Protection Relay REX 521Operator’s Manual3REX 521Issued:29.11.2001Version:E/04.06.2004We reserve the right to change data without prior notice.Protection Relay Operator’s Manual Contents1.About this manual (5)1.1.Copyrights .....................................................................................51.2.Trademarks ...................................................................................51.3.General .........................................................................................51.4.Abbrevitations ...............................................................................61.5.Related documents .......................................................................61.6.Document revisions .. (7)2.Safety information (7)3.Introduction (8)3.1.REX 521 protection relay (8)4.Instructions (9)4.1.HMI features (9)4.1.1.Push-button functions (11)4.1.2.Selecting language (12)4.1.3.Passwords (13)4.1.4.Display backlight (13)4.1.5.Display contrast (13)4.1.6.Display test (14)4.1.7.Selecting primary values (14)4.1.8.Optically isolated serial communication port (14)4.2.Menu chart (15)4.2.1.Measurement menu (16)4.2.2.Event menu (17)4.2.3.Manual control (18)4.2.3.1.Local/Remote position selection (18)4.2.3.2.Controlling breaker (19)4.2.4.Setting parameters (21)4.2.5.Setting bit masks (21)4.3.Indication messages (22)4.3.1.Protection indications (22)4.3.2.Self-supervision (23)4.3.3.Condition monitoring indication (24)4.4.LED indicators (25)4.4.1.Green indication LED (READY) (25)4.4.2.Yellow indication LED (START) (25)4.4.3.Red indication LED (TRIP) (25)4.5.Alarm LEDs (26)4.5.1.Alarm LED 1-8 (26)1MRS 751107-MUMREX 521Protection Relay1MRS 751107-MUMOperator’s Manual5.Test mode (27)5.1.I/O test (27)5.2.IRF test (27)5.3.Function block test (28)6.Index (29)41MRS 751107-MUMProtection Relay Operator’s Manual REX 52151.About this manual 1.1.Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document.This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.Copyright © 2004 ABB Oy All rights reserved.1.2.Trademarks Brand and product names mentioned in this document are trademarks or registered trademarks of their respective companies.1.3.GeneralThe purpose of this manual is to provide the user with basic information on the protection relay REX 521 Revision E, and to especially focus on explaining the use of the human-machine interface (HMI).For information about the new features of the relay, refer to REX 521 Technical Reference Manual, General (see “Related documents” on page 6).61MRS 751107-MUM Protection Relay Operator’s Manual REX 5211.4.Abbrevitations 1.5.Related documents Manuals for the REX 521Parameter and event lists for the REX 521Tool-specific manuals CBFP Circuit-breaker failure protection CT Current transformer HMI Human-machine interface HSPO High-speed power output IRF Internal relay fault LCD Liquid chrystal display PO Power output RS Rogowski sensor SO Signalling output VD Voltage divider VT Voltage transformer •Technical Reference Manual, Standard Configurations 1MRS 751802-MUM •Technical Reference Manual, General 1MRS 751108-MUM •Installation Manual 1MRS 750526-MUM •Technical Descriptions of Functions (CD-ROM)1MRS 750889-MCD •Modbus Remote Communication Protocol for REX 521, Technical Description 1MRS 755017•DNP 3.0 Remote Communication Protocol for REF 54_ and REX 521, Technical Description 1MRS 755260•Parameter List for REX 5211MRS 751999-RTI •Event List for REX 5211MRS 752000-RTI •General Parameters for REX 5211MRS 752156-RTI •Interoperability List for REX 5211MRS 752157-RTI •CAP505 Installation and Commissioning Manual 1MRS 751273-MEN •CAP505 Operator’s Manual 1MRS 751709-MEN •CAP505 Protocol Mapping Tool, Operator’s Manual 1MRS 755277•Tools for Relays and Terminals, User’s Guide 1MRS 752008-MUM •CAP 501 Installation and Commissioning Manual 1MRS 751270-MEN •CAP 501 Operator’s Manual 1MRS 751271-MUM1MRS 751107-MUMProtection Relay Operator’s Manual REX 52171.6.Document revisions 1.7.Safety information Version Revision number Date History D 25.03.2004Document layout changed E 04.06.2004Pictures updated in tables, chapter 3.2.1.Changes in tables, chapters 3.4.1. and 3.5.1.Warning text added, chapter 4.1.REX 521Protection Relay1MRS 751107-MUMOperator’s Manual2. Introduction2.1.REX 521 protection relayThe protection relay REX 521 is designed for protection, control, measuring andsupervision in medium voltage networks. Typical applications include incoming andoutgoing feeders as well as substation protection. The protection relay is providedwith energizing inputs for conventional current and voltage transformers. Also ahardware version with inputs for current and voltage sensors is available.The protection relay is based on a multiprocessor environment. The HMI includingan LCD (liquid chrystal display) with different views makes the local use easy andinforms the user via indication messages. Modern technology is applied both inhardware and software solutions.The REX 521 is part of the substation automation concept for distributionautomation and extends the functionality and flexibility of the concept.81MRS 751107-MUM Protection RelayOperator’s Manual REX 52193. Instructions3.1.HMI features•Push-buttons for navigating, [C] Clear/Cancel and [E] Enter •Language selection•Setting values are protected by passwords•Display backlight•Display contrast•Display test•Selection of primary values•Optically isolated serial communication port•Three LED indicators•Eight programmable alarm LEDsREX 521Protection Relay1MRS 751107-MUMOperator’s Manual ArrayFig. 3.1.-1HMI front view1.Alarm LEDs2.LED indicator: Trip, CBFP3.LED indicator: Start, Block4.LED indicator: Ready, IRF, Test mode5.LCD6.Optical PC connector7.Navigation buttons8.Clear/Cancel9.Enter103.1.1.Push-button functionsThe HMI includes push-buttons for operating the protection relay.A quick touch on the arrow button up [↑] or down [↓] is interpreted as one stepupwards or downwards in a menu or as the minimum step up or down in settingmode of a parameter.•The cursor stops at the first and last rows in a menu; pressing the [↑] button at thefirst row or [↓] button in the last row is ignored.•If the [↑] or [↓] button is kept pressed, the menus are automatically scrolled fasterthan with single button pressings.Fig. 3.1.1.-1Push-buttonsThe table below gives a short explanation of the push-buttons and their functions.Table 3.1.1-1Push-button functions11Table 3.1.1-1Push-button functions3.1.2.Selecting languageFig. 3.1.2.-1Selecting language1.Select with [↓] and [→ ] buttons Configuration in the main menu,General in the group menu, Software in the subgroup menu andActive language in the parameter menu.2.Press the [E] button until the second row of the display starts flashing. Thenselect the desired language with [↓] and [↑] buttons.3.Confirm the selection by pressing the [E] button once more or cancel theselection by pressing the [C] button.After altering the language, the display menus are shown in the new language andthe selection is restored after a disconnection of the power supply.12Operator’s Manual3.1.3.PasswordsFig. 3.1.3.-1Password menusSetting values are protected by passwords. There are two different passwords, onefor protecting the HMI setting values and another for protecting settings throughserial communication.•The default value of the serial communication password is 001 and of the HMIpassword 999.•The HMI password is not active until it has been changed from the default value.After changing it, the relay prompts for password whenever the [E] button ispressed in the setting value menu. Once the right password has been given, itstays active until the display is returned to idle state by time-out. To disable theHMI password, change it back to the default value 999.•In case a password is forgotten, the HMI password can be viewed and changedvia serial communication.3.1.4.Display backlightThe backlight of the display is normally off. When a button on the HMI is pressed,the backlight turns on automatically and the panel is ready for further operations.•At power up, the backlight is also turned on during the display test.•After a time-out period (5 min), the backlight is automatically switched off ifthere has not been any activity on the panel.•When changing between Local/Remote mode by a digital input, the backlight isturned on for 10 seconds.3.1.5.Display contrastThe display contrast is temperature compensated, which means that the contrastautomatically adjusts itself with temperature to preserve readability.•To obtain optimal readability, the contrast of the display can be adjusted.Pressing simultaneously the [E] button and [↑] or [↓] button increases ordecreases the contrast.13Fig. 3.1.5.-1Adjusting display contrast•The display contrast may be adjusted anywhere in the menu structure except inthe setting menus where the [E] button is used for entering the setting mode.•The selected contrast value is stored in a non-volatile memory and thus, after anauxiliary power failure, the contrast is restored automatically.3.1.6.Display testUpon auxiliary voltage connection, the backlight is turned on and a short display testis run. This display test includes all the LEDs and the LCD. The LEDs are tested byturning them on simultaneously while the LCD shows two patterns so that all thepixels are activated. After the test, the display returns to normal state.•The display test can also be started manually by navigating toConfiguration\Display\Test display and then selectingTest display (refer to section “Menu chart” on page15).3.1.7.Selecting primary valuesThe setting values, input data and recorded values that are relative to some quantitycan be obtained directly in amperes and volts. For the relay to know how to convertbetween primary and per unit values, the setting values describing the measurementdevices (CT, VT, VD, RS) need to be properly set.1.Navigate to Configuration\Display\Primary values and selectPrimary values instead of the default Per unit values.2.Navigate to Configuration\Meas. devices and enter the data for allthe CTs and VTs, VDs and RSs that are in use in that particular hardware. Forinformation about setting the rated values for the protected unit and about thetechnical data of the measuring devices, refer to Technical Reference Manual,General (see “Related documents” on page6).3.1.8.Optically isolated serial communication portThe front panel of the protection relay is provided with an optical serialcommunication connector. The connector is used for programming the relay with aPC via a RS-232 cable, type 1MKC950001-1.143.2.Menu chartThe contents of the menu chart depend on the configuration of the relay. However,Fig. 3.2.-1An example of a menu chart structure15Operator’s Manual3.2.1.Measurement menuThe contents of the measurement menu depend on the relay configuration.If a measurement view is selected, it remains active after the time-out period. Thesame is true with the manual control view. From other views, the display reverts toidle mode at the same time as the backlight is switched off.•If energy measurements are present, accumulated values can be reset by pressingthe [C] button for 2 s.Table 3.2.1-1Measurement view16Table 3.2.1-1Measurement view (Continued)* The calculated thermal level of the device, maximum from the stator and the rotor.**Only available in configuration H083.2.2.Event menuThe event menu (Main menu\Measured values\Events) contains thefunction block name and the event in the same manner as the indication messages(see “Indication messages” on page22). The first view of the event menu shows theamount of events (maximum 50). The most recent event is stored on top of the list.When a certain event is selected, date and time of the event in question can be readby moving one step right with the [→ ] button. If the event in question is a trip eventand its data in the recorded data menu (Main menu\Protection\…\Recorded data1\…3\) has not been overwritten, it is possible to move directlyto the associated recorded data by moving right [→ ] again in the date and time view.Return to the event view with the [C] button or with the [← ] button, like in normalmenu navigation. When viewing recorded data, the return is directed to the eventsummary view (Main menu\Measured values\Events) if•the recorded data is overwritten, or•the original event is overwritten in the event list, or•the event list is cleared.These events are stored in the non-volatile memory, which means that they can alsebe seen after a disconnection of the power supply. When displayed, the event list canbe cleared by pressing the [C] button for 2 seconds.17Fig. 3.2.2.-1Event view3.2.3.Manual control3.2.3.1.Local/Remote position selectionThe control position can be changed in Control\Manual control\Local/Remote.•The control mode can be selected by pressing the [E] button and using the [↑] and[↓] buttons.•The [E] button confirms the selected mode and the [C] button cancels theselection and keeps the current mode.For password handling, refer to section “Passwords” on page13.Table 3.2.3.1-1Control positionsControl position DescriptionControl off Local and remote operations are inhibited. The current state of the objectis shown in the control menu.Local Object can be controlled from the HMI and the digital inputs. Remotecontrol is inhibited.Remote Object can be controlled via remote communication. Control from theHMI and digital inputs is inhibited and the object state is shown in thecontrol menu.External input The digital input programmed for selector Local/Remote is used forselecting between the local and remote modes. When selected the modewill be displayed as Local (ext.) or Remote (ext.) depending onthe digital input state.The selected control position remains the same during auxiliary power-off.When the local mode is selected, the character “L” is shown in the bottom-rightcorner of the HMI main view. However, if the language in the relay is other thanEnglish, the character that is shown in the display depends on the selected language. 183.2.3.2.Controlling breakerThe object control menu is in Control\Manual control\Control CB.Only the current position of the breaker is shown and no control is possible in remoteor control off mode. In local mode the state of the breaker is shown and the possibletarget states can be scrolled with [→ ] and [← ] buttons. Possible target states areopen and closed. When the desired target state is selected the object can be selectedby using the [E] button.Message =Preparing... can be briefly shown before the text=Are you sure? is displayed. The operation can then be confirmed with the [E]button and cancelled with the [C] button. If the operation is cancelled the text=Aborted is displayed for three seconds and then the current state of the breakeris shown. The same happens if the =Are you sure? has been displayed for 30seconds.Notice that an adjustable timeout in Control\General\Select timeoutrestricts the time between the object selection and the control request. If the timeoutis shorter than 30 seconds and it elapses before the operation is confirmed,controlling the object will not be possible before the object is selected again. If theoperation is confirmed, the appropriate transition text (=Opening... or=Closing...) is shown for at least four seconds after which the current state ofthe object is shown.19The current state of the interlocking of the object can prevent the select or executerequests. In that case the text =Interlocked is displayed for three seconds. Theattempted operation is cancelled and after the three seconds the current state of theC o n t r o l C B=O p e n. E=C l o s e=C l o s e d. E=O p e n=C l o s e d. E=C l o s eC o n t r o l C BC o n t r o l C Br e Y o u S u r e ?C o n t r o l C B=O p e n i n g ...Fig. 3.2.3.-1Manual controlTable 3.2.3-1Manual control messagesMessage MeaningAborted The current operation was aborted either by user or state change in object statusor timeout.Are you sure?Waiting for confirmation for the selected operation. [E] accepts it and [C] cancels it.Closed Object state is closed. Control is not possible due to remote or control off state.Closed. E=Close Object state is closed. [E] will close it.Closed. E=Open Object state is closed. [E] will open it.Closing...Object is being closed.External change Local/remote state controlled by digital inputs has changed. Only in external inputmode. Cancels current operation if any.Failed Executing the control request failed. The reason was not interlocking.Interlocked Selecting the object or executing the control request failed due to interlocking.Not allowed Selecting the object failed. The reason was not interlocking.Not local Attempted to control the object in remote or control off state.Open Object state is open. Control is not possible due to remote or control off state.Open. E=Close Object state is open. [E] will close it.Open. E=Open Object state is open. [E] will open it.Opening...Object is being opened.Preparing...Object is being selected.Undefined Object state is undefined. Control is not possible.Unresolved Object state is unknown.20Operator’s Manual 213.2.4.Setting parameters The setting parameters are listed in the CD-ROM Technical Descriptions of Functions (see “Related documents” on page 6).1.Navigate to the right parameter using the buttons [↑], [↓] and [→ ], [← ] and the menu chart structure as reference.2.Activate setting mode by pressing the [E] button.3.If the default HMI password has been changed, it is now prompted. To enter the valid password, change the active digit by pressing the buttons [← ] and [→ ], then set the digit value by pressing the buttons [↑] and [↓].4.Once the password has been entered, press the [E] button to confirm. Now the selected setting value starts flashing.5.Enter the new setting value using the buttons [↑], [↓] and [→ ], [←].6.Press the [E] button to confirm.7.If the new value is within the allowed limits, it is now stored in the non-volatile memory and restored after disconnection of power supply.8.If an illegal setting value is confirmed, a message in the display tells the user that the setting is out of range by showing the message Invalid value, and the previous parameter value remains unchanged.3.2.5.Setting bit masksEvent masks and switchgroups are presented as bit masks with a checksum. Most of the events can be included in or excluded from the event reporting by altering the bits of the event masks. Switchgroups are used for changing the connections of inputs and outputs to the relay function blocks.Fig. 3.2.5.-1Bit mask in setting modeWhen navigating in menus containing bit masks, only the checksum is shown. If setting mode is entered, the single bit presentation (bit 0, value 1, in the example above) appears in the rightmost lower corner of the display. The contents of the bit mask may be altered by entering single bit values. However, the new values are not valid until setting mode has been exited by pressing the [E] button.1.Navigate to the right parameter using the buttons [↑], [↓] and [→], [← ] and the menu chart structure as reference.2.Activate setting mode by pressing the [E] button.3.If the default HMI password has been changed, it is now prompted. To enter the valid password, change the active digit by pressing the buttons [← ] and [→ ], then set the digit value by pressing the buttons [↑] and [↓].4.Once the password has been entered, press the [E] button to confirm. Now the selected setting value starts flashing.5.Enter the new setting value using the buttons [↑], [↓] and [→ ], [← ].6.Press the [E] button to confirm.When entering single bit values, the bit to be edited may be shifted by pressing the[→ ] button when the cursor is located in the rightmost corner of the display. In thatway, the cursor does not have to be moved back and forth between the bit numberand the value during the setting period, thus simplifying the procedure.For information about the meaning of each event, refer to Event List for REX 521on the CD-ROM Technical Descriptions of Functions (see “Related documents” onpage6).3.3.Indication messagesThere are two different kinds of indication messages:•A text message together with a LED indication.This type of messages are related to information from the protection functionsand information concerning the condition of the protection relay (self-supervision).•A text message without a LED indication.This type of messages are related to condition monitoring, alarms and warningsor help texts appearing when certain display operations are performed.Indication messages have a certain priority. If different types of indications occursimultaneously, the message with the highest priority appears on the display.Priority order of the messages:1.Internal fault, CBFP2.Trip3.Start, Block4.Help messagesIndication messages may be cleared with the [C] button, until the display reverts tothe menu active before the events.Help messages are displayed when certain operations are done. For example, whenresetting output relays, events and registered values by pressing the [C] and [E]buttons for 5 s, a help text describing the operation is displayed at the same time.3.3.1.Protection indicationsWhen a protection function starts, the symbol of the protection function and the textSTART are displayed. The corresponding yellow LED indicator is also lit. In caseof three-phase or two-phase protection functions, the faulted phases are displayed aswell.Fig. 3.3.1.-1Indication of startIf a started protection function is blocked, the name of the function and the textBLOCK are displayed. Now, the yellow LED indicator is blinking.22Fig. 3.3.1.-2Indication of blockingIf a protection function trips, the name of the function and the text TRIP appear onthe display. The red LED indicator is lit. The faulted phases are displayed in thiscase.Should the protection function deliver a delayed trip for circuit-breaker failureprotection (CBFP), the red indicator starts blinking.Fig. 3.3.1.-3Indication of trip3.3.2.Self-supervisionThe protection relay is provided with an extensive self-supervision system. The self-supervision system handles run-time fault situations and informs the user aboutexisting faults over the display and the serial communication.When a fault has been detected, the green READY indicator starts blinking. At thesame time, the self-supervision (IRF) output relay is activated.Additionally, a fault indication text INTERNAL FAULT appears on the display andan event is generated.Fig. 3.3.2.-1Indication of faultThe fault indication has the highest priority and no other indication can overrun it.The fault indication text is displayed until it is cleared by pressing the [C] button.The green READY indicator continues blinking as long as the fault is present.Should the fault disappear after a reset, the indicator stops blinking and an event isgenerated over the serial communication. The self-supervision (IRF) output relay isreturned to its normal state.23243.3.3.Condition monitoring indicationIf the relay configuration includes condition monitoring functions that are not directly related to any protection function or to the internal relay condition,indication messages with the message SUPERV and an explanatory text appear if faults are found.Fig. 3.3.3.-1Condition monitoring indicationOperator’s Manual3.4.LED indicators3.4.1.Green indication LED (READY)3.4.2.Yellow indication LED (START)3.4.3.Red indication LED (TRIP)253.5.Alarm LEDs3.5.1.Alarm LED 1-8a.Valid only if the LED is not activated by the parameter Alarm LED States.b.The alarm can also be OFF if an auxiliary supply break has occurred. The state of the LED is thenpreserved and has to be acknowledged (cleared) from the main view.26274. Test modeDigital inputs, output relays and IRF relay may be tested by setting the parameter Test mode to Testing in the menu Main menu\Tests\General . When test mode is activated, the green READY indicator is blinking. For more information, refer to Technical Reference Manual, General (see “Related documents” on page 6).Test mode can be cancelled by setting the parameter to No test or by disconnecting the power supply.If the user does not cancel the test mode, it remains active and the Ready LED remains blinking.4.1.I/O test The picture below shows the menu used for digital input testing (Tests\Inputs ) in the hardware variant with nine digital inputs. The digits correspond to the inputs DI1...DI9, starting from the right side. Fig. 4.1.-1Digital input testing The following picture shows the menu used for output relay testing Tests\Outputs . Observe that the self-supervision relay is activated in another menu and is thus not included in this menu. The relays are activated in the order: SO, PO and HSPO, starting from the right side.Fig. 4.1.-2Output relay testing If the user forgets to cancel the test mode, it remains on and the Ready LED indicator remains flashing.4.2.IRF testThe IRF relay may be tested by activating the IRF relay in the menuMain menu\Tests\General\Activate IRF .4.3.Function block testThe outputs (Start and Trip) of a function block can be activated locally via the HMIor externally via serial communication. This is possible without setting the relay intest mode as described in “Test mode” on page27. The outputs are activated byusing control parameters of the function. For more information about the functions,refer to the CD-ROM Technical Descriptions of Functions (see “Related documents”on page6).285. IndexAAbout this manual (5)Alarm LEDs ..........................................................................................9, 261-8 (26)Modes (26)BBit masks (21)Altering contents (21)Breaker (19)Buttons (11)DDigital inputsTesting (27)DisplayAdjusting Contrast (13)Backlight (13)Contrast (13)Display test (14)Language (12)EEvent view (17)HH07 configurationMeasurement view (17)HMI features (9)IIndication messagesCondition monitoring (24)Green LED (25)Help messages (22)Internal fault (22)Protection indication (22)Self-supervision (23)Start, Block (22)Trip, CBFP (22)Introduction (8)IRF relayTesting (27)JJump (17)29。

