FOXBORO_DCS系统维护手册范本

合集下载

DCS系统作业指导书(foxboro)

DCS系统作业指导书(foxboro)

第一章 I/A Series 系统概述3. I/A Series 的网络结构图1-2 一个简单的DCS 系统配置图我厂详细的FOXBORO 系统网络图DNBIAAWAUXANNUM 操作员键盘DNBI (AW51D )AWPESTGCIOANNUMDNBIAWPP0L 1线ANNUM ACOM01PRINTER LP11PRINTER LP10TERMTT10BCOM01PRINTER LP31PRINTERLP32第1页(AW51D )应用操作站处理机通信处理机(AW51D )操作站处理机巡查房RS232转RS422原用于9期节点总线GCIO 图形控制输入输出MODULE I.D.00010000MODULE I.D.00000100GCIO MODULE I.D.00001000s erial B口s erialPCI 1槽的RJ-45接口RJ-45接口RS423P2P1P2P1中控室打印机Local RepeaterLocal Repeater LocalRepeater2线ANNUM Nodebus E thernet T ransceiver Nodebus E thernet T ransceiver Nodebus E thernet T ransceiver E 50Ω工程师键盘鼠标A口终端机节点总线以态网收发器中继器至第2页COM1COM2注:GCIO 断电10秒再电,ANMUN 全部灯闪一下控制处理机ACP601A1F100A1F300ACP602A2F300DNBI(AW51D )BAWESTGCIO ANNUMDNBI(AW51D )BWPP0LGCIO 中继器E EE E 至第3页9期K70屏(冗余)9期2楼夹层FBIFBI2线和11期公共1线FBI K25.1 屏 K25.2 屏Local RepeaterNodebus E thernet Local Repeater3线ANNUM固相ANNUMT ransceiver Nodebus E thernet T ransceiver 中继器中继器中继器(冗余)A A1F100B A1F200A A1F200BA2F100A A2F100B A2F200A A2F200B接第1页第2页BCOM15OPTIC 光纤1对MOD PCPLC001BCP601E E (AW51D )CAWESTGCIO ANNUM(AW51D )CWPP0LGCIO CCP601E E接第2页4线FCMDNBTDNBTAdapter固相ⅠN46屏 3线和固相FBI光纤转换器OPTIC 光纤转换器TDRDRDTD节点总线k25.3和 k25.5和k25.6屏s erialA口RJ-45接口Adapter5线ANNUM MODULE I.D.00010000MODULE I.D.000001004线ANNUM 注:Adapter是接线盒(冗余)(冗余)B1F100A B1F100BB1F200A B1F200B B1F300AB1F300BC01100A B ABC01100C01200C01200k25.4屏至第4页第3页DNBX(AW51B )AWPPOYGCIOANNUMACOM15RS232转CCP6025线和11期公用FCM 至第5页NOD BUS Extender PLC001RS422RS422转RS232节点总线扩展组件E E k25.7和k25.8屏T ransceiver(冗余)E(冗余)AB C02100A B AB C02100C02200C02200注:1、启动过程中Transceiver RCV 闪烁、PWR 亮2、正常运行时,Transceiver 的XMT 、RCV 闪烁,PWR 亮3、进线有问题,CLN 亮接第3页第4页DNBT(AW51D )DAWPOYDNBT(WP70)DWPP0YGCIOANNUMANNUM第5页DCP601E E10期控制室12期控制室节点总线AdapterAdapterE至第4页E(冗余)NOD BUS Extender 节点总线扩展组件(冗余)ABD01300AB ABD01300D01400D01400D01100A BABD01100D01200D012006. I/A Series 智能自动化系列的硬件应用操作站处理AWAW51 具有应用处理机和操作站处理机的双重功能。

DCS系统维护手册

DCS系统维护手册

DCSDCS1.1)50~57 8 502)A B 51 523)10# 11# 1 2 12#3 44)2.3.1)2) TCP/IP3) I/O Profibus DPDCS1. FM801POWERSTANDBYRUNRESETBARRERY ON FM801 OFF FM8012.FM148ARDY COM3. FM148ERDY COM4. FM151A 8 4~20mARDY COM5. FM161DRDY COM〔 〕备 1~ 16 16 0~ 15 “ ” “ ”6.FM171BRDY COM〔 〕备 1~ 16 16 0~ 15 “ ” “ ”7.FM1201 DPRDY COM DP1 DP2〔 〕备DP1、DP2 。

DCSFM148A(FM148E FM151A)+FM131A1. FM148A+FM131A2.FM148E+FM131A3. FM151A+FM131A4. FM161D+FM131A〔 〕备 DCS DI1524VDC线24VDC原5. FM171B+FM131-E-A+FM138-ACRFM138-ACR 37 FM131-E-A FM138-ACR〔 〕备FM138原ACR 3 Ox 、COMx 、Cx x=1原16Ox 、COMx COMx 、Cx COMx 、Cx 备DO系尔引热系符尔引1524VDC线24VDC原个 DCS 1.superman macsv ops, eng, eng2. // /个 DCS1.MACSVYYGSB102.IP3.〔 〕备 “ ” “ ”个 DCS1.MACSV aaaa aaaaYYGSB2.IO 10IP A 130.0.0.1 A 131.0.0.1 A IP IP3.IP〔 1〕个 “ ”→“ ”→“”→“ ” 备〔 2〕个备〔 3〕个 “D:\MACSV \SysManage子exe ” 备〔 4〕个 “D:\MACSV\SysManageOPS子exe ” 备备1.MU MD2.0 1 2 3 4 3. PIDPIDDCS1.1 ON2342.12)3)4)a)b) D:\MACSV_ENG\c)YYGSBd)10~8e)f)D:\ MACSV\IE_Win2K_Eternal.exeg) MACSV仓仓、仓然 数1、 a作b作 c作 。

FOXBORO控制系统维护检修指导书

FOXBORO控制系统维护检修指导书

FOXBORO控制系统维护检修指导书1 目的为保证FOXBORO控制系统正确操作、维护,及安全、平稳运行,特制定本指导书。

2 范围本作业指导书对生产装置FOXBORO控制系统的操作和维护进行了规范。

3 职责3.1 DCS系统工程师负责FOXBORO控制系统的巡回检查,及时处理故障隐患。

3.2 DCS系统工程师的基本要求1)熟悉FOXBORO控制系统软硬件及配套仪表配件的技术技能;2)掌握该装置对生产工艺流程的作用;3)掌握调节回路、联锁报警回路、历史数据库等专业技能;4)掌握该系统维护检修及组态的基本技能;5)掌握常用测试仪器和有关的标准仪器使用方法。

4 主要技术指标4.1工作条件环境温度:20±5℃相对湿度:40%~80%室内尘埃量:<0.2mg/m2 (其中铁粉、碳粉等导电性尘埃必须非常少)室内腐蚀性气体含量:H2S<0.01ppm,SO2<0.05ppm供电电压:198~242VAC 47~63Hz接地电阻:<5Ω4.2性能指标操作系统:WINOWS XP SP15 维护检修内容5.1 日常维护5.1.1 巡回检查每班至少进行一次巡回检查,内容包括DCS系统的CP控制器、数据通讯、UPS供电、温度/湿度、IO卡件及操作站等模件的检查。

1)向当班工艺人员了解各测点数据、回路、联锁等是是否有异常;2)查看所有组件的状态指示灯,判断系统工作是否正常,定期使用系统自诊断系统软件对系统进行检查;3)检查控制室有无异常噪声和气味;4)检查机房温度、湿度是否满足4.1条的要求;5)调出系统管理显示画面,检查系统的通讯和各组件的运行状态是否正常;6)做好巡回检查记录。

5.2 定期维护1)每周进行一次电源的工作状态检查;2)装置自然检修时对机柜、各组件及外围设备进行除尘。

5.3 软件维护1)根据工艺实际需要对组态不断完善;2)在进行软件修改之前,先作好修改软件的设计,按组态要求填好数据表;3)修改软件输入完毕后应先作试验,确认满足设计要求方可投入运行;4)对投运后的修改软件,拷贝留底并做好软件修改记录;5)每年至少进行一次全盘拷贝。

DCS控制系统维护检修规程样本

DCS控制系统维护检修规程样本

DCS控制系统维护检修规程1、目DCS自动控制系统是由自身软、硬件以及操作台盘及现场仪表(变送器、测量仪表、电缆及执行机构等)构成有机整体。

避免系统中任何一种环节浮现问题导致系统某些功能失效或引起控制系统故障,甚至导致生产停车等事故,维护正常生产。

2、系统构成DCS控制系统由工程师站、操作站、控制站、过程网络构成。

2.1工程师站是为专业工程技术人员设计,内装有相应组态平台和系统维护工具。

通过系统组态平台生成适合于生产工艺规定应用系统,详细功能涉及:系统生成、数据库构造定义、组态操作、流程图画而组态、报表程序编制等。

而使用系统维护工具软件实而过程控制网络调试、故障诊断、信号调校等。

2.2操作站是由工业PC机、CRT、键盘、鼠标、打卬机等构成人机系统,是操作人员完毕过程控制监控管理任务环境。

2.3控制站是系统中直接与现场打交道I/O解决单元,完毕整个工业过程实时监控功能,控制站可冗余配路。

2.4过程控制网络实现工程师站、操作站、控制站连接,完毕信息、控制命令等传播,双重冗余设计。

3、系统寻常维护3.1寻常巡检内容:每天必要进行两次以上巡回检查,检查内容涉及:3.1.1向当班工艺人员理解DCS运营状况;3.1.2查看“故障诊断”画而,检查有无端障现象;3.1.3检查控制站各卡件批示灯有无异常;3.1.4检查控制室温度及空调运营状况;3.1.5检查控制站机柜及操作柜散热电扇运营状况。

3. 2控制站定期维护管理及测试:3.2.1控制室与操作室维护管理3.2.1.1保证控制室及操作室照明符合规定(安装H光灯进行采光);3.2.1.2检查操作室与控制室温度及湿度和空调运营状况,并应特别注意控制机柜卡件等电子设备有无浮现水珠或凝露现象;3.2.1.3检查有无腐蚀性气体腐蚀设备与过多粉尘堆积现象,操作台及控制机柜电扇滤网应定期拆洗,建议每月更换、拆洗一次;3.2.1.4检查操作室、控制室受电磁干扰状况和振动状况。

DCS系统维护

DCS系统维护

一、系统维护人员职责1. 负责DCS系统的系统软、硬件维护工作,确保DCS系统可靠地运行,保障生产过程的安全、稳定。

2. 协调并参与做好DCS的组态、控制方案的实现,以及系统的硬件连接、操作系统的安装和DCS系统调试工作。

3. 负责与DCS厂商进行技术沟通,学习DCS系统的使用、维护和管理技术,充分发挥DCS系统的作用;根据工艺生产的要求,健全完善DCS系统的控制及管理功能。

4. 指导操作人员进行DCS系统操作,解决操作人员操作中的问题;接到操作人员的请求后,立即做出响应并解决问题。

5. 做好DCS的日常、定期的巡检和维护工作;主动及时的发现系统的问题和隐患,查找原因并有效的解决,遇到疑难问题不能处理时,需及时咨询DCS厂商协调处理。

6. 负责系统运行参数修改、备份工作,避免出现任何数据损坏或丢失事件。

7. 做好DCS系统软、硬件的有效备份工作。

8. 负责DCS系统的启动和停止工作。

9. 负责操作员口令的设置与修改工作。

10. 制定DCS系统的维护及管理规定。

二、维护管理指导1. 控制室维护管理(1)制定机柜室、操作室管理规定。

对机柜室、操作室的卫生环境保持、进出人员管理、操作员操作管理、维护人员维护管理加以详细规定。

(2)控制室除维持适当的温度和湿度外,还要做好防水、防尘、防腐蚀、防干扰、防鼠防虫、避免机械震动等工作,具体请参考《控制系统环境规程》中的相关规定。

2. 计算机(操作站、工程师站、服务器站)维护管理(1)随时提醒操作人员文明操作,爱护设备,保持清洁,防水防尘。

(2)禁止操作人员退出实时监控;禁止操作人员增加、删改或移动计算机内任何文件或更改系统配置;禁止操作人员使用外来存储设备或光盘。

(3)尽量避免电磁场对计算机的干扰,避免移动运行中的计算机、显示器等,避免拉动或碰伤连接好的各类电缆。

(4)计算机应远离热源,保证通风口不被它物挡住。

(5)严禁使用非正版的操作系统软件(非正版操作系统软件指随机赠送的OEM 版和其它盗版软件);严禁在实时监控操作平台进行不必要的多任务操作,运行非必要的软件;严禁强制性关闭计算机电源;严禁带电拆装计算机硬件。

DCS维护手册

DCS维护手册

前言很荣幸贵方选择高达科技提供的DCS系统,为保证系统的稳定运行,高达科技特提供本手册,请认真阅读本手册,以保证系统长期稳定运行。

本维护手册的主要内容有系统结构、SIEMENS硬件介绍、系统电路、日常维护和常见故障处理等几个部分。

在阅读过程中可能需要了解西门子PCS7的相关内容,可通过西门子的手册进行了解,手册可从西门子网站()或高达科技网站()下载,也可向高达科技索取。

本手册不足之处,请批评指正。

目录系统结构 (1)DCS组成 (1)DCS系统结构图 (1)硬件介绍 (2)主控制器 (2)电源模块 (3)主控制器 (5)以太网模块 (8)ET 200M (8)IM153-1 (9)SM331 (9)SM332 (13)SM321 (14)SM322 (15)Profibus-DP (20)操作员站 (20)计算机 (21)UPS (21)操作系统 (22)系统软件 (22)TP/OP (22)系统电路 (22)柜内供电 (22)模拟量输入 (23)模拟量输出 (24)数字量输入 (25)数字量输出 (25)ES/OS站安装 (27)安装注意 (27)计算机恢复 (27)配置通讯 (29)控制级总线配置 (29)管理级总线配置 (30)通讯故障诊断 (31)控制级总线故障诊断 (31)管理级总线故障诊断 (32)下载 (33)下载硬件组态 (33)下载程序 (35)后记................................................................................................................. 错误!未定义书签。

系统结构DCS组成该项目DCS系统由高达科技设计制造,提供的主要设备有:1.控制柜个2.操作员站个(其中个兼作工程师站)3.UPS 个DCS系统结构图打浆控制室造纸控制室硬件介绍下面主要介绍DCS各部件的特点。

FOXBORO DCS系统维护手册

FOXBORO DCS系统维护手册

江苏镇江发电有限公司三期2X600MW机组DCS系统维护手册上海•福克斯波罗有限公司二零零四年九月页脚内容1第一章系统概述本手册为I/A’S系列DCS系统维护手册,并作为I/A’S培训手册的补充。

用户可以结合两本手册来进行系统操作、软件组态及系统维护。

必要时还应参考随机的原版资料及福克斯波罗公司提供的中文培训手册。

镇江发电厂5#机组控制系统采用了福克斯波罗制造的I/A’S系列DCS系统。

整个系统为三个独立节点,其中5#号机为一个节点、6#号机为一个节点、公用系统为一个节点,三个节点之间互不相连。

在5#号机冗余的节点总线上挂有:一台工程师站AW5001该站作为锅炉侧工程师站,内置512M内存及80GB硬盘,外挂一台80GB的磁带机,并配有一个21”的LCD。

