课题。
节能空调设计是酒店建筑节能的重要环节,环保空调系统设计是社会发展的趋势。
本文通过就酒店的空调设计,利用对空调机组的有效热源进行热回收设计,从而达到节能环保的理念。
酒店建筑的内外装饰华丽多彩,使用功能齐全,一般都装有全年性舒适空调,因此搞好此类建筑物的空调设计,保证各空调房间内的温度、湿度、新风量、风速、噪音和含尘浓度等6项涉及到热舒适标准和卫生要求的舒适性空调室内设计参数、是空调设计者的主要任务。
如设计计算失误将给酒店造成不可预料的损失,招致此类建筑达不到预定的等级,影响声誉并直接关系到客源和经营效益。
可见搞好酒店建筑空调设计的重要性不言自明。
在国内外,一般的热回收机组仅能在机组制冷时提供生活用热水,而到了冬季,用户仍需要其它加热方式来提供生活用热水。
热回收技术就是通过一定的方式将冷水机组运行过程中排向外界的大量废热回收再利用,作为用户的最终热源或初级热源。
通过热回收技术的应用,一方面减少了冷水机组运行过程中排放的大量余热,降低了对环境的废热污染,另一方面,由于制取免费的卫生热水,降低了对锅炉、电加热器等传统加热设备的过度依赖,同时,对液态制冷剂的进一步过冷作用,提高了冷水机组的能效比,改善了机组的运行条件,并提高了机组的运行寿命,整体上降低了企业的综合运营成本。
中央空调系统设计毕业论文
![中央空调系统设计毕业论文](https://img.taocdn.com/s3/m/8bea5be8a76e58fafbb0030d.png)
中央空调系统设计毕业论文第一章设计参考规与标准6一、通用设计规:6二、专用设计规:6三、专用设计标准图集:7第二章设计参数7一、商业和公共建筑物的空调设计参数 ASHRAE7二、舒适空调之室设计参数日本8三、新风量81、每人的新风标准ASHRAE82、最小新风量和推荐新风量UK93、各类建筑物的换气次数 UK94、各场所每小时换气次数104、每人的新风标准UK115、考虑节能的基本新风量(1/s人)(日本)116、办公室环境卫生标准日本117、民用建筑最小新风量12第三章空调负荷计算13一、不同窗面积下,冷负荷之分布%13二、负荷指标(估算)(仅供参考)13三、空调冷负荷法估算冷指标。
空调冷负荷法估算冷指标(W/m2空调面积)见下表14四、按建筑面积冷指标进行估算建筑面积冷指标15五、建筑物冷负荷概算指标XX16六、各类建筑物锅炉负荷估算W/m3℃17七、热损失概算W/m℃17八、冷库冷负荷概算指标18第四章风管系统设计18一、通风管道流量阻力表181、缩伸软管摩擦阻力表182、镀锌板风管摩擦阻力表18二、室送回风口尺寸表211、风口风量冷量对应表212、不同送风方式的风量指标和室平均流速ASHRAE22三、室风管风速选择表221、低速风管系统的推荐和最大流速m/s222、低速风管系统的最大允许速m/s233、通风系统之流速m/s23四、室风口风速选择表241、送风口风速242、以噪音标准控制的允许送风流速m/s243、推荐的送风口流速m/s244、送风口之最大允许流速m/s255、回风口风速256、回风格栅的推荐流速m/s257、百叶窗的推荐流速m/s258、逗留区流速与人体感觉的关系269、顶棚散流器送风量2610、侧送风口送风量26五、室风口的简单布置281、送风口布置间距282、标准型号风盘所接散流器的尺寸表-办公室283、散流器布置294、空调房间允许最大送风温差℃295、工艺性空气调节空调房间允许最大送风温差.306.1、厨房通风问题306.2如何确定厨房的通风量306.3厨房通风设计中的几个问题327、消声器、静压箱总结348.风管贴吸音材料风道的衰减量(日本)359.风管的自然衰减量(只有直风道dB/m,其它都是dB)35六、防排烟设计36第五章管道系统设计39一、空调管路系统的设计原则39二、管路系统的管材39三、供回水总管上的旁通阀与压差旁通阀的选择40四、空调水系统管径的确定41五、冷冻水泵扬程估算方法431、水泵扬程简易估算法432、冷冻水泵扬程实用估算方法443、水泵扬程设计45六、冷却水系统的设计451、冷却水系统的补水量462、冷却水循环系统设计中应注意的几个问题:46七、冷凝水管道设计47八、分汽缸、分水器、集水器尺寸的确定47九、膨胀水箱的容积计算50十、空压管道管径选择表52十一、空调水处理系统55十二、保温55十三、阀门选用56第六章空调设备选型57一、机组选型57二、机组选型案例57三、辅助设备581、冷却塔582、水泵的选型:593、热泵中央空调系统水量计算604、冷冻水和冷却水流量估算605、设备水压力降估算(日本)616、制冷机冷却水量估算表61第七章自控系统设计61第八章材料、设备资料61一、钢板和铝板的厚度和重量ASHRAE61二、角钢和角铝的规格和重量ASHRAE62三、计算单位换算62四、常用液体的密度(单位:103千克/米3,未注明者为常温下)64五、空气调节常用计算公式65六、钢材理论重量计算67七、专业英语68第九章耗电量、机房面积801、水源热泵系统设备耗电量比例802、医院耗电量比例 