[整理]REX521技术参考手册.

[整理]REX521技术参考手册.

REX 521型微机保护继电器技术参考手册汇编上海ABB工程有限公司2002,08,181. 概述REX521建立在RED500平台上,是REF54_型馈线终端的一种简化产品。

它是综合保护、控制、测量、监视和通信为一体的微机终端。

本手册阐述REX521终端的概貌、及其配置。

首先是概述,第二部分逐项描述了基本配置和中级配置等两种的标准配置的概况,第三部分到第六部分介绍了信号路径及其功能,第七部分为应用举例。

最后是附录,为原版Copy的技术数据和外部结线图,以供查阅防止误导。

REX 521 和RED 500 平台在功能模块介绍上的不同在CD-ROM“功能的技术介绍” (1MRS 750889-MUM)的功能模块的介绍方面, REX521 和RED 500 平台在某些方面有所不同。

首先,某些术语是指其他产品而不是REX521,其次,有某些数据仅适用于REX521:• 在试验某一功能模块时,READY 指示灯闪烁。

• 事件标识位1仅适用于SPA 通讯。

• 不能实现直接控制自动重合闸的功能。

REX521输入、输出量一览表:REX521的输出继电器接点能力REX521 机箱安装尺寸:请参阅下图中的标准19英寸的1/3 (表中第二项)。

REX521的整定范围一览表:REX521的通信串口:面前一个背后两个,全是光纤通信口。

背后串口的通信规约LON/IEC/SPA 可选。

表1.-1 REX 521的两种标准配置表1.-2 REX521的保护功能表1.-3 REX521的控制功能表 1.-4 REX521的测量功能表 1.-5 REX 521的状态监测功能表 1.-6 REX 521电源质量监视功能基本配置和中级配置的主要区别在于,中级配置增加了方向接地保护。

B01和B02以及M01和 M02之间的区别是,B02 和M02增加了自动重合闸功能。

2. 信号路径总图表示除模拟量信号外的输入、输出的功能控制的耒龙去脉的信号路径图图:2.-1 信号路径总图概念2.1. 数字量输入为了实现不同的功能,数字量输入(DI1...DI9) 要连接到功能模块的输入口,或直接连接到输出回路。

RC521-FE、RC522-FE(REV.D)用户使用手册200702

RC521-FE、RC522-FE(REV.D)用户使用手册200702

RC521/2-FE(D) 用户使用手册
200702
瑞斯康达科技发展股份有限公司为客户提供全方位的技术支持和服务。 直接向瑞斯康达科技发展股份有限公司购买产品的用户,可与瑞斯康达科技发展股份有限公司各地办事 处或用户服务中心联系,也可直接与公司总部联系。 读者如有任何关于产品的问题,或者有意进一步了解公司相关产品,可采用下列方式与我们联系: 公司网址: 8610-82883110(7×24 小时)
接地警示信息:为了保证设备的安全与运行稳定性,在使用本设备时必须提供良好 的接地保护。如果电源的接地系统不完善,请务必用接地线将本设备的接地螺钉和安全接 地系统连接。接地线的线径要求是至少大于或等于 AWG16(1.5mm2) 。
请勿擅自拆卸设备,否则将可能造成不可恢复的损坏,瑞斯康达科技发展股份 有限公司将视擅自拆卸设备为自动放弃保修权利。


Copyright ©2007 瑞斯康达科技发展股份有限公司 版权所有,保留一切权利。 非经本公司书面许可,任何单位和个人不得擅自摘抄、复制本书内容的部分或全部,并不得以任何形式 传播。 是瑞斯康达科技发展股份有限公司的注册商标。 对于本手册中出现的其它商标,由各自的所有人拥有。 这里的产品和服务名称都为瑞斯康达科技发展股份有限公司的商标。 由于产品版本升级或其它原因,本手册内容会不定期进行更新。除非另有约定,本手册仅作为使用指导, 本手册中的所有陈述、信息和建议不构成任何明示或暗示的担保。
1.2 功能特性
1、 RC521-FE(D)台式设备,用户端使用 2、 RC522-FE(D)模块式设备,放置于采用双电源容错的局端十六槽机箱使用,热插拔模块,高可靠性。 3、 RC522-FE(D)有 Master 和 Slave 两种工作方式,局端设备为 Master,远端设备为 Slave,可以通过拨码设 置改变,内置远端管理模块。 4、 能传输 10M 或 100M 速率的以太网业务。可选配不同距离、不同波长的业务模块以满足不同的要求 5、 丰富的工作状态指示灯,方便、准确地了解设备接口、链路的工作状态 6、 RC522-FE(D)在网管软件的支持下可以对电口速率进行 N*64kb/s 配置 7、 支持可选择的光路、以太网电口中断转移功能,可将中断告警传递给对端设备 8、 光口默认类型 DSC 接口,可根据需要定制 FC 等接口类型 9、 光口支持 100Base-FX 光纤传输标准,可与其它产品互通 10、以太网电口 10/100Mbps 自适应,全双工/半双工自适应 11、支持直连线,交叉线自适应功能 12、支持超常帧传输,最大 2046 字节透传 13、 RC521-FE (D) 紧凑小机箱结构, 内置交流 220V 电源, 放置于客户端, 物理尺寸 120mm×39mm×155mm(宽 X 高 X 深) 14、RC522-FE(D)亦可配合内置电源的一槽、四槽机箱使用,配置灵活,物理尺寸 91mmX25mmX152mm 15、工作温度 0~45℃ 16、设备功耗<5W 产品结构 1、 电源由 16 槽(4 槽)机箱背板或单槽机箱供电,电源电压为+5V5%;消耗电流小于 0.6A。 2、结构尺寸与现有收发器板卡尺寸相同。

REX521_CN_new

REX521_CN_new

© ABB Oy - 12 9 May 2005
REX 521 Feeder and Motor Protection
各种通讯规约
易于接入监控系统
REX521支持的通讯规约包括:
DNP 3.0 level 2 IEC 60870-5-103 Modbus LON SPA
© ABB Oy - 13 9 May 2005
© ABB Oy - 33 9 May 2005
REX 521 Feeder and Motor Protection
REX521输出继电器的接点能力
HSPO / PO SO / IRF 5 A 10 A 8 A 1/0.25/0.15 A
连续载流能力 0.5秒接通能力 3秒接通能力 在DC 48/110/220V,控 制回路时间常数 L/R<40ms下的遮断能力
© ABB Oy - 29 9 May 2005
定时限: 0.05— 300.00 S 同上
REX 521 Feeder and Motor Protection
REX521的整定范围-4
励磁涌流和电动机启动检测功能块 二次谐波比率:5—50% 启动电流: 0.1—5.0 X In 三相电流少于5% In ,且t >60 ms后,出现任一相大 于整定的启动电流,“电动机启动”动作。在大于整定的最 短脉宽下、当三相电流均少于90 %的整定启动电流且时间 大于150 ms时,“电动机启动”返回。 动作的最短脉冲宽度可在Control settings中整定, 其范围为:0—1000ms
© ABB Oy - 20 9 May 2005
REX 521 Feeder and Motor Protection
DI 输入回路及其输入菜单选择器

ABB继电器选型资料

ABB继电器选型资料
ransmission and Distribution Automation Equipment ( Xiamen ) Co., Ltd.
选型手册
Product Catalog


发布:2005.09.12 状态:新稿 版本:A/2005.09.12 本公司保留数据修改权利·恕不另行通知
1
5
三 端子接线图
*) 功率方向 **) 典型接线 6
外部 跳闸 外部 合闸
隔离开关 Q1 合 隔离开关 Q1 分
隔离开关 Q2 合 隔离开关 Q2 分 隔离开关 Q3 合 隔离开关 Q3 分
REF 542plus 开关柜保护和测控装置
一概述
在中压开关柜的无论有无后台系统各种应用场合中,均能 使用数字式控制技术的解决方案。开关柜保护和测控装置 REF 542plus 就如同它的前一代产品 REF 542,集成了测 量、监视、保护、控制和自检等功能,同时拥有完善的通 讯规约,REF 542plus 能够方便地集成到 ABB 或其他第三 方后台系统中。上述功能和其他一些电能质量检测功能都 基于可编程环境中,新一代装置特别的灵活性和可扩展性 使得一个装置可实现所有的二次方案,甚至传统的方法无 法实现的方案,它都很容易实现。
开关量输入和输出接点数量
输入/输出接点数量 开关量输入接点 跳闸回路监视输出接点
REF 541 15 2
REF 543 25 2
REF 545 34 2
大容量输出接点(NO 单极)
0
大容量输出接点(NO 双极)
5
信号输出接点(NO)
2
2
3
9
11
2
4
信号输出接点(NO/NC)
5

REX521保护继电器操作手册

REX521保护继电器操作手册

Protect IT保护继电器REX 521操作手册ABB的Industrial IT产品是用于提高生产率的标准件,并具备所有必要的工具,可在产品的寿命周期内以电子形式提供支持。

目录1.安全信息 (5)2.引言 (6)2.1.REX 521保护继电器 (6)3.说明 (7)3.1.HMI的特点 (7)3.1.1.按钮功能 (9)3.1.2.选择语言 (11)3.1.3.密码 (12)3.1.4.显示背光 (12)3.1.5.显示器对比度 (12)3.1.6.显示器测试 (13)3.1.7.选择一次侧值 (13)3.1.8.带光隔离的串行通讯端口 (13)3.2.菜单图 (14)3.2.1.测量菜单 (15)3.2.2.事件菜单 (16)3.2.3.手动控制 (17)3.2.3.1.本地/远方位置选择 (17)3.2.3.2.控制断路器 (17)3.2.4.整定参数 (20)3.2.5.整定位掩码 (20)3.3.指示信息 (21)3.3.1.保护指示 (21)3.3.2.自检 (22)3.3.3.状态监视指示 (23)3.4.LED指示灯 (24)3.4.1.绿色指示LED(READY) (24)3.4.2.黄色指示LED(START) (24)3.4.3.红色指示LED(TRIP) (24)3.5.告警LED (25)3.5.1.告警LED1-8 (25)4.测试模式 (26)4.1.I/O测试 (26)4.2.IRF测试 (26)4.3.功能块测试 (27)5.参考书目 (28)6.索引 (29)7.附录A缩略语: (32)修订历史版本D/17.11.2003:–更改第3.1节., 第3.2.3.1.和第5节。

–更改第10页表3.1.1-1,“按钮功能”,第15页表3.2.1-1,“测量视图”。

–更改图3.2.-1中的内容。

版本D/25.03.2004:–更改文档版面1. 安全信息2. 引言本手册旨在给用户提供关于保护继电器REX 521 版本C的基本信息,着重阐述人机界面(HMI)的使用。