同时该工作站通过第二以太网卡与5#机组16端口HUB相连。

一台工程师站AW5002(属于DEH系统)该站作为汽机侧工程师站,内置512M内存及80GB硬盘,并配有一个21”的LCD。

同时该工作站通过第二以太网卡与5#机组16端口HUB相连。

一台工程师站AW5003该站作为SIS系统通讯接口工程师站,内置512M内存及80GB硬盘,并配有一个21”的LCD。

同时该工作站通过第二以太网卡与5#机组16端口HUB相连。

HUB在与电厂SIS系统相连。

一台操作员站WP5001该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘,并配有一台21”的LCD以及提供一个大屏幕相连的第二以太网卡。

一台操作员站WP5002该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘,并配有一台21”的LCD以及提供一个大屏幕相连的接口。

一台操作员站WP5003该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘,并配有一台21”的LCD以及提供一个大屏幕相连的第二以太网卡。

一台操作员站WP5004该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘和,并配有一台21”的LCD以及提供一个大屏幕相连的第二以太网卡。

FOXBORO维护检修规程

FOXBORO维护检修规程

一、总则1、1主题内容与使用范围1、1、1主题内容本节规程规定福克斯波罗I/A′S的日常维护,大修的内容1、1、2适用范围本节规程适用于福克斯波罗I/A′S控制系统。

1、2编写依据本书规程依据福克斯波罗I/A′S控制系统编写。

二、概述2、1 I/A′S控制系统简介:I/A Series系统包括流程图,趋势图,报表,顺序事件记录等。

在流程图上,运行人员可以从流程图上监视到各点的实时运行参数,报警状态,从画面上的设备可以直接调出相应的操作画面(OVERLAY),实现了在监视实时参数的同时进行控制操作。

2、2 I/A Series 的网络结构I/A Series 系统的通讯网络是建立在国际标准化组织(ISO)所定义的开放系统互连(OSI)标准基础上的,并符合 IEEE 的规范,是按照局域概念构造的标准网。

图 1-1 I/A Series 系统网络结构简图2、2、1 I/A Series 的通讯网络结构I/A Series 采用商用交换机组成Mesh网,由一组以太网交换机以各种网络拓扑方式连接而成。

Mesh控制网络将控制站、输入输出模块和各种工作站集中在了一个100Mb/1Gbde的交换机以太网中。

这些控制站、输入输出模块和工作站通过Mesh控制网络连接在一起,为过程系统的检测、控制和工厂信息管理提供了一个规模灵活的控制系统网络平台,他的高速、多冗余以及点对点的网络通讯性能为控制系统的高性能和安全性提供了可靠的基础。

每对控制站、输入输出模块和工作站可以使用冗余连接与Mesh网上的其他控制站、输入输出模块和工作站进行通讯。

通讯网络结构分为四个层次:宽带局域网 (BROADBAND LAN);载波带局域网( CARRIERBAND LAN );节点总线(NODE BUS);现场总线(FIELD BUS)。

.这些通讯标准的低层通讯(物理层和逻辑层)均与制造商自动化协议(MAP)兼容。

出于通讯的安全考虑,节点总线是冗余的,载波带可选冗余。

foxboro维护手册

foxboro维护手册

I/A’s系统维护手册(工程师手册)编制:何卫兵上海•福克斯波罗有限公司二零零二年元月第一章系统概述本手册为上海福克斯波罗有限公司DCS系统I/A维护手册,并作为I/A’s 培训手册的补充。

用户可以结合两本手册来进行系统操作、软件组态及系统维护。

必要时还应参考随机的原版资料及福克斯波罗公司提供的中文培训手册。

本手册针对福克斯波罗制造的I/A’S,采用Solaris 2.5.1操作系统和I/A’s 6.2.1版本应用软件。

整个系统为一个节点,在冗余的节点总线DNBI上挂有:●三台工程师站AW5101、AW5102、AW5103该站作为工程师站,内置256M内存及8GB硬盘,AW5102外挂一台喷墨打印机(电缆长度15米),AW5103配有和MIS系统通讯用的第二以太网卡。

该工作站安放在工程师站内,与I/A机柜(位于电子间)之间的通讯电缆长度为30米。

●四台操作员站WP5101、WP5103、WP5104、WP5105该站内置128M内存及8GB硬盘,并各配有一个21”的CRT。

该工作站安放在主控室内与I/A机柜(位于电子间)之间的通讯电缆长度为30米。

●一台操作员站WP5102该站作为大屏幕操作站,内置128M内存及8GB硬盘,除配有一个21”的CRT外。

还配有一台用于显示大屏幕的以太网卡。

该工作站安放在主控室内,与I/A机柜(位于电子间)之间的通讯电缆长度为30米。

十一对容错台控制处理站CP4001、CP4002、CP4003、CP4004、CP4005、CP4006、CP4007、CP4008、CP4009、CP4010、CP4011此容错型控制处理站CP40BFT,用于实现DCS系统的数据采集及控制。

该控制处理器安放在电子间内。

现场由十八个装有现场总线组件FBM的现场机柜、十个安装DCS系统辅助装置(包括冗余的24VDC电源、交流继电器、直流继电器、SIMENSE交流接触器、以及相应的I/O端子)的继电器柜、一个DCS系统220VAC配电柜共同构成。