TRANE803、各种系统分项造价占总造价的百分率%(近似)804、冷水机组和附属设备估算(△t=5℃)805、空调面积占建筑面积比例816、空调机房建筑面积概算指标817、空调设备所占的建筑面积百分率%828、设备层布置原则:82第十章参考实例83第十一章暖通空调中存在的问题与解决方法、图纸要求83一、贯彻执行暖通设计规、标准方面存在的问题831.1 室外空气计算参数不符合规要求831.2 供暖热负荷计算有漏项和错项831.3 卫生间散热器型式选择不妥831.4 楼梯间散热器立、支管未单独配置841.5 供暖管道敷设坡度不符合规要求841.6 厨房操作间通风存在问题841.7 膨胀水箱与热(冷)水系统的连接不符合规要求841.8 通风空调系统防火阀的设置不符合规要求841.9 防烟楼梯间前室送风口风量的确定有问题841.10 误将防烟分区排风量的计算混同于排烟风机风量的计算841.11 高层建筑排烟系统排烟口选型不当85二、在工程设计中存在的问题852.1 供暖入口设置过多852.2 供暖系统设计不合理852.3 排风系统设计不合理852.4 空调系统的选择不合理862.5 厕所采用风机盘管时未加新风862.6 平衡阀的设置与口径选择存在问题862.7 系统分区不当造成失败862.8、双风机系统设计问题872.9 送回风管布置不好873.0 排气系统设计诸问题88三、设计图纸方面存在的问题903.1 设计说明容不完整903.2 平面图深度不够,有些应该绘制的容遗漏903.3 系统图深度不够903.4 锅炉房设计过于简化903.5 计算书容不全甚至全部空白913.6 暖通空调设备未编号列表表示,图画繁杂不清913.7 平面图、剖面图、系统图不一致913.8 设计图纸与计算书不一致91四、问题原因与克服方法91五、施工图设计深度要求91设计说明、施工说明、图例和设备表91设备平面图92剖面图92通风、空调、制冷机房平面图92通风、空调、制冷机房剖面图92暖通设计中的系统图、立管图92详图93计算书(供部使用,备查)93第一章设计参考规与标准中央空调主要参考以下的规与标准:一、通用设计规:1.《采暧通风与空气调节设计规》( GBJI19-87)2.《采暖通风与至气调节制图标准》(GBJ114-88)3.《建筑设计防火现》(GBJ116-87)4、《高层民用建筑设计防火现他》( GBJ0045-95)5.《民用建筑节能设计标准(采暖居住建筑部分)》(JGJ26-95)二、专用设计规:1、《宿舍建筑设计规》(JGJ36-87)2、《住宅设计规》(GB50096-99)3.《办公建筑设计规》(JG67-89)4、〈旅馆建筑设计规〉(JGJ67-89)5.《旅游旅馆建筑热土与空气调节节能设计标准》(GB50189-93)6、其它专用设计规三、专用设计标准图集:1.《暖通空调标准图集》2.《暖通空调设计选用手册》(上、下册)3、其它有关标准第二章设计参数一、商业和公共建筑物的空调设计参数 ASHRAE二、舒适空调之室设计参数日本三、新风量1、每人的新风标准ASHRAE2、最小新风量和推荐新风量UK3、各类建筑物的换气次数 UK4、各场所每小时换气次数依人数计算换气量4、每人的新风标准UK5、考虑节能的基本新风量(1/s人)(日本)6、办公室环境卫生标准日本7、民用建筑最小新风量《空调通风工程系统运行管理规》(征求意见稿):空调通风系统运行期间,新风量宜满足下表的规定值,或者满足空气调节房间二氧化碳浓度小于0.1%。
毕业设计-某别墅空调工程设计
![毕业设计-某别墅空调工程设计](https://img.taocdn.com/s3/m/b4feaa43cf84b9d528ea7aeb.png)
河南科技大学毕业设计(论文)题目_别墅空调工程设计_姓名吕小龙院系车辆与动力工程专业热能与动力工程指导教师_王志远_2011年5月30日别墅空调工程设计摘要空气调节是对某一房间或空间的温度、湿度、洁净度和空气流动速度等进行调节与控制,并提供足够量的新鲜空气。
空调可以实现对建筑热湿环境、空气品质的全面控制,目前正被广泛地应用于现代建筑当中。
本设计为别墅的空调工程设计,地点为陕西省西安市,建筑面积为480㎡,空调总面积为441㎡,要求冬天能够供热,夏天能够供冷。
该别墅共三层,空调总面积不大,各房间面积相对较小、且有独立控制要求;空调使用时间分散,且各功能间负荷不会同时达到最大;综合考虑建筑物的特点、对舒适性的要求及经济性等因素,选用数码涡旋多联机系统,并对各层房间进行分区,这样既能满足别墅不同时刻不同负荷的要求,而且达到了节能的目的,同时运行管理方便,调节灵活。
设计中首先对各房间进行冷热湿负荷计算,再进行冬夏季送风参数计算;经比较采用一次回风系统,并为舒适度要求高的房间用室内机吸入新风。
采用R410a环保冷媒,选用“美的”D4机型。
针对不同功能房间室内装修特点,及有无新风要求,选用不同形式的室内机,并按配置率80%~130%选择室外机。
根据空调设备生产厂家的施工要求,布置室内外机位置、凝水管、风管及风口。
关键词:别墅空调系统,数码涡旋多联机,VRV, 自吸新风THE DESIGN OF AIR-CONDITION SYSTEMFOR COTTAGEABSTRACTAir-conditioning is control and regulation for temperature, moisture cleanliness and air velocity etc. of one room or space and provide enough fresh air in addition.Air-conditioning can realize the comprehensive control for building thermal or humid environment. So it's being applied extensively in modern buildings.This design is the cottage air-conditioning engineering design. It's located in Xi'an. The total construction areas is 480㎡and air conditioning areas is 441㎡. It's required that refrigerating can be realized in sunmer and heating in winter. There are 3 storys in all. The total air conditioning area is not big,besides, the area of each room is small relatively and controlling independently is demanded. At the same time, the using time of air conditioning system is so decentralized that load of each room will not reach the maximum in the meantime. Given these above reasons,and taking the building's feature and economy into the account ,I adopt the DVM system. In this design, I devide the rooms of each floor into different zones so that it can not only satisfied the load need of different times,but also realize the energy conservation.Moreover it is easy to management and flexible to controlling.In the design of each room,I first calculate the cold, hot and wet load, again carries on the winter and summer air distribution parameter calculation; By comparison, using a return air system of the high demand for comfort with indoor air inhaled room. Adopt R410a environmental refrigerant, choose "Midea" the D4 models. According to different