sl521中文资料_数据手册_IC数据表

sl521中文资料_数据手册_IC数据表

SL521150MHz WIDEBAND LOG AMPLIFIERThe SL521A, B and C are bipolar monolithic Integrated circuit wideband amplifiers, intended primarily for use in successive detection logarithmic IF strips, operating at centre frequencies between 10MHz and 100MHz The devices provide amplification, limiting and rectification, are suitable for direct coupling and incorporate supply line decoupling The mid-band voltage gain of the SL521 is typically12dB(4times)The SL521A, B and C differ mainly in the tolerance of voltage gain and upper cut-off frequencyThe device is also available as the 5962-90792 which has guaranteed operation over the full Military Temperature Range and is screened to MIL-STD-883 Class B. Data is available separatelyFEATURESs Wide Defined Gain s 4dB Noise Figure s Hlgh I/P impedance s Low O/Pi mpedance s 165MHz Bandwidths On Chip Supply Decoupling sLow External Component CountORDERING INFORMATIONSL521 A CM 5962-90792 (SMD)SL521 B CM SL521 C CMABSOLUTE MAXIMUM RATINGS(Non-simultaneous)Storage temperature range -65°C to +150°C Operating temperature range -55°C to +125°CChip operating temperature+175°C Chip-to-ambient thermal resistance 225°C/W Chip-to-case thermal resistance 65°C/WMaximum instantaneous voltage at Video output +12V Supply voltage+9VAPPLICATIONSs Logarithmic IF Strips wlth Gains up to 108dB andLinearity better than 1dBFig.1 Pin connections - bottom viewCM8Fig.2 Circuit diagram SL521DS3606 - 2.0ADVANCE INFORMATIONSL521ELECTRICAL CHARACTERISTICSThese characteristics are guaranteed over the following conditions (unless otherwise stated)Temperature = +22°C + 2°C Supply voltage = +6VDC connection between input and bias pins.B 140170 MHz 10 ohms source, 8pF loadC 130170MHz Lower cut-off frequency (Fig. 3) A B C 5 7 MHz 10 ohms source, 8pF loadA B C 2ns Maximum rectified video output A 1.00 1.10 mA B 0.95 1.15 mA f = 60MHz, 0.5V rms inputC 0.901.20mA Note: Overload occurs when the input signal reaches a level sufficient to forward bias the base-collector junction to TR2 on peaks.Fig.3 Voltage gain v. frequency (typical)Fig.4 Rectified output current v. input signal (typical)SL521Fig.5 Maximum rectified output current v. temperature(typical)Fig.6 Noise figure v. temperature (typical)Fig.7 Input admittance with open-circuit output (typical)Fig.8 Direct Coupled amplifiersFig.9 Suitable interstagetuned circuitOPERATING NOTESThe amplifiers are intended for use directly coupled, as shown in Fig 8.The seventh stage in an untuned cascade will be giving virtually full output on noise.Noise may be reduced by inserting a single tuned circuit in the chain As there is a large mismatch between stages a simple shunt or series circuit cannot be used The choice of network is also controlled by the need to avoid distorting the logarithmic law; the network must give unity voltage transfer at resonance A suitable network is shown in Fig 9. The value of C1 must be chosen so that at resonance its admittance equals the total loss conductance across the tuned circuit Resistor R1may be introduced to improve the symmetry of filter response,providing other values are adjusted for unity galn at resonance.A simple capacitor may not be suitable for decoupling the output line if many stages and fast rise times are required.Alternative arrangements may be derived, based on the parasitic parameters given.Values of positive supply line decoupling capacitor requlred for untuned cascades are given below. Smaller values can be used in high frequency tuned cascades.The amplifiers have been provided with two earth leads to avoid the introduction of common ground lead inductance between input and output circuits. The equipment designer should take care to avoid the subsequent introduction of such inductance.The 500pF supply decoupling capacitor has a resistance of, typically, 1 0Q. It is a junction type having a low breakdown voltage and consequently the positive supply current will increase rapidly if the supply voltage exceeds 7.5V (see Absolute Maximum Ratings).SL521Current from pin 2Voltage at pin 6= = 0.003Effective voltage induced at pin 6Voltage at pin 4= = 20 mmhosParasitic Feedback Parameters (Approximate)The quotation of these parameters does not indicate that elaborate decoupling arrangements are required, the amplifier has been designed specifically to avoid this requirement. The parameters have been given so that the necessity or otherwise of further decoupling, may become a matter of calculation rather than guesswork.I4V 6~RF current component from pin 4Voltage at pin 6(This figure allows for detector being forward biased by noise signals).V 4V 6= = 6 mmhos (f = 10MHz)I 2V 6Voltage induced at pin 6Voltage at pin 2 = = 0.03 (f = 10MHz)Voltage at pin 2(pin joined to pin 7 and fed from 300Ω source)Voltage induced at pin 6Voltage at pin 2 = = 0.01 (f = 10MHz)Voltage at pin 2(pin 7 decoupled)I2V 6decrease with frequency above 10MHzat 6dB/octaveHEADQUARTERS OPERATIONSGEC PLESSEY SEMICONDUCTORS Cheney Manor, Swindon,Wiltshire SN2 2QW, United Kingdom.Tel: (0793) 518000Fax: (0793) 518411GEC PLESSEY SEMICONDUCTORSP.O. Box 6600171500 Green Hills Road,Scotts Valley, California 95067-0017,United States of America.Tel: (408) 438 2900Fax: (408) 438 5576This publication is issued to provide information only which (unless agreed by the Company in writing) may not be used, applied or reproduced for any purpose nor form part of any order or contract nor to be regarded as a representation relating to the products or services concerned. No warranty or guarantee express or implied is made regarding the capability, performance or suitability of any product or service. The Company reserves the right to alter without prior knowledge the specification, design or price of any product or service. Information concerning possible methods of use is provided as a guide only and does not constitute any guarantee that such methods of use will be satisfactory in a specific piece of equipment. It is the user's responsibility to fully determine the performance and suitability of any equipment using such information and to ensure that any publication or data used is up to date and has not been superseded. These products are not suitable for use in any medical products whose failure to perform may result in significant injuryor death to the user. All products and materials are sold and services provided subject to the Company's conditions of sale, which are available on request.CUSTOMER SERVICE CENTRES•FRANCE & BENELUX Les Ulis Cedex Tel: (1) 64 46 23 45 Fax : (1) 64 46 06 07 •GERMANY Munich Tel: (089) 3609 06-0 Fax : (089) 3609 06-55 •ITALY Milan Tel: (02) 66040867 Fax: (02) 66040993 •JAPAN Tokyo Tel: (03) 5276-5501 Fax: (03) 5276-5510•NORTH AMERICA Scotts Valley, USA Tel (408) 438 2900 Fax: (408) 438 7023. •SOUTH EAST ASIA Singapore Tel: (65) 3827708 Fax: (65) 3828872 •SWEDEN Stockholm, Tel: 46 8 702 97 70 Fax: 46 8 640 47 36 •UK, EIRE, DENMARK, FINLAND & NORWAY Swindon Tel: (0793) 518510 Fax : (0793) 518582These are supported by Agents and Distributors in major countries world-wide.© GEC Plessey Semiconductors 1994。