DCS系统检查和维护作业指导书

DCS系统检查和维护作业指导书
DCS系统检查和维护作业指导书
中国石化长城能源化工(宁夏)有限公司运行
生产装置检维修施工作业
DCS系统
1、概述
热点运行部
DCS检修作业指导书
版次:1
#1机组A级检修使用有效
目的
本作业指导书适用于热点运行部DCS检修作业
规范性引用文件
《热控检修规程》
《电力安全工作规程》
《检修作业管理标准SB-03-11》
工作负责人确认签字: 时间:
3.2技术交底(根据内容要求填写)

序号
内容
1
消除设备缺陷。
2
现场安全技术措施及图纸如有错误,可能造成做人身伤害或设备损坏。
3
严格按照W、H点进行验收。
4
设备检修工艺不当,引起设备损坏。
5
是否有强电串入系统
6
其它安全保障要求(防火、防坠落、消防设施的配备、安全帽、安全带等)。
5
工作人员着装不当,易造成自身保护、防护能力不够(烫伤)
工作人员必须穿合格的工作服和绝缘鞋
6
使用电动工具时,着装不当易发生触电
使用电动工具时,要戴绝缘手套,并穿绝缘鞋
7
作业环境
现场光照昏暗
工作现场照明充分
8
物料摆放混乱
材料、工器具、零部件定置管理,防止高空落物
9
灰尘伤害、有毒有害空间气体中毒、受限空间窒息
工作负责人确认签字: 时间:
3.3检修所需参考图纸资料
序号
资料名称
资料图号
1
相关图纸、说明书
2
原绐安装资料
3
热控检修规程
工作负责人确认签字: 时间:
3.4检修所需备品备件
工作所需备品配件准备

foxboro维护手册

foxboro维护手册

I/A’s系统维护手册(工程师手册)编制:何卫兵上海•福克斯波罗有限公司二零零二年元月第一章系统概述本手册为上海福克斯波罗有限公司DCS系统I/A维护手册,并作为I/A’s 培训手册的补充。

用户可以结合两本手册来进行系统操作、软件组态及系统维护。

必要时还应参考随机的原版资料及福克斯波罗公司提供的中文培训手册。

本手册针对福克斯波罗制造的I/A’S,采用Solaris 2.5.1操作系统和I/A’s 6.2.1版本应用软件。

整个系统为一个节点,在冗余的节点总线DNBI上挂有:●三台工程师站AW5101、AW5102、AW5103该站作为工程师站,内置256M内存及8GB硬盘,AW5102外挂一台喷墨打印机(电缆长度15米),AW5103配有和MIS系统通讯用的第二以太网卡。

该工作站安放在工程师站内,与I/A机柜(位于电子间)之间的通讯电缆长度为30米。

●四台操作员站WP5101、WP5103、WP5104、WP5105该站内置128M内存及8GB硬盘,并各配有一个21”的CRT。

该工作站安放在主控室内与I/A机柜(位于电子间)之间的通讯电缆长度为30米。

●一台操作员站WP5102该站作为大屏幕操作站,内置128M内存及8GB硬盘,除配有一个21”的CRT外。

还配有一台用于显示大屏幕的以太网卡。

该工作站安放在主控室内,与I/A机柜(位于电子间)之间的通讯电缆长度为30米。

十一对容错台控制处理站CP4001、CP4002、CP4003、CP4004、CP4005、CP4006、CP4007、CP4008、CP4009、CP4010、CP4011此容错型控制处理站CP40BFT,用于实现DCS系统的数据采集及控制。

该控制处理器安放在电子间内。

现场由十八个装有现场总线组件FBM的现场机柜、十个安装DCS系统辅助装置(包括冗余的24VDC电源、交流继电器、直流继电器、SIMENSE交流接触器、以及相应的I/O端子)的继电器柜、一个DCS系统220VAC配电柜共同构成。

Foxboro系统的维护

Foxboro系统的维护
对于第一项 CIO 备份,在 AW 上用下面命令进行备份: 进入 VT100, cd /opt/fox/ciocfg/api
save_all CP 名 /路径/ (CP 名大写) 系统关机及重启
I/A 系统对关机要求严格,非正常关机(即直接关掉电源)可能 损坏系统文件或硬盘,正常关机步骤如下:
进入过程工程师环境, 依次选择 [SftMnt] → Shutdown_AW (WP),输入超级用户口令 gnomes, 等 # 字提示符出现后再输入 命令 halt, 等待 OK 提示符出现, 然后输入 power-off 回车,即可。 如果要搬运,要求在断电后等 1.5 分钟才可移动机器。
/an_init.cfg ( SERVER ) cd /opt/fox/ais/bin/ ; tar rvf /dev/fd0 /
opt/fox/ais/bin /an_init.tcp ( SERVER )
tar rvf /dev/fd0 /
opt/fox/ais/bin /servers ( 右 键 锁 定 ) cd /usr/openwin/lib/ ; tar rvf /dev/fd0 /
日常维护:
*系统备份 所有操作都在工程师环境下完成的。即:Sys—Change_Env--Proc_Eng_Env 环境 1、 控制组态文件的备份:(也就是平时所说的 CIO 备份) 在 Config 菜单下,选择 Control_Cfg---- CIO_STN_Cfg 选择一个
1
CP 进入 在 MAINT 菜单下,选择 Save All ,然后选择软盘所放入的驱动 器的主机的逻辑名(如:AW5101),回车即可。 2、 画面文件的备份:
在 SftMnt 菜单下,选择 VT100 进入, cd /usr/ hstorian/ tar cvf /dev/fd0 /usr/ hstorian/文件名

DCS系统的管理与维护

DCS系统的管理与维护

DCS系统的管理与维护DCS系统的管理与维护1、简介DCS(分布式控制系统)是一种广泛应用于工业控制领域的自动化控制系统。

本文档旨在介绍DCS系统的管理与维护工作,以确保系统的正常运行和长期稳定性。

2、系统架构2.1 硬件组成2.2 软件架构2.3 网络拓扑3、系统管理3.1 系统监控3.1.1 硬件监控3.1.2 软件监控3.1.3 网络监控3.2 数据备份与恢复3.2.1 定期备份3.2.2 数据恢复测试4、系统维护4.1 软件更新与升级4.2 硬件维护4.2.1 清洁与维护4.2.2 硬件故障处理4.3 系统性能优化4.3.1 性能监测与评估4.3.2 优化策略与实施5、安全管理5.1 访问控制5.2 防火墙与安全策略5.3 安全漏洞管理6、故障排除与故障恢复6.1 故障排查流程6.2 故障解决方案6.3 紧急故障恢复7、系统性能监测与评估7.1 关键性能指标7.2 性能监测工具与方法7.3 性能评估报告8、系统日志与审计8.1 日志记录与管理8.2 安全审计附件:1、系统架构图2、系统维护工具与软件清单法律名词及注释:1、DCS(分布式控制系统)- 一种广泛应用于工业控制领域的自动化控制系统。

该系统通过分布在不同位置的控制器和传感器,实现对工业流程的监控与控制。

2、网络拓扑 - 指多个设备通过网络连接的物理和逻辑布局。

网络拓扑主要包括总线型、环形、星型、树型、网状等多种形式。

3、数据备份与恢复 - 对系统数据进行定期备份,以防止数据丢失或损坏,并能够及时恢复备份数据。

4、安全漏洞管理 - 对系统中存在的安全漏洞进行管理和修复,以提高系统的安全性和稳定性。

5、故障排除与故障恢复 - 对系统中出现的故障进行排查和解决,以及进行紧急故障恢复工作。

6、系统性能监测与评估 - 通过监测与评估关键性能指标,对系统的工作状态和性能进行监控和评估。

西电Foxboro DCS系列产品说明书

西电Foxboro DCS系列产品说明书

Foxboro ™ DCSFBM243/243b, FoxCom Dual Baud Rate, Intelligent Device ModulesPSS 41H-2S243Product SpecificationAugust2019Legal InformationThe Schneider Electric brand and any trademarks of Schneider Electric SE and itssubsidiaries referred to in this guide are the property of Schneider Electric SE or itssubsidiaries.All other brands may be trademarks of their respective owners.This guide and its content are protected under applicable copyright laws and furnishedfor informational use only.No part of this guide may be reproduced or transmitted inany form or by any means(electronic,mechanical,photocopying,recording,orotherwise),for any purpose,without the prior written permission of Schneider Electric.Schneider Electric does not grant any right or license for commercial use of the guideor its content,except for a non-exclusive and personal license to consult it on an"as is"basis.Schneider Electric products and equipment should be installed,operated,serviced,and maintained only by qualified personnel.As standards,specifications,and designs change from time to time,informationcontained in this guide may be subject to change without notice.To the extent permitted by applicable law,no responsibility or liability is assumed bySchneider Electric and its subsidiaries for any errors or omissions in the informationalcontent of this material or consequences arising out of or resulting from the use of theinformation contained herein.Overview FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesOverviewThe FBM243,FoxCom Dual Baud Rate,Intelligent Device Module contains eightindividual channels.The FBM243b,FoxCom Dual Baud Rate,Intelligent DeviceModule contains four individual input channels and four0to20mA analog outputchannels.Each input provides internal isolated power and digital communication capabilities to aFoxboro Intelligent Field Device.Each channel communicates over a single twistedpair of wires and each channel of the FBM243/243b is channel isolated.The modules also allow the use of an external power supply to power the IntelligentField Device.(The use of an external power supply common to two or more loopsneeds the use of a cable balun module to maintain digital communication linebalance).The baud rate is determined by the configuration of the field deviceconnected to each channel,independently of the other channels.The modulesprovide bidirectional digital communication at4800baud rate between the IntelligentField Device and the system redundant Fieldbus,or provides bidirectional digitalcommunication at600baud rate between the field device and the modules whileallowing a simultaneous4to20mA analog signal from the field device to anemergency shutdown system.The FBM243/243b is an Intelligent Field Device host,enabling the system to receivedigital messages from the field device in engineering units.Each message is receivedten times per second at4800baud,and two times per second at600baud.Eachmessage contains:•Up to three measured variables in IEEE32-bit floating-point format•Security information•Diagnostics•Message checkingThis information is available to each of the elements of the system.Since communication is bidirectional,the system can display the output,transmittertemperature(°C and°F),and the results of continuous self-diagnostics.In addition,the following information can be displayed or reconfigured from a console,a FieldCommunicator,or PC-Based Configurator:•Output in engineering units•Fail-safe information•Tag number,name and location•Device name(letterbug)•Last calibration date•Two levels of upload/download capabilitiesWhen connected to the appropriate TAs,the FBM243/243b modules providefunctionality formerly provided by the100Series FBM I/O subsystem.TAs areavailable for the FBM243that support the functionality of the100Series FBM18andFBM43.TAs are available for the FBM243b that support the functionality of the100SeriesFBM39and FBM44.FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModules Features Features•For the FBM243,8individual digital communication channels•For the FBM243b,4individual dual baud,FoxCom communication channels andfour0to20mA analog output channels•Receives messages10times per second at4800baud,or2times per second at600baud,and contains:◦Up to3measured variables in IEEE◦32-bit floating-point format◦Security information◦Diagnostics◦Message checking•Allows use of an external power supply or the FBM243internal isolated power topower the Intelligent Field Device•Digital communication capabilities to a Foxboro Intelligent Field Device over asingle twisted pair of wires•Allows a simultaneous4to20mA analog signal from the field device to anemergency shutdown system•Termination Assemblies(TAs)for locally or remotely connecting field wiring to theFBM243•Termination Assemblies(TAs)for non-intrinsically safe or intrinsically safeapplicationsFeatures FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesStandard DesignThe FBM243/243b has a rugged extruded aluminum exterior for physical protection ofthe circuits.Enclosures specially designed for mounting of the FBMs provide variouslevels of environmental protection,up to harsh environments per ISA StandardS71.04.Visual IndicatorsLight-emitting diodes(LEDs)incorporated into the front of the module provide visualindication of the module operational status,and communication activity of the inputchannels.Easy Removal/ReplacementThe module can be removed/replaced without removing field device terminationcabling,power,or communication cabling.Figure1-FBM243/243b I/O ConfigurationFBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModules Features Fieldbus CommunicationThe Fieldbus Communications Module(FCM)or the Field Control Processor(FCP)interfaces to the redundant2Mbps module Fieldbus used by the FBMs.TheFBM243/243b accepts communication from either path(A or B)of the2MbpsFieldbus.If one path is unsuccessful or is switched at the system level,the modulecontinues communication over the active path.Modular Baseplate MountingThe FBM243/243b mounts on a Standard200Series Modular Baseplate(see Figure1),which accommodates up to four or eight Fieldbus Modules.TheModular Baseplate is either DIN rail mounted or rack mounted,and includes signalconnectors for redundant Module Fieldbus,redundant independent dc power,andtermination cables.Termination AssembliesField I/O signals connect to the FBM subsystem via DIN rail mounted terminationassemblies(TAs).For the FBM243,TA RH931KJ contains a51ohm resistor in series with each channelfor use in non-intrinsically safe applications.TA RH917XW is a direct channel for use in intrinsically safe applications.An intrinsicsafety barrier needs to be connected to each channel of this TA providing thenecessary resistance for each channel.TAs RH931KJ,RH917XW,and RH931KJ are available in Polyamide material.For the FBM243b,TAs RH924QQ and RH924QY are available for use in non-intrinsically safe applications.TA RH924QY has output bypass jacks that help removeFBMs from service during system maintenance.An Output Bypass Station providesmanually driven milliamp output signals through the bypass jacks to deter interruptionof the process output signals.The DIN rail mounted TAs connect to the FBM subsystem baseplate by means of aremovable termination cable.The cable is available in a variety of lengths,up to30meters(98feet),allowing the TA to be mounted in either the enclosure or in anadjacent enclosure.Termination cables are available in these materials:•Polyurethane•Low Smoke Zero Halogen(LSZH)Refer to Table1.Features FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesCable Balun ModuleA Cable Balun Module maintains digital communication line balance for IntelligentField Devices connected in FBM loops that are powered from a common externalpower supply.This powering method effectively connects one line of each loop to asingle point.(Without the baluns,the multiple common connections at the externalpower source cause communication cross-talk between the loops.)Baluns are notneeded for loops that use internal power sourcing(powered from the FBM).TheCable Balun Module(RH903SV)contains four baluns,with one balun used for eachloop powered from the external power supply.Each balun adds28ohms of resistanceto its associated loop.FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModules Functional Specifications Functional SpecificationsFunctional Specifications FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesFBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceSpecificationsModules FunctionalEnvironmental SpecificationsFBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesEnvironmental SpecificationsNOTE:The environmental limits of this module may be enhanced by the type of enclosure containing the module.Refer to the applicable Product Specification Sheet (PSS)that describes the specific type of enclosure that is to be used.FBM243/243b,FoxCom Dual Baud Rate,Intelligent Device ModulesPhysicalSpecificationsPhysical SpecificationsPhysical Specifications FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesFBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModules Physical SpecificationsTable1-Termination Cable Types and Part NumbersUpgrade Use of Termination AssembliesWhen an FBM243/243b is used to replace the100Series FBM,it may use any of theappropriate termination assemblies listed in this PSS for the100Series FBM’s fieldI/O wiring.Alternatively,the FBM243/243b can accept this field wiring through aTermination Assembly Adapter(TAA)instead of a termination assembly.This isdiscussed in Termination Assembly Adapter Modules for100Series Upgrade(PSS41H-2W4).Dimensions-Nominal FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModulesDimensions-NominalFigure2-Termination Assemblies(a)Overall width—for determining DIN rail loading.(b)Height above DIN rail(add to DIN rail height for total).FBM243/243b,FoxCom Dual Baud Rate,Intelligent DeviceModules Related Product Documents Related Product DocumentsWARNING: This product canexpose you to chemicalsincluding lead and leadcompounds, which areknown to the State ofCalifornia to cause cancerand birth defects or otherreproductive harm. For moreinformation, go to/. Schneider Electric Systems USA,Inc.38Neponset AvenueFoxborough,Massachusetts02035–2037United States of AmericaGlobal Customer Support:https://As standards,specifications,and design change from time to time,please ask for confirmation of the information given in this publication.©2015–2019Schneider Electric.All rights reserved.PSS41H-2S243,Rev A。

