ABB m马达起动器 MS132
- 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
- 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
- 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。
Description
–Overload protection – trip class 10 –Phase loss sensitivity –Disconnect function
–Temperature compensation from -25 … +60 °C –Adjustable current setting for overload protection –Suitable for three- and single-phase application –Trip-free mechanism –Status indication
–Clear switch position indication ON/OFF/TRIP –Lockable handle Order data
MS132 screw terminal
Setting range A
Type Trip class
Order code Packing unit PCE Weight per PCE kg 0.10...0.16MS132-0.1610A 1SAM350000R100110.2150.16...0.25 MS132-0.25101SAM350000R100210.2150.25...0.40MS132-0.4101SAM350000R100310.2150.40...0.63 MS132-0.63101SAM350000R100410.2150.63...1.00 MS132-1.0101SAM350000R100510.2151.00...1.60 MS132-1.6101SAM350000R100610.2651.60...2.50 MS132-2.5101SAM350000R100710.2652.50...4.00 MS132-4.0101SAM350000R100810.2654.00...6.30 MS132-6.3101SAM350000R100910.2656.30...10.00 MS132-10101SAM350000R101010.2658.00...12.00 MS132-12 101SAM350000R1012 1
0.31010.00...16.00 MS132-16101SAM350000R101110.31016.00...20.00 MS132-20101SAM350000R101310.31020.00...25.00 MS132-25101SAM350000R101410.31025.00...32.00
MS132-32
10
1SAM350000R1015
1
0.310
Note: MS132 with pre-assembled auxiliary contact HKF1-11,
please order as follow 1SAM350005Rxxxx
Manual motor starters are electro-mechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less against short-circuit, overload and phase failures. Fuse less protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Fuse less starter combinations are setup together with contactors.
2C D C 241020F 0009
Approvals
A cULus UL 508K
CB scheme ABS E CCC D
GOST-R GOST-F
P
Lloyd’s Register
GL
DNV RINA
Marks a
CE
2 - 2CDC131021D0201
Functional description
2C D C 241020F 000
9
1
234567
1 Terminals 1L1, 3L2, 5L3
2 Switch position TRIP
3 Lockable handle
4 Status indication for short-circuit
5 Current setting range
Adjustable current setting for overload protection 6 Test function
7 Terminals 2T1, 4T2, 6T3
Application
The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole protection devices with thermal tripping elements for overload protection and electromagnetic tripping elements for short-circuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and can be used for the manual switching of loads.
The manual motor starters have a setting scale in amperes, which allows the direct adjusting of the device without any
additional calculation. In compliance with international and national standards, the setting current is the rated current of the motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current).
Operation mode
Single-phase operation Three-phase operation
Wiring diagram