function room interior decoration features, and presence of fresh air requirements, choose different forms of indoor parts,and press select PeiZhiLv 80% ~ 130% outdoor air-conditioners. According to the air conditioning equipment manufacturer's construction requirements, decorate indoor and outdoor machine position, coagulation plumbing, duct and draught.KEY WORDS:Villa air conditioning system, digital scroll VRF, VRV, self-priming fresh air目录前言 (1)第1章工程概况 (2)§1.1 建筑概况 (2)§1.2 气象参数 (2)§1.3 设计参数 (2)第2章负荷的计算 (7)§2.1 夏季冷负荷的计算 (7)§2.2 冬季热负荷的计算 (14)§2.3 湿负荷的计算 (16)第3章空调方案的确定 (17)§3.1 系统形式的确定 (17)§3.2 户式中央空调的形式和特点 (18)§3.3 变频技术和数码涡旋技术的比较 (23)§3.4 空调风系统 (28)第4章送风状态参数及送风形式的确定 (31)§4.1 新风量的确定 (31)§4.2 新风负荷 (32)§4.3 一次回风系统 (33)§4.4 新风引入方式 (35)第5章空调设备的选择 (37)§5.1 室内机选型 (37)§5.2 室外机选型 (38)§5.3 其他设备选型 (39)总结 (41)参考文献 (42)致谢 (43)附录 (44)前言自19世纪空调问世以来,空调技术随着经济的发展获得了飞速的提高,现在空调已成为现代建筑中不可缺少的设施之一。
中央空调系统毕业设计
![中央空调系统毕业设计](https://img.taocdn.com/s3/m/47582e93294ac850ad02de80d4d8d15abe230080.png)
中央空调系统毕业设计中央空调系统是现代建筑物中不可或缺的设备之一,它可以有效地调节室内温度、湿度和空气质量,提供舒适的室内环境。
在本次毕业设计中,我们将研究并设计一套中央空调系统。
一、设计要求本中央空调系统设计要求能够适应客户的需求,具有以下特点:1、可变制冷量。
系统需要能够根据实际需求自动调节制冷量,以便节省能源和成本。
2、高效节能。
系统需要能够高效地工作,以降低能源消耗和维护成本。
3、稳定可靠。
中央空调系统需要能够稳定可靠地运行,以确保用户能够长期享受高质量的室内空气。
4、易于维护。
系统需要能够易于维护,以帮助减少维护成本和延长设备使用寿命。
二、系统结构设计中央空调系统通常由制冷机组、管道系统、风机盘管、空气处理器、控制系统等组成。
下面我们将对各个部分的设计进行详细的介绍。
1、制冷机组制冷机组是中央空调系统的核心部分,它提供制冷能力。
在本次设计中,我们将采用螺杆式压缩机和冷却塔组成的制冷机组。
螺杆式压缩机是一种高效、节能、低噪音的压缩机,适用于中大型中央空调系统。
冷却塔是用于散热的设备,可将制冷机组排出的热气散发到空气中,确保系统运行稳定。
2、管道系统管道系统是中央空调系统的输送管道,用于将制冷剂和空气输送到各个需要的地方。
在设计中,我们将采用优质的钢管和镀锌铁管,以确保系统的耐用性和稳定性。
3、风机盘管风机盘管是一个结合了换热器和风机的设备,用于加热或制冷室内空气。
在设计中,我们将采用高效的风机及风机盘管,可自动调节风量和温度,以确保室内空气质量。
4、空气处理器空气处理器是用于处理室内空气的设备,可帮助去除空气中的灰尘、细菌等有害物质。
在设计中,我们将采用高效的过滤器和新风设备,确保清新室内空气质量。
5、控制系统控制系统是中央空调系统的管控系统,用于监测和控制整个系统的运行情况。
在设计中,我们将采用PLC控制系统,结合人机交互面板,实现系统自动化管理。
三、总结设计一套高效、稳定、易维护的中央空调系统是需要综合考虑各个方面因素的。
小型别墅中央空调系统毕业设计
![小型别墅中央空调系统毕业设计](https://img.taocdn.com/s3/m/2b5a92126c175f0e7cd137df.png)
第1章绪论中国的建筑行业正处于飞速发展的阶段,人们对生活环境的要求也越来越高,而生活环境最主要的就是居住环境,这种需求带动了中国的空调制冷业的发展。