ABB REX 521 馈线和电动机保护继电器 说明书

ABB REX 521 馈线和电动机保护继电器 说明书

REX 521 馈线和电动机保护继电器操作手册如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********馈线和电动机保护继电器 操作手册3REX 5211MRS755714发布日期18.07.2005版本B/17.02.2006目录1.关于本手册 (7)1.1.本手册.................................................71.2.符号的使用.............................................71.3.相关文件...............................................71.4.文件修订版 (8)2.安全信息 (9)3.引言 (11)3.1.REX 521保护继电器 (11)4.说明 (13)4.1.HMI 的特点 (13)4.2.按钮功能 (15)4.2.1.选择语言 (16)4.2.1.1.使用按钮组合更改语言 (16)4.2.2.选择保护功能命名 (17)4.2.3.密码 (17)4.2.4.显示背光 (18)4.2.5.显示器对比度 (18)4.2.6.显示器测试 (18)4.2.7.选择一次侧值 (19)4.2.8.带光隔离的串行通讯端口 (19)4.3.菜单图 (20)4.3.1.测量菜单 (21)4.3.2.事件菜单 (22)4.3.3.手动控制 (23)4.3.3.1.就地/远方位置选择 (23)4.3.3.2.控制断路器 (24)4.3.4.整定参数 (26)4.3.5.整定掩码 (26)4.4.指示信息 (27)4.4.1.保护指示 (28)4.4.2.自检 (28)4.4.3.状态监视 (29)4.5.LED 指示灯 (30)4.5.1.绿色指示LED 就绪 (30)4.5.2.黄色指示LED 启动 (30)4.5.3.红色指示LED 跳闸 (31)4.5.4.告警LED1-8.....................................31版本馈线和电动机保护继电器报警通信端口如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********41MRS755714馈线和电动机保护继电器操作手册REX 521 5.测试模式 (33)5.1.I/O 测试 (33)5.2.IRF 测试 (34)5.3.功能模块测试 (34)6.缩写词 (35)7.索引 (37)装置内部故障测试如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********版权本文件中的信息如有更改恕不另行通知文件内容不应视为ABB Oy(芬兰)的承诺ABB Oy(芬兰)对本文件中可能出现的任何错误均不承担责任对于因使用本文件而产生的任何性质或类型的直接间接特殊偶然或必然损害以及因使用本文件中描述的软件或硬件而产生的偶然或必然损害ABB Oy(芬兰)均不承担任何责任未经ABB Oy(芬兰)的书面允许不得复制或复印本文件的任何部分不得将其内容告知第三方或进行未经授权的应用本文件中的软件或硬件受许可证保护只有在符合许可条款的情况下才能使用复制或公开版权所有© 2006 ABB Oy 保留所有权利商标ABB 是ABB集团的注册商标本文件中提到的所有其它品牌或产品名称可能是其所有者的商标或注册商标担保请向最近的ABB办事处咨询担保条款1MRS755714REX 5215馈线和电动机保护继电器操作手册如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182******** 61MRS755714REX 5217馈线和电动机保护继电器 操作手册1.关于本手册1.1.本手册本手册旨在向用户提供关于REX 521 馈线和电动机保护继电器的基本信息着重说明人机界面(HMI)的使用关于本继电器的新特点请参见REX 521技术参考手册概述(参见第7页相关文件)1.2.符号的使用本出版物包含的下列图标表示与安全相关的状况或其它重要信息尽管预警危险关系到人身伤害但必须明确在特定操作条件下运行损坏的设备将导致运行性能下降从而造成人身伤害或死亡因此须严格遵守所有预警和警告说明1.3.相关文件关于REX 521的手册电气预警图标表示存在可能导致电击的危险警告图标表示与本文中所讨论的概念相关的重要信息或预警信号表示存在可能导致软件瘫痪设备损坏或财产损失的危险信息图标提醒读者相关事实和条件•技术参考手册通用1MRS751108-MUM •技术参考手册标准配置1MRS751802-MUM •安装手册1MRS755713•功能模块技术说明(CD-ROM)1MRS750889-MCD •REX 521 Modbus远方通信协议技术说明1MRS755017•REF54_,RET54_和REX 521 DNP 3.0远方通信协议,技术说明1MRS755260如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********81MRS755714馈线和电动机保护继电器 操作手册REX 521REX 521参数和事件列表专用工具手册1.4.文件版本•REX 521参数列表1MRS751999-RTI •REX 521事件列表1MRS752000-RTI •REX 521一般参数1MRS752156-RTI •REX 521互操作性列表1MRS752157-RTI •CAP505安装和调试手册1MRS751273-MEN •CAP505操作手册1MRS751709-MEN •CAP505协议映射工具操作手册1MRS755277•继电器和终端装置用户指南1MRS752008-MUM •CAP501安装和调试手册1MRS751270-MEN •CAP501操作手册1MRS751271-MUM 版本日期历史A 18.07.2005创建文件B 17.02.2006由英文修订版1MR751107,rev.F 翻译而成如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********1MRS755714REX 5219馈线和电动机保护继电器操作手册2.安全信息即使切断辅助电源后在接线端子上也会出现危险电压不遵守上述说明可能导致死亡人身伤害或重大财产损失只允许由有资质的电工进行电气安装必须始终遵守国家和当地电气安全法规必须将该装置机架良好接地设备中包含有对静电放电敏感的元件因此应避免不必要地接触电子元件损坏装置背板上的封条将无权要求保修并不再确保正常的运行如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182******** 101MRS755714REX 52111馈线和电动机保护继电器操作手册3.引言3.1.REX 521 馈线和电动机保护继电器REX 521 馈线和电动机保护继电器设计用于在中压电力系统中进行保护控制测量和监控典型的应用包括进出馈线以及变电站保护保护继电器配有用于常规电流和电压互感器的交流量输入端此外该继电器还提供含电流和电压传感器输入的硬件版本该继电器基于多处理器环境HMI 包括一个LCD(液晶显示器)具有不同的视图便于本地使用并通过指示信息通知用户在硬件和软件解决方案中采用现代技术REX 521是用于配电自动控制中变电站自动控制概念的一部分进一步扩展了系统的功能和灵活性如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182******** 121MRS755714REX 52113馈线和电动机保护继电器操作手册4.说明4.1.HMI 的特点•导航按钮[C]清除/取消 和[E]确认/回车•语言选择•通过密码保护整定值•显示背光•可调节显示对比度•显示测试•选择一次侧值•含光隔离的串行通信端口•三个LED 指示灯•8个可编程报警LED如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********141MRS755714馈线和电动机保护继电器操作手册REX 521A060014图.4.1.-1HMI 正视图1.报警LED2.LED指示灯跳闸, CBFP 3.LED 指示灯启动, 闭锁4.LED指示灯准备就绪, IRF, 测试模式5.LCD6.光隔串行通信口7.导航按钮8.清除/取消9.确认/回车如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********1MRS755714REX 52115馈线和电动机保护继电器操作手册4.2.按钮功能HMI 含有用于操作继电器的按钮快速点击上移[↑]或下移[↓] 箭头按钮表示在菜单中前进一步或后退一步或表示在参数整定模式中最小的上移或下移•光标停止在菜单中的第一行和最后一行在第一行中按下[↑]按钮或在最后一行中按下[↓]按钮不起作用•如果按下[↑]或[↓]按钮不放那么菜单自动滚动的速度快于快速点击按钮的速度A060108图.4.2.-1按钮下表简要描述了按钮及其功能表 4.2.-1按钮功能上移/下移这些按钮用于• 在菜单中上移和下移• 输入新的整定值时滚动参数的有效数字左移/右移这些按钮用于• 在菜单中左移和右移• 输入新的整定值时更改参数的有效数字清除/取消这些按钮用于• 退出整定模式不保存• 从子菜单返回主菜单• 清除指示信息• 选择事件子菜单时清除事件(按下按钮长达2秒)选择主菜单时清除报警LED (按下按钮长达2秒)• 复归自保持输出继电器(按下按钮长达5秒)确认/回车该按钮用于• 用于进入参数的整定模式• 用于确认整定参数的新值• 配合使用[↑]或[↓]按钮调节显示对比度如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********161MRS755714馈线和电动机保护继电器操作手册REX 5214.2.1.选择语言图.4.2.1.-1选择语言1.通过[↓]和[→ ]按钮在主菜单中选择软件配置在组菜单中选择常规在子组菜单中选择软件以及在参数菜单中选择当前语言2.按下[E]按钮直到显示器的第二行开始闪烁然后用[↓]和[↑]按钮选择需要的语言3.再次按下[E]按钮确认选择或按下[C]按钮取消选择更改语言后菜单中的文字将用新的语言切断电源后恢复该选择4.2.1.1.使用按钮组合更改语言同时按住[← ]和[E]按钮5秒钟,将语言从英语更改为其它语言或从其它语言更改为英语该按钮组合可以在HMI菜单结构的任意位置使用所选的当前语言在继电器复位或电源断开后重新工作时将被恢复(清除/取消)&(确认/回车)同时按下这些按钮长达5秒• 复归自保持输出继电器事件以及保护功能已动作的记录值• 清除故障录波数据左移 & (确认/回车)同时按下两个按钮5秒• 将HMI 的语言从英语更改为其它语言或者从其它语言更改为英语表 4.2.-1按钮功能续++如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********1MRS755714REX 52117馈线和电动机保护继电器操作手册4.2.2.选择保护功能命名用户可以选择功能模块命名规则有ANSI 和IEC 两个选项可供使用它们分别遵循ANSI 标准和IEC标准保护功能命名规则导航至软件配置\显示\保护功能命名规则然后选择ANSI 或IEC所作的修改立即生效4.2.3.密码图.4.2.3.-1密码菜单通过密码保护整定值有两个不同的密码一个密码用于保护HMI整定值另一个密码用于通过串行通信保护整定值• 串行通信密码的缺省值为001HMI 的缺省密码为999•在更改缺省值之前HMI密码无效更改密码之后只要在整定值菜单中按下[E]按钮继电器就提示需要输入密码一旦给定正确的密码它将一直保持有效直到显示器由于超过时限而返回空闲状态要禁用HMI 密码应将其更改回缺省值999•如果忘记密码那么可以通过串行通信查看并更改HMI密码选择Chinese (中文)时一些IEC 保护功能名称将被译成中文如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********181MRS755714馈线和电动机保护继电器操作手册REX 5214.2.4.显示背光显示器的背光在正常情况下是关闭的按下HMI 上的按钮时背光将自动打开操作面板就绪等待下一步的操作•上电时在显示测试期间背光也打开•超过时限之后(5分钟)如果不操作面板那么背光自动关闭•通过开关量输入在就地/远方模式之间切换时背光打开长达10秒4.2.5.显示器对比度显示器对比度为温度补偿型这表示自动根据温度调节对比度保持可读性•要获取最佳可读性可调节显示器的对比度同时按下[E] 按钮和[↑]或[↓]按钮可增大或降低对比度A060114图.4.2.5.-1调节显示器对比度•可以在菜单的任何地方调节显示对比度但整定菜单除外该菜单中的[E]按钮用于进入整定模式•在非易失性记忆芯片中存储选中的对比度值当辅助电源产生故障后系统会自动恢复该对比度4.2.6.显示器测试连接辅助电源时背光打开系统将进行短时间的显示器测试该显示器测试包括所有LED 和LCD 在LCD 显示两个模式时同时打开所有LED 进行测试从而可以激活所有像素测试后显示器返回正常状态也可以通过导航到软件配置\显示\测试显示然后选择测试显示(参见第20页菜单图选择)如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********1MRS755714REX 52119馈线和电动机保护继电器操作手册4.2.7.选择一次侧值可直接获取与一些数量有关的整定值输入数据和记录值(单位为A 或V)为使继电器能够在一次侧值和二次侧值之间转换那么需要正确设置传感器或互感器(CTVTVD RS)的整定值1.导航到软件配置\显示\按一次侧值显示然后选择按一次值显示以代替按继电器额定电流倍数显示缺省值2.导航到软件配置\测量设备然后输入在每个互感器或传感器中使用的相关数据参见通用技术参考手册(参见第7页相关文件)以获取整定保护装置的额定值以及测量设备的技术数据信息4.2.8.带光隔离的串行通信端口保护继电器的前面板配有一个光隔离串行通信接口通过一条通信电缆型号为1MKC950001-2经RS-232端口与PC相连通过PC 对该继电器进行设置如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********201MRS755714馈线和电动机保护继电器操作手册REX 5214.3.菜单图菜单的内容取决于继电器不同版本的配置然而主菜单结构是不变的图.4.3.-1菜单结构图示例如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********1MRS755714REX 52121馈线和电动机保护继电器操作手册4.3.1.测量菜单测量菜单的内容取决于继电器不同版本的配置如果选择了测量菜单在超过时限之后该菜单仍然保持有效手动控制菜单也是如此对于其它菜单当背光关闭时显示器返回空闲模式•如果出现电能测量那么可通过按下[C]按钮达2秒复位累积值表 4.3.1-1测量菜单如需购买此产品欢迎联系重庆艾利顿自动化联系人:余经理 联系电话:182********热能级设备的计算热能级来自定子和转子的最大值4.3.2.事件菜单事件菜单主菜单\测量值\事件包含功能块名称和事件它们与指示信息(参见第27页指示信息)相同事件菜单的第一个窗口显示事件数量最多为50个在列表的顶部存储最近发生的事件当选择某个事件时可通过[→ ]按钮向右移动一步可以读取所述事件的日期和时间如果所述事件为跳闸事件并且没有覆盖记录数据菜单中的数据主菜单\保护\\录波数据1\3\那么可以在日期和时间窗口中右移[→ ]将其直接跳转到相关的已记录数据 在事件的第一行中用>大于号来表示这种可能性1通过[C]按钮或[← ]按钮返回事件菜单操作与标准菜单导航相同浏览已记录数据时(如果发生下述情况)直接返回到事件菜单主菜单\测量值\事件•覆盖记录数据•在事件列表中覆盖原始事件•清除事件列表事件均存储在非易失性芯片中这意味着切断电源后再送电时也可以浏览这些事件显示这些事件时可按下[C]按钮长达2秒清除事件列表表 4.3.1-1测量菜单1.选择Chinese(中文)时无效2223图.4.3.2.-1事件视图4.3.3.手动控制4.3.3.1.就地/远方位置选择可以在控制\手动控制\就地/远方中更改控制位置•可按下[E]按钮使用[↑]和[↓]按钮选择控制模式•[E]按钮确认选中模式[C] 按钮取消选择并保持当前模式 欲知密码设置信息请参见第7页相关文件.切断辅助电源期间选中的控制位置保持不变选择就地模式时在HMI主菜单的右下角显示字符L表 4.3.3.1-1控制位置控制位置描述关闭控制禁止就地和远方操作在控制菜单中显示操作对象的当前状态就地可通过HMI 和开关量输入控制操作对象禁止远方控制远方可通过远方通信控制操作对象禁止通过HMI 和开关量输入进行控制并在控制菜单中显示被控对象的状态外部输入用于给就地/远方切换被控开关量输入当选择使用时将由开关量输入的状态来决定为就地(外部)或远方(外部)244.3.3.2.控制断路器对象控制菜单位于控制\手动控制\控制CB中在远方模式或控制关闭模式中不能进行任何控制只显示断路器的当前状态在就地模式中显示断路器的状态并可通过[→ ] 和[← ]按钮滚动可能出现的目标状态可能目标状态为分或合当选择需要的目标状态后可使用[E]按钮选择对象信息=确定出现之前系统会简要显示消息=正在准备...然后可通过[E]按钮确认该操作通过[C]按钮取消该操作如果取消该操作那么信息=终止会显示3秒然后显示断路器的当前状态如果=确认?已经显示30秒也执行同样操作请注意控制\常规\选择超时中的可调节超时将限制对象选择和控制请求之间的时间如果超时时限小于30秒它会在确认操作之前结束那么将不能控制该对象如果确认操作那么相应的过渡信息=正在分闸...或=正在合闸...显示至少4秒之后系统会显示该对象的当前状态操作对象处于闭锁状态时不可以执行选择或执行请求此时信息=已联锁3秒可以取消准备进行的操作3秒后系统会显示对象的当前状态断路器延时合闸通过在就地HMI 使断路器合闸时出于安全考虑有时可能要求延迟实际合闸操作这样操作员可以有时间远离操作位置通过这种方式可避免在发生严重故障时导致人员受伤的危险 延时是可选和可调节的参数控制/常规/断路器合闸延时用于调节延时设置范围为 0 (30)秒参数的缺省值为0表示未激活延时功能仅可对合闸操作进行延时分闸操作通常立即执行当控制位置设为远方时不使用延时如果合闸延时激活并设为15秒则将显示倒计时信息15秒后合闸14秒后合闸1秒后合闸而不显示信息正在合闸...延时结束后断路器将合闸显示信息=合闸 E=分闸如果因联锁或其它原因不能合闸将中断控制序列并在LCD 上显示故障原因直至故障清除该消息之后将再次显示信息分闸 E=合闸25在延时倒计时期间按下任一个键或改变控制位置时(当控制位置为逻辑时)可取消延时合闸操作这两种情况下在LCD上显示信息终止此外当显示信息确认时按下[C]按钮也显示终止图.4.3.3.-1手动控制选择超时设置缺省值为30秒在LCD上显示信息确认时开始计时此时若按下[E]按钮便开始计算断路器合闸延时按下[E]按钮时继电器检查选择超时的剩余时间是否大于设定的断路器合闸延时时间如果不大于则在按下[E]按钮时在LCD 上显示信息=已终止表4.3.3-1手动控制信息信息含义终止可通过用户或对象状态中的状态更改或超时时限来终止当前的操作确认等待确认选中操作[E]表示确认[C]表示取消合闸合闸由于远方或控制关闭状态而不能进行控制合闸 E=合闸合闸[E]将进行合闸合闸 E=分闸合闸[E] 将进行分闸正在合闸正在合闸秒后合闸断路器合闸延时剩余时间(单位秒)外部变化修改由开关量输入控制的就地/远方状态已经改变系统只处于外部输入模式如有必要取消当前操作失败执行控制请求失败原因在于没有联锁264.3.4.整定参数在功能模块技术说明光盘中列出整定的参数(参见第7页相关文件)1.使用按钮[↑][↓]和[→ ][← ]并使用菜单结构图作为参考进入到正确的参数2.按下[E]按钮激活整定模式3.如果已经更改HMI缺省密码那么此时将出现提示信息用以下方式输入有效密码通过[← ]和[→ ]按钮更改有效位并通过[↑]和[↓]按钮改变数值4.一旦输入密码按下[E]按钮确认现在选中的整定值开始闪烁5.使用按钮[↑][↓]和[→ ][← ]输入新的整定值6.按下[E]按钮确认7.如果修改的整定值位于许可范围内那么系统会在非易失性芯片中存储该值并且在断电后恢复该值8.如果整定值无效那么继电器显示信息为无效值提示用户该整定值超出范围而先前的整定值不变4.3.5.整定掩码事件掩码和开关组以位掩码显示带有校验和通过更改事件掩码的位可以从事件报告中添加或删除大部分事件开关组用于更改继电器功能模块的输入和输出连接图.4.3.5.-1整定模式中的位掩码在包含位掩码的菜单中只显示校验和如果进入整定模式那么在显示器最右下角会显示位(在上述示例中为位0值1)可通过输入单位值来更改位掩码的内容然而新设定的值只有在按下[E]按钮并退出整定模式之后才有效已联锁由于联锁选择对象或执行控制请求失败不允许选择对象失败原因在于没有联锁不在就地状态尝试在远方或控制关闭状态下控制对象分闸分闸由于远方或控制关闭状态而不能进行控制分闸E=合闸分闸[E]将进行合闸分闸E=分闸分闸[E]将进行分闸正在分闸正在分闸正在准备正在选择对象不确认对象状态由于未定义而不确认不能进行控制未决定的对象状态未知表4.3.3-1手动控制信息续信息含义271.使用按钮[↑][↓]和[→][←]并使用菜单结构图作为参考进入到正确的参数2.按下[E]按钮激活整定模式3.如果已经更改HMI 缺省密码那么将弹出提示信息用以下方式输入有效密码通过按钮[← ]和[→ ]更改有效位并通过按钮[↑]和[↓]改变数值4.一旦输入密码按下[E]按钮确认现在选中的整定值开始闪烁5.使用按钮[↑][↓]和[→][← ]输入新的整定值6.按下[E]按钮确认输入位值时当光标位于显示器的最右角时可以按下[→ ]按钮移动要编辑的位这样在整定期间光标不必在位编号和值之间进行前后移动从而简化程序欲获取关于每个事件意义的信息请参见REX 521事例列表在功能模块技术说明光盘中(参见第7页相关文件)4.4.指示信息有两种不同的指示信息•带LED 指示的文本信息 该类信息是来自保护功能的信息以及与涉及保护继电器自身状态的信息 (自检)•无LED 指示的文本信息该类信息是关于状态监视报警以及预警或操作帮助有关的信息指示信息具有一定的优先级如果不同类型的指示同时产生那么在显示器上会出现具有最高优先级的信息信息的优先级次序为1.内部故障CBFP 2.跳闸3.启动闭锁4.帮助信息在显示器返回到发生事件之前的有效菜单之前可以通过[C]按钮清除指示信息完成某些操作时显示帮助信息比如通过按下[C]和[E]按钮长达5秒来复位输出继电器事件和记录值时会同时显示描述该操作的帮助信息4.4.1.保护指示保护启动时将会显示保护代码(或名称)和信息启动相应的黄色LED 指示灯也点亮如果为三相或两相保护功能也显示故障相28图.4.4.1.-1启动指示如果闭锁已启动的保护将显示被闭锁的保护代码(或名称)和信息闭锁此时黄色LED指示灯闪烁图.4.4.1.-2闭锁指示如果保护力能跳闸将显示动作的保护代码(或名称)和信息跳闸红色LED 指示灯点亮此时显示故障相如果是断路器失灵保护(CBFP)发送的延迟跳闸信号那么红色指示灯开始闪烁图.4.4.1.-3跳闸指示4.4.2.自检继电器装有完善的自检系统该自检系统检查出故障后在显示屏上或在后台系统通知用户检测到故障时绿色READY(就绪)指示灯开始闪烁与此同时系统会激活自检(IRF)输出继电器此外在显示屏上显示故障信息内部错误并产生相应的事件。

