1、General
SPB-XSL16 Series applies to measure, alarm and retransmit 2-16 channel signals of thermocouple and RTD. Ø Basic intrinsic error is less than 0.2%, indication range is -1999~9999. Ø The signal type, range, alarm value of each channel can be set separately.
Ø
Digital filtering time coefficient of each channel, which can improve anti-interference ability, can be set separately.
Ø
Zero and full scale rectification, which can effectively reduce sensor errors to improve measuring accuracy, can be set separately.
Ø Channels unused can be shut at will.
SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china Fax :0086-512-68381803 2
SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china 3
2、Technical Specifications
Input RTD :Pt100,Cu100,Cu50,BA1,BA2,G53. Display solution is 0.1℃ for full range and disconnection identification is available.
Thermocouple :K ,S ,R ,B ,N ,E ,J ,T
Display solution can be set to 1 or 0.1℃℃ for full range (negative temperature included) and
disconnecting identification is available
Accuracy 16-bit A/D converter
Measuring Accuracy :±0.2%F·S
Display Resolution :1/10000
Rate
200ms per channel (related to parameter )
Display 2-digit LED channel number display 4-digit LED measured value display
Alarm state indicator of all channels Alarm 3 mode of alarm 2 public relays
Relay contact capacity: 250V AC ,2A (resistance load ) Power
160V AC~260V AC ,50Hz
Circumstance Temperature :0~50℃℃
Humidity :≤90%R·H
SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china
4
3、
Installation and Wiring
For the sake of safety, turn off the power supply before wiring.
The terminal
is a common terminal of power filter, with high voltage, which can only be connected to
the earth and connecting with other terminals is FORBIDDEN . Installation 【Dimensions 】
【Cut-out Dimensions 】
【wiring 】
Input
RTD:
If the input signal is 2-wire, B and C should be shortcutting. Thermocouple: