XSL16温度巡检仪英文版

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

SUZHOU SURPON INSTRUMENT CO.,LTD

ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china Fax :0086-512-68381803

SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china Fax :0086-512-68381803 1

1、General

SPB-XSL16 Series applies to measure, alarm and retransmit 2-16 channel signals of thermocouple and RTD. Ø Basic intrinsic error is less than 0.2%, indication range is -1999~9999. Ø The signal type, range, alarm value of each channel can be set separately.

Ø

Digital filtering time coefficient of each channel, which can improve anti-interference ability, can be set separately.

Ø

Zero and full scale rectification, which can effectively reduce sensor errors to improve measuring accuracy, can be set separately.

Ø Channels unused can be shut at will.

SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china Fax :0086-512-68381803 2

SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china 3

2、Technical Specifications

Input RTD :Pt100,Cu100,Cu50,BA1,BA2,G53. Display solution is 0.1℃ for full range and disconnection identification is available.

Thermocouple :K ,S ,R ,B ,N ,E ,J ,T

Display solution can be set to 1 or 0.1℃℃ for full range (negative temperature included) and

disconnecting identification is available

Accuracy 16-bit A/D converter

Measuring Accuracy :±0.2%F·S

Display Resolution :1/10000

Rate

200ms per channel (related to parameter )

Display 2-digit LED channel number display 4-digit LED measured value display

Alarm state indicator of all channels Alarm 3 mode of alarm 2 public relays

Relay contact capacity: 250V AC ,2A (resistance load ) Power

160V AC~260V AC ,50Hz

Circumstance Temperature :0~50℃℃

Humidity :≤90%R·H

SUZHOU SURPON INSTRUMENT CO.,LTD ADD:F6hengfeng building,NO.26-6North Tongjing Road. Suzhou,Jiangsu province china

4

3、

Installation and Wiring

For the sake of safety, turn off the power supply before wiring.

The terminal

is a common terminal of power filter, with high voltage, which can only be connected to

the earth and connecting with other terminals is FORBIDDEN . Installation 【Dimensions 】

【Cut-out Dimensions 】

【wiring 】

Input

RTD:

If the input signal is 2-wire, B and C should be shortcutting. Thermocouple:

相关文档
最新文档