Logix520说明书

Logix520说明书

Flowserve 公司,Valtek 控制产品 电话:美国 801 489 8611 51-1流体控制部安装、使用、维修说明书Logix520数字式定位器一般资料下面的说明用于按照Logix TM 500数字式定位器的要求进行开箱、安装和维修。

系列500是下面所有定位器的代号,具体数字表示某一型号的具体特征。

Logix520指明该定位器使用HART ®协议。

产品用户和维修人员在进行阀门安装、使用或维修之前,应仔细阅读本说明书。

关于阀门、执行机构以及其它辅件,Valtek 有单独的安装、使用、维修说明书。

需要时请参阅IOM1、IOM27、IOM2,以及IOM31等相关资料。

警告:本产品有电气导管连接,使用规格为0.5英寸的美国标准螺纹(NPT )或M20螺纹。

这两种螺纹看来相同,但不可互换。

用力把不相同的螺纹拧到一起会损坏设备,伤及人身,中止有害场所的使用许可。

安装之前,电气导管辅件必须与设备外壳的螺纹相配。

如果不配,应使用适合的适配器或与Flowserve 公司办公室联系。

警告:使用本设备或任何其它工艺控制产品时,必须遵守标准工业安全规程。

对于本设备来说,作为保修要求,尤其必须使用人身保护装置和起吊设备。

开箱1、 打开Logix500定位器包装箱时,应按照装箱单检查收到的产品。

每一运输包装箱内,都应装有系统和辅件清单。

警告:在用吊带起吊阀门执行机构组件时,必须注意,被吊件的重心可能在起吊点以上。

因此,必须加以支撑,以防阀门/执行机构翻倒。

否则,可能造成人身的重伤或相邻设备的损坏。

2、 如果发现运输损坏,应立即与运输公司联系。

3、 万一发生问题,请与Flowserve 公司的代理联系。

目录一般资料-------------------------------------------1 开箱-------------------------------------------------1 Logix520定位器概述----------------------------3 技术指标-------------------------------------------3 定位器的运转-------------------------------------4 组装和安装----------------------------------------4 直行程执行机构----------------------------5角行程执行机构----------------------------7定位器到执行机构的接管----------------8接线和接地指南----------------------------9接地螺钉-------------------------------------9恒流输出电压-------------------------------9起动-------------------------------------------10初始DIP开关设定-------------------------11快速校准操作-------------------------------12Logix520定位器状态工况代码----------13 HART275手持通信器---------------------------16 限位开关-------------------------------------------16 型号选择-------------------------------------16运转原理-------------------------------------16安装-------------------------------------------16起动-------------------------------------------16 故障查找-------------------------------------------18 备件套件-------------------------------------------20 安装套件-------------------------------------------20Logix500数字式定位器51-2 Flowserve公司,Valtek控制产品电话:美国801 489 8611Logix520定位器概述Logix500系列定位器是两线制、4~20毫安输入信号控制的、数字式阀位控制器,通过直行程和角行程安装,控制单作用执行机构。

ABB REX521 H50版本保护参数表

ABB REX521 H50版本保护参数表
75
工作模式
□退出□定时限□A曲线□B曲线
76
电压定值
0.10...1.60×Un
77
时间定值
0.05...300.00s
78
反时限时间系数
0.05...1.00
79
过电压保护Ⅰ段,3U>>(59-2)
80
工作模式
□退出□定时限
81
电压定值
0.10...1.60×Un
82
时间定值
0.05...300.00s
57
工作模式
□退出□定时限□标准反时限
58
□极反时限□RI-反时限□RD-反时限
59
□甚反时限□长延时反时限
60
电流定值
0.05...40.00×In
61
定时限时间定值
0.05...300.0s
62
反时限时间系数
0.05...1.00
63
灵敏角ϕb
0°...90°
64
动作方向区
□正向□反向
65
接地保护
23
工作模式
□退出□定时限□瞬时
24
电流定值
0.10...12.00×In
25
时间定值
0.05...300.00s
26
方向零序电流保护Ⅲ段,I0>→(67N-1)
27
工作模式
□退出□定时限□标准反时限
28
□极反时限□甚反时限□长反时限
29
□RD-反时限
30
动作判据
□灵敏角与U0□灵敏角
31
□I0Sin/Cos与U0□I0Sin/Cos
ABB REX521 H50版本保护参数表

TETRIX 421.521 ACDC comfort

TETRIX 421.521 ACDC comfort
保证,在说明书规定的合理使用范围内,我们为您提供一年期限的质保期。 全程质量控制体系!从每个部件的生产到最终成品,我们全程质量控制,从每个细节让产品的质量得
到保证。 在高科技方面,我们一直致力于在保证质量的基础上尽可能的应用最先进的技术,我们小心谨慎的对
待我们的每一个产品,从原材料的选择,加工到装配,我们每个焊接都做到无可挑剔。 本操作手册内容包括:机器调试、安全操作规定、维护和保养、技术参数以及质保方面的相关规
焊机可以在符合IEC 60974,EN 60974, VDE0544 防触电附加标准环境下使用。
© 2007 随时更新
标号 No.: 099-000108-EWM09
Dated: 20.04.07
SIMPLY MORE
尊敬的客户: 您好! 首先要恭喜您,因为您选择了来自EWM HIGHTEC WELDING Co.,Ltd.生产的高品质的焊接电源! EWM 先进的质量管理体系让我们很自豪的说:我们生产出来的产品近乎完美!同时我们很自信的
2
安全规则简介 ................................................................................................................................. 7
2.1
为了您的安全 ......................................................................................................................... 7
EWM 机器方盖章/签名 交货日期
3
目录

REXA操作册

REXA操作册

Mpac 开关型电液执行器操作手册Version 5.7 (03/08)目录:1概述 (1)1.1 引言 (1)1.2 维修周期 (1)1.3 需要的工具(仅仅指动力单元) (2)1.4 工作原理 (3)1.4.1 综述 (3)1.4.2执行器 (3)1.4.3 电控箱 (4)1.4.4 操作概述 (13)1.4.5 控制模式 (14)1.4.6 手动操作 (15)1.4.7 限位开关 (16)2 运输 (17)2.1 接收 (17)2.2 存储 (17)2.3 开箱 (17)3 油 (18)3.1 油位检查 (18)3.2 注油 (18)4 电控箱 (19)5 电气安装 (19)5.1 供电电源 (19)5.2 电缆 (19)5.2.1 电缆长度 (21)5.2.2 电缆走线 (21)5.3 挠性管及接头 (22)6. 执行器安装与调试 (23)6.1 安装前准备 (23)6.2 蓄能器充压 (23)6.3 安装 (23)6.4 开关极限位调整 (24)7 操作 (25)7.1 参数设置 (25)7.2 就地模式 (39)7.3 就地操作状态 (40)7.4就地状态下的阀门活动试验 (41)7.5 就地状态下的ESD (43)7.6 远控状态 (45)7.7远控状态下的活动试验 (46)7.8远控状态下的ESD (48)7.9 查询状态 (49)7.9.1 I/O状态查询 (49)7.9.2 参数查询 (50)7.9.3 指令历史查询 (51)7.9.4 故障解释 (52)7.9.5指令解释 (54)7.9.6 屏幕中的缩写 (54)安全注意事项电压冲击:执行器有可能产生电压冲击;只有有资质的安装和服务人员才能对设备进行安装和调整.对中:安装时执行器的轴孔和阀门的轴必须对中,若对中不良,将导致设备的损坏和人员的损伤。

避免突然启动:当安装执行器时确保切断电源;当执行器给电后,可能立即响应控制信号,这些不经意的动作可能对设备和人员造成损害。

rex521保护使用说明书

rex521保护使用说明书
REX 521 馈线和电动机保护继电器
用户指南
特性
REX 521 馈 线 和 电 动 机 保 护 继 电 器
1YZA000013
发布:2001.11.20 版本:G/2006. 03. 15 本公司保留数据修改权利·恕不另行通知
基本版 B01: ● 三段过流保护 ● 三段零序过流(接地)保护 ● 缺相保护 ● 热过负荷保护 ● 涌流制动 ● 电流输入回路监视 ● 电流波形畸变测量 ● 电流测量 ● 零序电流测量 ● 断路器累积电气磨损计算 ● 故障录波 ● 跳闸回路监视 ● 断路器失灵保护 ● 断路器状态监视及控制 ● 输出自保持 ● 状态监视 ● 就地 / 远方切换选择 ● 用户自定义输入 / 输出 ● 电气联锁 ● 用户自定义告警灯
感器通道采用相电压的接入方式。
高级版 H09: ● 三段过流保护 ● 三段零序电流(接地)保护 ● 两段过电压保护 ● 两段低电压保护 ● 三段零序电压保护 ● 涌流制动 ● 两段低周或过频保护 ● 电流输入回路监视 ● 电压输入回路监视 ● 电流波形畸变测量 ● 电压波形畸变测量 ● 电流测量 ● 自动重合闸(1-5 次重合) ● 零序电流测量 ● 电压测量 ● 零序电压测量 ● 频率测量 ● 三相功率和电能测量 ● 断路器累积电气磨损计算 ● 故障录波 ● 跳闸回路监视 ● 断路器失灵保护 ● 断路器状态监视及控制 ● 自保持输出 ● 状态监视 ● 就地 / 远方切换选择 ● 用户自定义输入 / 输出 ● 电气联锁 ● 用户自定义告警灯 注意:高级版 H09 提供 CT 和 PT 通道,采用相
特性(续)
REX 521 馈 线 和 电 动 机 保 护 继 电 器
● 就地 / 远方切换选择 ● 用户自定义输入 / 输出 ● 电气联锁 ● 用户自定义告警灯

