The thermostat controls the temperature using a microprocessor.Features
Values Measuring and control range
0...600°C Sensor type
PT 100
Fe-CuNi
Degree of protection IP20Operating temperature -10...50°C Control voltage • H02 - 1• H02 - 5
230 / 11524V AC
V DC
Contents:1Connection 21.1Connections / DIP switch (22)
Operation
4
2.1Interface elements................................................................................................42.2Changing the control parameters..........................................................................52.3Changing the hysteresis........................................................................................62.4Adjusting the set point (7)
T:\\9081\\458011\\x00101td.tif
1 Connection
1.1 Connections / DIP switch
DIP switch 1.5
1Sensor type on1
off1PT 100 Fe-CuNi
2Hysteresis setting on
off2blocked possible
3Set value II on2
off free coupled
4not occupied-
•1 Switch setting dependent on the temperature sensor used
•2
Switch setting on delivery
T:\\9081\\458020\\e00102td.wmf
1.1Output 10 mA / 24 V DC
1.2Output III Last max.
1.3Input PT 100 / Fe-CuNi
1.4Output II
1.5DIP switch
1.6Control voltage
T:\\9081\\645094\\E00001kd.WMF
2 Operation
elements
2.1 Interface
•Current temperature reading
When adjusting:
•Set switching temperature
•Set control parameters
T:\\9081\\458010\\x00001td.wmf
2.1Key
2.2Key
2.3Display
2.4Up/down keys
2.2 Changing the control parameters
Caution:
Do not change factory settings!
½ Key 2.1 and key 2.2 5 seconds press
Õ Display 2.3 shows the parameter Settings ½ Select parameter with key 2.2½ Change parameter value with 2.4up/down keys Õ Display 2.3 blinks
½ Save parameter value with key 2.2½ Press key 2.1 and key 2.2
Õ Display 2.3 shows current actual value
Control parameters Display Parameter
Adjusting range Factory settings Display
Gluing Pxx 3dxx 30Ixx 15Cxx 20txx 0Fxx 0Lxx
60
T:\\9081\\458010\\x00001td.wmf
2.1Key 2.2Key 2.3Display
2.4
Up/down keys
Yxx Positioning degree display, current Cannot be adjusted Pxx Proportional range off, P1...P99%dxx Rate time off, 1...99sec Ixx Reset time
off, 1...99x106sec Cxx Switching cycle time 1...99sec txx Self optimization
off, on Fxx Actual value offset setting -19...99°C Lxx
Inst. rating scaling Input
100...600°C L10...L60