从发展趋势上看小型中央空调将成为住宅、办公室空调的主流产品。
因此中国市场发展前景非常诱人。
1.1 家用小型中央空调的发展现状一个国家家用空调的发展是与该国的地理气候条件、经济发展水平、人民生活水准、居住住宅形式以及社会人文环境等因素密切相关的,脱离了这些因素来谈家用空调的发展是不现实的。
同样,分析家用小型中央空调的发展也离不开这些因素。
一般而言,常见的住宅可以分为公寓型住宅和别墅型住宅。
以下将分别结合这两种典型住宅的特点,结合各个国家的不同特点,对外国和中国的家用小型中央空调的发展现状进行分析。
1.2 外国家用小型中央空调发展现状美国的家用小型中央空调普及率较高,这与其良好的居住条件以及较高的生活水平是分不开的。
美国是世界第一经济大国,人民生活水准较高,对居住的舒适性要求也较高,这些都促进了该国家用小型中央空调的普及使用。
美国的别墅型住宅具有宽敞、高大的特点,通常由中、高收入的家庭居住。
由于其层高较大,具有足够的建筑空间用于布置风道,因此在美国,风管式系统在家用小型中央空调中所占的比重相当大。
同时,由于美国居民对家用空调舒适性的要求较高,因此多采用有新风的风管式系统。
目前,美国风管式系统的年产量约为600万台/年,占其家用空调产量的一半左右。
美国的公寓型住宅适合于中、低收入的人群居住,其消费水平偏低,其家用空调的型式以窗式空调器为主,也有采用小区供冷/热水的,一般不使用家用小型中央空调。
目前美国窗式空调器年产量约为600万台/年,占其家用空调产量的一半左右。
日本的家用空调走的是一条"氟系统"为主的发展道路,从窗式空调器到定速分体式空调器,再到变频分体式空调器。
同样,日本的家用小型中央空调也以冷剂式空调即VRV(Varied Refrigerant Volume)系统(包括一拖多)为主。
广东某别墅中央空调系统设计毕业论文
![广东某别墅中央空调系统设计毕业论文](https://img.taocdn.com/s3/m/1452c3adda38376baf1fae96.png)
某别墅中央空调系统设计毕业论文目录1工程概况 (1)1.1 所选建筑物 (1)1.2 地理参数 (1)2设计参数及参照标准 (2)2.1室外参数 (2)2.2室温湿度要求 (2)2.3参照标准 (2)3负荷计算 (3)3.1 空调负荷的概念及组成 (3)3.2 各房间负荷、总负荷 (5)3.2.1 外墙和屋面瞬变传热引起的冷负荷 (5)3.2.2 墙,楼板等室传热维护结构形成的瞬时冷负荷 (5)3.2.3 外玻璃窗瞬变传热引起的冷负荷 (6)3.2.4 透过玻璃窗的日射得热引起的冷负荷 (6)3.2.5 人体散热形成的冷负荷 (6)3.2.6 门引起的冷负荷 (7)3.2.7 照明、设备散热形成的冷负荷 (7)3.3相关参数的选取 (7)3.4 负荷计算总结 (8)4风机盘管与外机机组选型 (23)4.1大金家用VRV的优点及优势 (23)4.1.1大金家用VRV系统的优点 (23)4.1.2大金家用中央空调优势 (23)4.2风机盘管选型 (24)4.2.1风机盘管型号及各参数 (24)4.2.2各房间风机盘管选型 (26)4.3 外机机组选型 (26)4.3.1 计算总负荷数值 (26)4.3.2 外机机组型号及各参数值 (26)4.3.3 外机机组选型 (27)5各楼层平面设计图 (28)5.1 楼层平面图 (28)5.2 智能感知3D气流风管式风机及冷煤管道、冷凝水管道布置 (31)结论 (34)谢辞 (35)参考文献 (36)附录 (37)1工程概况1.1 所选建筑物某别墅;本建筑是一座家用别墅,所在地省市,房间总面积约300平方米。
共三层,主要房间有客厅、主卧室、客卧、厨房、卫生间等,层高3.3m,窗高2m、门高2.5m,空调面积为约200平方米。
1.2 地理参数①经纬度:北纬21°50′,东经111°45′②海拔高度:23.3m2设计参数及参照标准2.1室外参数表2-1 室外气象参数2.2室温湿度要求表2-2 舒适型空调室设计参数2.3参照标准表2-4 参考标准3负荷计算3.1 空调负荷的概念及组成空调房间的冷(热)、湿负荷是确定空调系统送风量和选取空调设备的基本依据。
中央空调系统 论文
![中央空调系统 论文](https://img.taocdn.com/s3/m/eefbd901a6c30c2259019eec.png)
中央空调系统B07221 李建春 37一、概述随着科学技术的日新月异,特别是近年来计算机技术、信息技术、通讯技术、系统工程技术以及控制技术、综合布线技术等的迅速发展,使得人们对信息社会和安全舒适的生活方式的需求在不断的增加。