高压开关柜-工作记录

高压开关柜-工作记录

龙岩龙长高速公路机电人员中高级培训培训手册中铁三局集团电务工程有限公司1.1REX521 (5)1.1.1REX521概述 (5)1.1.2REX521的操作、日常维护和常见故障处理 (6)1.2REF610 (12)1.2.1REF610概述 (12)1.2.2REF610的操作、日常维护和常见故障处理 (13)1.3RTU560 (18)1.3.1RTU560概述 (18)1.3.2通信模块CMU02 (19)1.3.3 23BA40 (19)1.3.4 23BE40 (19)1.3.5常见故障处理 (19)1.4主要设备工作状态测试 (20)2.高压开关柜 (24)2.1高压开关柜的组成、连锁 (24)2.2高压开关柜的连锁 (25)2.3高压开关柜的操作和注意事项 (26)1、断路器车 (26)2、接地开关操作 (26)2.3.1高压进线柜使用 (26)2.3.2母线PT柜使用 (27)2.3.3计量柜使用 (28)2.3.4高压馈线柜使用 (29)2.4高压开关柜的常见故障处理 (30)2.5高压带电显示器 (30)2.6高压开关柜的日常维护和保养 (31)2.6.1日常维护 (31)2.6.2母线室母线的安装 (31)2.6.3维护注意事项 (32)3.低压开关柜 (32)3.1低压开关柜的组成和连锁方式 (32)3.1.1 结构特征 (32)3.1.2 柜体的分区设计 (32)3.1.3抽屉的电气和机械联锁 (34)3.1.4母线系统 (35)3.1.5保护接地系统 (36)3.1.6安全保护系统 (36)3.2低压开关柜的操作和注意事项 (36)3.2.1干式变压器馈线柜的操作 (36)3.2.2隧道电缆线路馈线柜的操作 (37)3.2.3时控仪的操作 (37)3.3低压开关柜的维护保养和常见故障处理 (38)3.3.1双电源切换开关的维护保养和常见故障处理 (39)4.1干式变压器的组成 (40)4.2干式变压器温度控制器的操作 (40)D1 (40)4.3干式变压器的维护保养和常见故障处理 (41)4.4干式变压器温度控制器的维护保养和常见故障出路 (41)5.地埋式变压器 (42)5.1地埋是变压器的组成 (42)5.2地埋式变压器的调整 (42)5.2.1地埋式变压器分接头的调整 (42)5.2地埋式变压器退出运行后的应急处理办法 (43)5.3地埋式变压器熔断器更换操作 (43)5.4地埋式变压器电缆头的操作 (43)5.4.1高压电缆 (43)5.4.2低压电缆 (43)5.5地埋式变压器的维护保养和常见故障处理 (44)5.5.1巡视检查的主要内容 (44)5.5.2 地埋式变压器有下列情况之一者应进行检查、处理。

REX521操作手册

REX521操作手册

REX 521 保护继电器操作手册1MRS 751107-MUM REX 521操作手册出版时间:27.6.2001版本: B/15.10.2001ABB保留对数据的修改权---------------------------------------------------------------------------------------------目录1. 简介 (4)1.1. REX 521 保护继电器 (4)2. 使用须知 (5)3.操作指导 (6)3.1. 人机界面HMI 特点 (6)3.1.1. 按钮介绍 (6)3.1.2. 选择语言 (7)3.1.3. 密码 (8)3.1.4. 显示背景荧光 (8)3.1.5. 显示对比度 (9)3.1.6. 显示试验 (9)3.1.7. 选择一次侧数值 (9)3.1.8. 光隔离的串行通行口 (9)3.2. 菜单图解 (10)3.2.1. 测量菜单 (11)3.2.2. 事件菜单 (11)3.2.3. 整定参数 (12)3.2.4. 整定数据位 (12)3.3. 提示信息 (13)3.3.1. 保护指示 (13)3.3.2. 自检 (14)3.3.3. 状态监视指示 (14)3.4. LED 指示灯 (15)3.4.1. 绿色指示灯LED (READY) (15)3.4.2. 黄色指示灯LED (START) (15)3.4.3. 红色指示灯LED (TRIP) (16)4. 服务 (17)4.1. 试验模式 (17)4.1.1. I/O 试验 (17)5. 参考资料目录 (18)1. 简介本手册向用户提供REX521继电器的基本情况,重点说明人机界面(HMI)的使用。

1.1. REX 521 保护继电器REX521继电器可用于中压电网的保护,控制,测量和监视。

主要用于进出线保护及变电站保护。

继电器有大容量的输入端,可以和传统的流变和压变配合使用,采用多处理器提高其性能,由强大的CPU支持的数字信号处理提高了继电器的响应时间和精度。

REX521技术参考手册

REX521技术参考手册

REX 521型微机保护继电器技术参考手册汇编上海ABB工程有限公司2002,08,181. 概述REX521建立在RED500平台上,是REF54_型馈线终端的一种简化产品。

它是综合保护、控制、测量、监视和通信为一体的微机终端。

本手册阐述REX521终端的概貌、及其配置。

首先是概述,第二部分逐项描述了基本配置和中级配置等两种的标准配置的概况,第三部分到第六部分介绍了信号路径及其功能,第七部分为应用举例。

最后是附录,为原版Copy的技术数据和外部结线图,以供查阅防止误导。

REX 521 和RED 500 平台在功能模块介绍上的不同在CD-ROM“功能的技术介绍” (1MRS 750889-MUM)的功能模块的介绍方面, REX521 和RED 500 平台在某些方面有所不同。

首先,某些术语是指其他产品而不是REX521,其次,有某些数据仅适用于REX521:• 在试验某一功能模块时,READY 指示灯闪烁。

• 事件标识位1仅适用于SPA 通讯。

• 不能实现直接控制自动重合闸的功能。

REX521输入、输出量一览表:REX521的输出继电器接点能力REX521 机箱安装尺寸:请参阅下图中的标准19英寸的1/3 (表中第二项)。

REX521的整定范围一览表:REX521的通信串口:面前一个背后两个,全是光纤通信口。

背后串口的通信规约LON/IEC/SPA 可选。

表1.-1 REX 521的两种标准配置表1.-2 REX521的保护功能表1.-3 REX521的控制功能表 1.-4 REX521的测量功能表 1.-5 REX 521的状态监测功能表 1.-6 REX 521电源质量监视功能基本配置和中级配置的主要区别在于,中级配置增加了方向接地保护。

B01和B02以及M01和 M02之间的区别是,B02 和M02增加了自动重合闸功能。

2. 信号路径总图表示除模拟量信号外的输入、输出的功能控制的耒龙去脉的信号路径图图:2.-1 信号路径总图概念2.1. 数字量输入为了实现不同的功能,数字量输入(DI1...DI9) 要连接到功能模块的输入口,或直接连接到输出回路。

优利德UT521使用说明书

优利德UT521使用说明书

序 言尊敬的用户:您好!感谢您选购全新的优利德仪表,为了正确的使用本仪表,请您在本仪表使用之前仔细阅读本说明书全文,特别有关“安全注意事项”的部分。

如果您已经阅读完本说明书全文,建议您将此说明书进行妥善的保管,与仪表一同放置或者放在您随时可以查阅的地方,以便在将来的使用过程中进行查阅。

目录项目 页1一、安全提示二、特性三、技术规格四、仪器外观及配件五、测量前准备六、测量方法七、保养和维修2569101017一、安全提示本说明书包括确保仪器安全使用必须遵守的注意事项和安全规则,因此使用前请务必认真阅读。

在使用本仪器之前,请阅读并理解本说明书所包括的内容。

本说明书要妥善保管,以便随时为测试作参考。

使用本仪器必须严格按照本说明书中描述测试步骤进行。

请务必详细了解本说明书中有关安全方面的内容。

一定要严格遵守相关安全规则,否则可能导致伤害事故或仪器损坏。

23的操作。

请勿在有易燃易爆的环境下测试,否则可能会产生火花引起爆炸。

当本仪器潮湿或使用者的手潮湿的时候请勿做接线动作。

请勿施加超过本仪器的容许界限或测试范围的电量。

当您正在测试时请不要打开电池盖。

4请一定不要在出现任何不正常情况的时候进行测试。

如:胶壳破裂,测试线断 裂、脱皮外露等。

请用户不要随意拆装本仪器,若需维修请与本公司售后服务部或代理处联系。

当仪器表面湿滑,请不要更换电池或打开电池门,需先用干布擦干后再进行。

若需更换电池或打开电池门,请在关机后进行。

测试前请确认测试线的连接插头都已紧密的插入相应端口内。

当仪器在很长时间不使用时,请把电池取出并放置好。

不要把本仪器暴露在极端温度和潮湿等恶劣环境中。

请用湿布或中性清洁剂去清洁本仪器,不要用磨剂或溶剂。

当本仪器潮湿时,请确定使其干燥后储存。

本仪器中图形标志有以下几种,使用时请注意其内容:表示危险、警告、注意标志 表示有双重绝缘或强化绝缘保护表示交流(AC) 接地符合欧洲共同体(European Union)标准二、特性本仪器采用智能微控制器芯片控制,具有高精度和高可靠性;可用于测量各种电力设施配线,电气设备,防雷设备等接地装置的接地电阻值,还可以进行接地电压测量。

浅谈变电所PT断线及备自投保护功能的应用

浅谈变电所PT断线及备自投保护功能的应用

94一、选题背景39/149变电所是为动力厂锅炉装置、二套除盐水、除油除铁及厂前化工园区和生活区供电的6kV变电所。

该所始建于1991年11月,2005年通过改造,将继电保护装置改为ABB REX521系列微机保护装置,至今14年。

微机保护装置已超过厂家承诺的十年无故障质保期,在实际运行中存在较多问题,不利于安全长周期供电。

二、存在问题1.原设计选用的ABB REX521系列微机保护装置无PT断线功能,通过测量模块设置搭接完成的PT断线经调试无法实现该功能,如图A,可靠性低、故障率高,不利于继电保护安全运行;图A ABB微机保护装置PT断线逻辑图2.微机保护装置于2005年开始使用,超过10年安全使用期限,出现了不定期故障报警、死机、元器件老化、键盘不灵敏等问题,存在安全隐患。

3.原有进线微机保护装置无电压采集功能,两段电压均输入母联装置,通过逻辑判断后用于备自投功能,这种方式增加了进线与母联的联络电缆和连接点,无形中增加了故障点,且与我车间其他变电所备自投逻辑不同,不利于运行维护人员维护。

三、问题改进为了解决目前存在的问题,提高继电保护工作人员的技能水平,解决生产过程中的瓶颈问题,对39/149变电所继电保护进行完善。

1.更换微机保护装置,将A B B R E X521微机保护装置更换成西门子7SJ62系列微机保护装置。

2.在西门子7SJ62 4.9版本中实现PT 断线功能。

(1)首先开启西门子7SJ62 4.9版本中的VT断线功能,如图B。

图B PT断线逻辑配置图3.2.2由于PT断线功能需闭锁低电压保护,在I/O矩阵中进行闭锁低电压配置,如图C。

图C 闭锁低电压逻辑配置图(2)通过CONNECT功能块,将PT断线逻辑及闭锁低电压保护逻辑信息连接起来,实现PT断线功能,可靠闭锁低电压保护,如图D,提高供电可靠性。

图D PT断线逻辑及闭锁低电压逻辑连接图3.由于该所进线是由两个供电系统进行供电,不能并联,备自投功能长期退出。

rex521保护使用说明书

rex521保护使用说明书
中级版 M02: ● 三段过流保护 ● 三段方向零序过流(接地)保护 ● 缺相保护 ● 热过负荷保护 ● 涌流制动 ● 电流输入回路监视 ● 电流波形畸变测量
3
特性(续)
4
REX 521 馈 线 和 电 动 机 保 护 继 电 器
● 电流测量 ● 零序电流测量 ● 零序电压测量 ● 断路器累积电气磨损计算 ● 故障录波 ● 跳闸回路监视 ● 断路器失灵保护 ● 自动重合闸(1-5 次重合) ● 断路器状态监视及控制 ● 输出自保持 ● 状态监视 ● 就地 / 远方切换选择 ● 用户自定义输入 / 输出 ● 电气联锁 ● 用户自定义告警灯
基本版 B02: ● 三段过流保护 ● 三段零序过流(接地)保护 ● 缺相保护 ● 热过负荷保护 ● 涌流制动 ● 电流输入回路监视 ● 电流波形畸变测量 ● 电流测量 ● 零序电流测量 ● 断路器累积电气磨损计算 ● 故障录波 ● 跳闸回路监视 ● 断路器失灵保护 ● 自动重合闸(1-5 次重合) ● 断路器状态监视及控制
高级版 H06: ● 两段过流保护 ● 两段过电压保护 ● 两段低电压保护 ● 三段零序电压保护 ● 两段频率保护 ● 电流输入回路监视 ● 电压输入回路监视 ● 电流波形畸变测量 ● 电压波形畸变测量 ● 电流测量 ● 零序电流测量 ● 电压测量 ● 零序电压测量 ● 频率测量 ● 三相功率和电能测量 ● 断路器累积电气磨损计算 ● 故障录波 ● 跳闸回路监视 ● 断路器失灵保护
通道。
应用
REX 521 馈 线 和 电 动 机 保 护 继 电 器
REX 521 用途广泛,可用在输、配电网络上作 保护、控制和监视,可用于不同电压等级的中 性点接地、小电阻接地、中性点不接地和谐振 接地的网络。该装置既适用于辐射网也用于环 状网,既适用于单端供电系统也可用于多端供 电的线路。
  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

REX 521型微机保护继电器技术参考手册汇编上海ABB工程有限公司2002,08,181. 概述REX521建立在RED500平台上,是REF54_型馈线终端的一种简化产品。

它是综合保护、控制、测量、监视和通信为一体的微机终端。

本手册阐述REX521终端的概貌、及其配置。

首先是概述,第二部分逐项描述了基本配置和中级配置等两种的标准配置的概况,第三部分到第六部分介绍了信号路径及其功能,第七部分为应用举例。

最后是附录,为原版Copy的技术数据和外部结线图,以供查阅防止误导。

REX 521 和RED 500 平台在功能模块介绍上的不同在CD-ROM“功能的技术介绍” (1MRS 750889-MUM)的功能模块的介绍方面, REX521 和RED 500 平台在某些方面有所不同。

首先,某些术语是指其他产品而不是REX521,其次,有某些数据仅适用于REX521:• 在试验某一功能模块时,READY 指示灯闪烁。

• 事件标识位1仅适用于SPA 通讯。

• 不能实现直接控制自动重合闸的功能。

REX521输入、输出量一览表:REX521的输出继电器接点能力REX521 机箱安装尺寸:请参阅下图中的标准19英寸的1/3 (表中第二项)。

REX521的整定范围一览表:REX521的通信串口:面前一个背后两个,全是光纤通信口。

背后串口的通信规约LON/IEC/SPA 可选。

表1.-1 REX 521的两种标准配置表1.-2 REX521的保护功能表1.-3 REX521的控制功能表 1.-4 REX521的测量功能表 1.-5 REX 521的状态监测功能表 1.-6 REX 521电源质量监视功能基本配置和中级配置的主要区别在于,中级配置增加了方向接地保护。

B01和B02以及M01和 M02之间的区别是,B02 和M02增加了自动重合闸功能。

2. 信号路径总图表示除模拟量信号外的输入、输出的功能控制的耒龙去脉的信号路径图图:2.-1 信号路径总图概念2.1. 数字量输入为了实现不同的功能,数字量输入(DI1...DI9) 要连接到功能模块的输入口,或直接连接到输出回路。

以对任何个数字量输入(DI1...DI9) 进行编程,进行信号极性的转换,设定延时的过滤。

数字量输入和不同的功能块之间的连接路径由选择器和切换组(SWGRP)实现。

2.1.1. 输入选择器每个数字量输入(DI1...DI9)能连接到特定的输入信号。

2.1.2. 输入切换组(SWGRP)切换组用电子开关来将特定的输入信号连接到一个或数个功能模块的输入口。

2.1.3. 输入信号下图所示为输入信号部分。

图:输入信号路径图解图中至SCADA系统的对象状态指示功能模块1<->0 IND1 和1<->0 IND2 用于通过通讯口向变电站监控系统传送事件,事件为隔离开关位置(分/合)和接地闸刀位置(分/合)状态。

2.2. 信号路径总图中的功能模块每一个标准配置的所有功能模块见下图.2.-1。

不同配置的继电器有不同种类的功能块。

图:2.-1 信号路径总图中的功能模块2.3.1输出切换组(SWGRP)用输出切换组用电子开关型式将每一个功能模块的特定输出(如启动,跳闸和报警信号)引接至特定输出信号,如Trip 2。

2.3.2 输出选择器用输出选择器将输出信号(如Start1,Trip1)引接至输出继电器(如PO1,HSPO1,SO1)。

2.4. 信号总图中的其他功能24.1. 保持(Lockout)功能保持(Lockout)功能是使跳闸出口继电器(HSPO)具有自保持的特性。

用输入选择器将数字量输入(DI1---DI9)中的一个连接到(Lockout reset )解除自保持的作用端,就可以对该功能进行复归。

注意,不能按[C] 或 [C] +[E] 按钮来清除跳闸LED指示,除非对保持(Lockout)进行复归。

在上图中,为了内部闭锁,Lockout working 信号被内部连接到COCB断路器控制功能模块的CLOSEENA 输入口。

这表示如果保持(Lockout)功能启动,则不允许进行控制断路器的合闸操作。

保持(lockout)功能有两种应用方式:第一种方式是用HSPO1的输出来执行保持(lockout)功能。

“Lockout HSPO1” 选择器用来启动强制自保持。

已经自保持的输出继电器只能由数字量输入复归。

这种方式要有一个外部接点,该接点在允许断路器合闸操作前必须复归。

例如,一条带电动机的馈线跳闸,在电动机温度未降到允许的水平前,有必要禁止电动机的重新启动。

图:2.1.-2 保持(Lockout)功能的第一种应用方式另一种方式见图4.4.1.-3,通过为相应的输出信号选择器选择保持(lockout)功能,对选定的输出继电器,如PO1,选择保持(Lockout)信号,将断路器合闸控制回路和一个大容量输出继电器PO1串联。

图:2.4.1.-3 保持(lockout)功能的另一种应用注意,当使用了保持(lockout)功能并发生了辅助电源失电时,输出继电器回复到无电状态。

当外部保持(lockout)功能和输出继电器PO1, PO2, PO3, SO11和SO21配合使用,并发生了辅助电源失电时,会有同样的情况。

保护继电器重新恢复电源时,输出继电器回复到失电前的状态,用于保持(lockout)功能的输出继电器带电。

如果保持(lockout)功能和HSPO1继电器配合使用,保护继电器的电源未接上时,也能实现对断路器的控制。

为最大限度的保证使用保持(lockout)功能时的安全性,建议使用电池作为辅助电源,这样保护对象的故障不会影响对保护继电器的辅助电源,保持(lockout)功能的状态回存储在保护继电器的记忆中。

3.数字量输入的编程数字量输入用于执行不同的功能,例如通过对选择器和切换组编程复归所需要的功能模块。

图:5.-1 选择器选项3.1. 输入选择器。

具有如下功能输出:3.1.1. 复归功能 (Reset 1, Reset 2 )将输入DI1—DI9中的任何一个用于复归自保持的跳闸信号和功能的记录数据(如O/C, E/F, Iub>,3Ith>,PQ3Inf1)。

3.1.2. 整定值组切换功能 (Group )用于将保护功能块的整定值在整定值组1和整定值组2之间切换。

3.1.3. 闭锁功能 (Blocking 1, Blocking 2 )每个保护功能块具有不同作用的闭锁端BS1和BS2。

Blocking 1连接至相关保功能块的BS1,而连接至相关保护功能块的BS2。

3.1.4. 触发故障录波功能 (DREC trig )用于启动故障录波器3.1.5. 触发电源质量记录 (PQ 3Inf trig )用于启动对电源质量的测量记录。

3.1.6. 零序方向元件的灵敏角控制功能 (BACTRL )3.1.7 主跳功能 (Master trip )主跳功能不经过联闭锁程序直接连接到快速跳闸继电器HSPO1进行跳闸。

3.1.8. 外部跳闸功能 (Extermal trip )外部跳闸信号不经过联闭锁程序可以接到输出继电器PO1...PO3 和SO1...SO2 .3.1.9.解除自保持功能(Lockout reset)3.1.10. 就地 / 遥控操作方式的切换功能 ( Remote )就地模式时,只能通过二进制输入而不能通过通讯口,对断路器进行控制。

在遥控模式时,只能通过通讯口进行控制。

3.1.11. 允许合闸 (Close enable )不论由数字量输入或通讯口发合闸命令均要接受允许合闸的条件的检验才能进行合闸。

3.1.12. 直接控制分,合闸 (open /close )用于控制断路器的分、合闸。

3.1.13. 设备状态指示 (Object indication )用于发送给MicroSCADA系统显示相关设备的状态。

并且可作为联锁逻辑的编程的要素。

其中又分:CB pos. open ---断路器分闸位置 CB pos. close---断路器合闸位置DC pos. open ---闸刀分闸位置 DC pos. close---闸刀合闸位置ES pos. open—接地闸刀分闸位置 ES pos. close--- 接地闸刀合闸位置时间同步数字量输入9 用于GPS 时间同步输入。

3.1.14. 外部控制重合闸的功能 (0→1 Ext. start , 0→1 trip )用于外部控制重合闸功能块的启动,禁止或投入。

3.1.15. 逻辑输入1...3 (Logic 1 ~Logic 3 )是联锁逻辑编程的外部条件输入端。

3.2.互联闭锁 ( Interlocking )I<->O CB1功能模块的CLOSEENA输入口可以发允许断路器合闸命令。

用图5.2.-1 和图 5.2.1.-4所示的联闭锁逻辑,可以建立允许合闸的不同逻辑。

接地闸刀和隔离开关的逻辑状态,以及数字量输入(DI1...DI9) 可以用图5.2.-1.所示的联锁逻辑同时使用。

图:3.-1 联闭锁3.2.3.2.1.互联闭锁选项联闭锁选项仅包括断路器合闸。

断路器分闸一般总是允许的。

通过人机或继电器整定工具(Main menu\Configuration\Input Signals\Close enable)进行整定,可以人工整定联闭锁为TRUE 或不连接(FALSE)。

直接用数字量输入可以直接选择数字量输入(DI1...DI9) 中的一个来允许合闸。

用继电器菜单中名为“Closeena”的选择器或继电器整定工具选择输入。

进一步的,从总数字量输入菜单中选择输入延时和转换。

逻辑状态1为允许合闸,逻辑状态0不允许断路器合闸。

用接地闸刀状态如果接地闸刀的状态指示信号接到数字量输入并连接到ES pos. open 和 ES pos. Close,这些位置指示可以包含在联闭锁逻辑里。

信号“i nterlocking_A”在接地闸刀合上时逻辑值为0,接地闸刀分开时,逻辑值为1。

在“Closeena” 选择器中选择“Interlocking_A”,就可以用这个信号来允许合闸。

图:3.2.1.-1 用接地闸刀状态联闭锁用隔离开关状态如果隔离闸刀的状态指示信号接到数字量输入并连接到DC pos. Open和DC pos. Close,这些位置指示可以包含在联闭锁逻辑里。

信号“Interlocking_A”在隔离开关合上时逻辑值为0,隔离开关分开时,逻辑值为0。

在“Closeena” 选择器中选择“Interlocking_A”,就可以用这个信号来允许合闸。

图:3.2.1-2 用隔离开关状态联闭锁用隔离开关和/或接地闸刀状态如果同时用接地闸刀和隔离开关指示并连接到DC pos. open, DC pos. close, ES pos. open 和ES pos. Close,这些状态指示可以包含在联闭锁逻辑里。