而目前正在兴起的楼宇自动化热,正是适应了这种社会信息化、生活舒适化与经济国际化的需要。
楼宇自动化向人们提供全面的,高质量的、安全、舒适、快捷的综合服务功能,它是现代高科技的结晶,是建筑艺术和信息技术的完美结合。
空气调节技术是楼宇自动化的一个重要组成部分。
楼宇自动化是一个热门话题。
如何在现有技术、产品的基础上设计开发能满足具体要求的自动化系统成为楼宇自动化行业技术人员的重要研究内容。
楼宇自动化作为智能建筑的一个重要分支,正逐渐体现出它的重要性和现实需要性。
目前在我过对楼宇自动化的需求越来越多,为了对楼宇自动化有一个清楚的了解,我们有必要对楼宇自动化进行充分的理解和研究。
空气调节技术已成为我国科学技术发展中的重要学科,近年来,空气调节技术在国民经济各个领域和人民生活的各个方面得到了广泛应用。
空调即空气调节,主要是通过一定的空调设备和调节手段对空气进行处理。
空气调节的任务就是在任何自然环境下,将室内空气维持在一定的温度、湿度、气流速度以及一定的洁净度。
二、空调系统的一般组成为了达到空调的目的,发挥空调的作用,就必须有对空气进行处理和调节的措施和方法,一般的空气调节的基本措施,要求其系统的结构组成应包括以下几部分。
2.1新风部分空调系统在运行过程中必须采用一部分室外的新鲜空气(即新风),这部分新风必须满足室内工作人员所需要的最小新鲜空气量,因此空调系统的新风取入量决定于空调系统的服务用途和卫生要求。
新风的导入口一般设在周围不受污染影响的地方。
这些新风的导入口和空调系统的新风管道以及新风的滤尘装置(新风空气过滤器)、新风预热器(又称为空调系统的一次加热器)共同组成了空调系统的新风系统。
精编【房地产管理】别墅户式中央空调系统设计
![精编【房地产管理】别墅户式中央空调系统设计](https://img.taocdn.com/s3/m/786e0deaf46527d3250ce024.png)
【房地产管理】别墅户式中央空调系统设计xxxx年xx月xx日xxxxxxxx集团企业有限公司Please enter your company's name and contentv别墅(户式)中央空调系统设计简介:小型风冷式冷水机组安装便捷,无需机房,省去了冷却塔,只需连通冷热水管路,水泵即可进行系统冷水循环。
而且机组可采用自动化控制、节水节电和对环境污染小等优点。
风冷热泵式和水冷热泵式应用于小型别墅的空气调节很好。
对于水冷热泵来说,需设置专用的冷却塔等装置。
因此,小型风冷热泵式空调很适合于小面积的场合使用。
关键字:别墅风冷热泵水冷热泵风机盘管相关站中站:空调水泵选型设计如何选择冷却塔?风机盘管选型方法冷却塔最新技术资料大全冷冻冷藏资料专区一、方案选择大型空调的冷水机组多为水冷式,而且一般制冷量大,不太适合于小型建筑的多室中央空调系统。
小型风冷式冷水机组安装便捷,无需机房,省去了冷却塔,只需连通冷热水管路,水泵即可进行系统冷水循环。
而且机组可采用自动化控制、节水节电和对环境污染小等优点。
正因为如此,系统采用中央空调的小型风冷式冷水机组配合风机盘管空调器的方案。
二、负荷计算根据中央空调的冷负荷系数法计算得出的结果如下:三、风机盘管选型根据中央空调的风机盘管选型方法,计算后得出的结果如下:注明:产品选自《申菱FP—WA系列空调器》样本手册。
四、风冷热泵机组选型风冷热泵机组:风冷热泵机组的冷负荷为14714.2*1.1= 16185.5W,我们选择TLC系列小型风冷式冷水机组的TLC—05。
其参数为:冷量15000Kcal/h,冷水流量6m3/h,水压损失2.3mH2O,接管管径DN70膨胀水箱:膨胀水箱选用V=0.6m3即可。
五、水管设计系统水管图六、风系统设计1.送风系统2.排风系统七、经济性参数建筑面积:157平方米空调面积:82.23平方米建筑面积指标:103W/m2空调面积指标:190W/ m2八、本设计的优点1.市场的户式中央空调很流行,对于我们来说,做户式中央空调的设计实例有助于就业。
中央空调系统在某高档住宅小区的应用
![中央空调系统在某高档住宅小区的应用](https://img.taocdn.com/s3/m/e3baf0032379168884868762caaedd3383c4b52f.png)
中央空调系统在某高档住宅小区的应用
曾庆钱;江冰
【期刊名称】《广东土木与建筑》
【年(卷),期】2004(000)011
【摘要】介绍广州地区某高档住宅小区采用中央空调系统的分析与设计过程,指出通过合理设计,中央空调系统在住宅建筑中应用可以达到节能、美观、舒适等效果,具有广阔的应用前景.
【总页数】2页(P35-36)
【作者】曾庆钱;江冰
【作者单位】广州市设计院,广州,510620;广州市设计院,广州,510620
【正文语种】中文
【中图分类】TU6
【相关文献】
1.某住宅小区中央空调系统余热利用的设计分析 [J], 周前;刘恩海;白岩
2.住宅小区设置中央空调系统的探讨 [J], 刘玲;李立玮
3.蓄能中央空调系统在住宅小区中的应用 [J], 罗雨标
4.蓄能中央空调系统在住宅小区中的应用 [J], 罗雨标;
5.上海路易凯旋宫住宅小区采用冰蓄冷中央空调系统夏季高峰转移用电量43万kW·h [J], 潘百城
因版权原因,仅展示原文概要,查看原文内容请购买。
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
毕业设计(论文)报告题目名称:广东某别墅中央空调系统设计学生姓名:吴雄邦学号: 1104173132二级学院(系)/专业:能源与电气工程学院/供热通风与空调工程技术班级:空冷1111班指导教师:王俊琪李振平2014年05月29日┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊摘要本设计为广东某别墅中央空调系统设计,拟为之设计合理的中央空调系统为室内生活人员提供舒适的生活环境。
建筑物共三层,一层为客厅、书房、餐厅、厨房、工人房、洗衣房,二层为3个卧室,1个起居室,三层为主卧室、衣库;要求采用中央空调夏季制冷冬季供暖。
内容包括将整个设计过程进行阐述,包括分析该建筑的地理环境和功能,根据暖通空调相关的设计手册和规范进行数据分析并确定空调系统,根据建筑结构特征和朝向等进行的负荷计算,根据各房间的负荷进行的末端设备选型,其末端是风机盘管的设计,最后根据别墅的空调使用率进行VRV家用中央空调的选型,然后绘制系统的平面图等,最后根据图纸进行负荷计算。
关键词:中央空调系统;风机盘管;负荷计算┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊ABSTRACTThis design is the design of a villa in Guangdong central air conditioning system, to provide a comfortable living environment for the indoor living personnel to design the central air conditioning system. The building of three floors, one for the living room, study room, restaurant, kitchen, laundry room, workers housing, the two layer is the 3 bedrooms, 1 living room, bedroom, three layer clothing library; require the use of central air-conditioning refrigeration in summer and heating in winter.The content includes the whole design process are expounded, including the analysis of the geographical environment and function, according to the HV AC design manual and standard data analysis and calculate the air conditioning system, according to the building structure and orientation of the load calculation, according to the terminal equipment selection room load, the end is the design of the wind the fan coil unit, according to the selection of air conditioning usage villa VRV household central air-conditioning, and then draw the system plans, according to the drawings for load calculation.Key words: The central air conditioning system; Fan coil units; Load calculation┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊目录1工程概况 (1)1.1 所选建筑物 (1)1.2 地理参数 (1)2设计参数及参照标准 (2)2.1室外参数 (2)2.2室内温湿度要求 (2)2.3参照标准 (2)3负荷计算 (3)3.1 空调负荷的概念及组成 (3)3.2 各房间负荷、总负荷 (5)3.2.1 外墙和屋面瞬变传热引起的冷负荷 (5)3.2.2 内墙,楼板等室内传热维护结构形成的瞬时冷负荷 (5)3.2.3 外玻璃窗瞬变传热引起的冷负荷 (6)3.2.4 透过玻璃窗的日射得热引起的冷负荷 (6)3.2.5 人体散热形成的冷负荷 (6)3.2.6 门引起的冷负荷 (7)3.2.7 照明、设备散热形成的冷负荷 (7)3.3相关参数的选取 (7)3.4 负荷计算总结 (8)4风机盘管与外机机组选型 (23)4.1大金家用VRV的优点及优势 (23)4.1.1大金家用VRV系统的优点 (23)4.1.2大金家用中央空调优势 (23)4.2风机盘管选型 (24)4.2.1风机盘管型号及各参数 (24)4.2.2各房间风机盘管选型 (26)4.3 外机机组选型 (26)4.3.1 计算总负荷数值 (26)4.3.2 外机机组型号及各参数值 (26)4.3.3 外机机组选型 (27)5各楼层平面设计图 (28)┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊5.1 楼层平面图 (28)5.2 智能感知3D气流风管式风机及冷煤管道、冷凝水管道布置 (31)结束语 (34)致谢 (35)参考文献 (36)附录 (37)┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊1工程概况1.1 所选建筑物广东某别墅;本建筑是一座家用别墅,所在地广东省阳江市,房间总面积约300平方米。
共三层,主要房间有客厅、主卧室、客卧、厨房、卫生间等,层高3.3m,窗高2m、门高2.5m,空调面积为约200平方米。
1.2 地理参数①经纬度:北纬21°50′,东经111°45′②海拔高度:23.3m┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊2设计参数及参照标准2.1室外参数表2-1 阳江室外气象参数2.2室内温湿度要求表2-2 舒适型空调室内设计参数2.3参照标准表2-4 参考标准┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊3负荷计算3.1 空调负荷的概念及组成空调房间的冷(热)、湿负荷是确定空调系统送风量和选取空调设备的基本依据。
在室内外热、湿扰量的作用下,某一时刻进入房间的总热量和湿量叫做该时刻的得热量和得湿量。
冷负荷的含义是维持一定的室内热湿环境所需要的在单位时间内从室内除去的热量,包括显热量和潜热量两部分。
热负荷的含义是维持一定室内的热湿环境所需要的在单位时间内向室内加入的热量,也同样包括显热负荷和潜热负荷量部分。
湿负荷的含义是维持室内恒定的相对湿度所需除去的湿量。
空调房间或区域的夏季负荷计算,应根据下列各项确定:⑴外墙负荷计算;⑵太阳辐射引起的负荷;⑶内墙总负荷;⑷电热设备总负荷;⑸电子设备总负荷;⑹人员散热总负荷;表3-1房间负荷结构表┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊3.2 各房间负荷、总负荷3.2.1 外墙和屋面瞬变传热引起的冷负荷在日射和室外气温综合作用下,外墙和屋面瞬变传热引起的逐时冷负荷计算公式:Qc,τ=KF[(tc,τ+td)KαKρ-t n] 式(3-1)式中: Qc,τ——外墙和屋面瞬变传热引起的逐时冷负荷,W;F——外墙和屋面的面积,㎡;K——外墙和屋面的传热系数,W/(㎡·℃)tn——室内计算温度,℃;td——地区修正系数,℃;ka——不同外表面换热系数修正系数kp——不同外表面的颜色系数修正系数由于αw、αn、ρ都采用北京地区特定条件,则有:Kα=1.0 Kρ=1.03.2.2 内墙,楼板等室内传热维护结构形成的瞬时冷负荷当空调房间的温度与相邻非空调房间的温度大于3℃时,要考虑由内维护结构的温差传热对空调房间形成的瞬时冷负荷传热公式计算:Qc,τ=F·K·(tl s- tn) W 式(3-2)式中:F——内维护结构的传热面积,m²;K——内维护结构的传热系数,W /( m²·k) ;tn——夏季空调房间室内设计温度,℃;tl s——相邻非空调房间的平均计算温度,℃。
t'l s按下式计算 t'l s=t +tl s℃式中:t ——夏季空调房间室外计算日平均温度,℃;tl s——相邻非空调房间的平均计算温度与夏季空调房间室外计算日平均温度的差值,当相邻散热量很少(如走廊)时,tl s取 3 ℃,当相邻散热量在23~116 W /m2时,tl s取5℃所以内墙及楼板冷负荷计算:内墙及楼板冷负荷的计算公式为:Q=KF(tls-tn)其中:tls=twp+△tlstls——相邻非空调房间的平均计算温度;twp——夏季空调室外计算日平均温度;△tls——相邻非空调房间的平均计算温度与夏季空调室外计算日平均温度的差值。
┊┊┊┊┊┊┊┊┊┊┊┊┊装┊┊┊┊┊订┊┊┊┊┊线┊┊┊┊┊┊┊┊┊┊┊┊┊3.2.3 外玻璃窗瞬变传热引起的冷负荷在室内外温差的作用下,玻璃窗瞬变热形成的冷负荷由下式计算:Qc,τ=F·K·(tl– tn) W 式(3-3)式中:F——外玻璃窗面积,m²;K——玻璃的传热系数,W /( m²·k) ;tl——玻璃窗的冷负荷温度逐时值,℃;tn——室内设计温度,℃。
不同地点对t1按下式修正:tl’=tl+td式中:td——地区修正系数,℃所以外窗传热温差引起的冷负荷:玻璃窗由温差引起的冷负荷计算公为:Qc,τ=KF(tˊc,τ-tn)其中: tˊc,τ=(tc,τ+td)Kα3.2.4 透过玻璃窗的日射得热引起的冷负荷透过玻璃窗进入室内的日射得热形成的逐时冷负荷由下式计算:Qc,τ=F·CZ·Dj.max· CLQW 式(3-4)式中:F——玻璃窗的净面积,是窗口面积乘以有效面积系数Ca,本设计双层钢窗Ca=0.75;CZ——玻璃窗的综合遮挡系数CZ= Cs·Cn;其中,Cs——玻璃窗的遮挡系数,6mm厚吸热玻璃Cs =0.87;Cn——窗内遮阳设施的遮阳系数,中间色活动百叶帘Cn=0.6;Dj.max——日射得热因数的最大值,W/m²CLQ——冷负荷系数所以南外窗日射得热引起的冷负荷:玻璃窗由日射得热引起的冷负荷计算公式为:Qf,τ=FCSCnDj,maxCL式(3-5)其中: Qf.Τ——透过玻璃窗的日射得热引起的逐时冷负荷(W);Dj,max——不同纬度带各朝向七月份日射得热因素的最大值;CS——窗玻璃的遮阳系数;CL——冷负荷系数。