foxboroIADCS维护手册

foxboroIADCS维护手册

Ni 第一部分硬件概述第一章I/A’S 系统概述1.1 I/A’S系统简介自七十年代以来,以微处理器为核心的分布式控制系统(亦称集散控制系统)将现代高科技的最新成就集成一体,为系统资源的共享和集中管理,方便而丰富的人机联系提供了强有力的支持。

在这基础上,现代控制理论的实用化成为可能,大大促进了自动控制技术的发展。

步随1975年美国Honeywell公司在世界上发表第一个分布式控制系统TDC-2000以后,世界上各自动化仪表制造商也纷纷推出了自己的分布式新成就与自动控制技术集为一体,使自动化仪表装置向系统化、分散化、多样化和高性能化的方向产生了一个质的飞跃。

由于分布式控制系统的分散结构思想替代了微机集中控制,使得系统的可靠性得以极大的提高;高性能的微处理能力使系统的功能远远超过了以往任何自动化仪表;高速有效的通讯系统和CRT显示技控制系统。

基于分布式控制系统所采用的硬件和软件灵活性、通用性及易开发性,系统版本将不断更新。

发展甚为迅速,竞争十分激烈。

目前,我国从国外引进的集散控制系统DCS(Distributed Control System)产品种类就多达几十种。

从发展的眼光看,无论哪一个DCS厂商生产的产品都必须是开放式控制系统。

什么是开放式控制系统呢?凡是符合国际标准化组织(ISO)提出的开放系统互连(OSI)参考模型的即可称为开放系统。

1978年,美国Foxboro公司在世界上第一个开放式DCS系统——I/A Series system(简称I/A’S),它主要有以下特点:●采用IEEE802标准通讯协议●系统软、硬件彼此独立,不会因软件升级而使硬件失效●操作平台基于WINDOWS NT/UNIX,能够方便地与第三方软件兼容●控制功能强大,能满足所有常规过程控制要求●系统软、硬件组态及维护比较容易,并具有完善的自诊断功能1.2 I/A’S网络结构I/A’S的通讯网络结构分为四个层次:●宽带局域网(Broadband LAN - Baseband Local Area Network)●载波带局域网(Carrierband LAN – Carrierband Local Area Network)●节点总线(NODE BUS)●现场总线(FIELD BUS)下图是I/A Series系统四层网络结构简图(图1-1)图1-1宽带局域网(Broadband LAN—Baseband local area network)通讯规范:IEEE802.4结构形式:总线结构信号传送方式:Token Passing(令牌传送)数据传送速率:10 MB/S通讯传送介质:同轴电缆15 Km最多可下挂64个载波带局域网载波带局域网(Carrierband LAN—Carrierband Local Area Network)通讯规范:IEEE802.4结构形式:总线结构信号传送方式:Token Passing(令牌传送)数据传送速率:5 MB/S通讯传送介质:同轴电缆1.2 Km、光缆10Km最多可下挂64个节点总线节点总线(NODE BUS)通讯规范:IEEE802.3(Ethernet 以太网)结构形式:总线结构信号传送方式:Carrier Sense Multiple Access With CollisionDetection(带冲突检测的多路送取争用总线)数据传送速率:10 MB/S通讯传送介质:同轴电缆30m(不带扩展组件)。

DCS维护及工作说明

DCS维护及工作说明

DCS维护及工作说明一、故障判断。

1、开关量故障判断。

开关量点可通过短接来判断DCS系统是否正确。

开关量输入点短接后DCS上会显示该点为一。

如果短接后该点不唯一则说明该点不正常。

开关量输出测点,先检测该测点上是否有电压,如果电压不正常先检测现场设备。

如电压正常,短接后相当于DCS发出该点的控制指令,如现场设备正常动作,而DCS控制无法完成则检查DCS指令发出时该点是否接通,如该点在发出指令时没有变化则说明该点不正常。

2、模拟量故障判断。

模拟量点可通过加标准信号来判断DCS系统是否正确。

在加标准信号时请注意接线方式。

如果信号电缆接地也会造成无法正确检测。

3、脉冲量故障判断。

脉冲量点可通过连续短接来判断DCS系统是否正确。

在连续短接时该点的检测量会出现变化。

如果如果没有变化,请检测电压是否正常。

如果电压正常而短接后没有变化则说明该点不正常。

二、DCS故障维护1、检查系统状态。

在操作员站画面上点击图象管理——系统状态图,检查系统网络状态是否正常。

点击I/O站,观察模块状态有无异常。

2、更换模块。

如果系统状态和该模块的状态都没有异常,则很有可能是该模块损坏,更换同一类型的模块进行试验,如果更换后正常则说明该模块的通道有损坏的现象。

更换模块前一定要进行通道电压的检查,以免损坏模块。

三、设备的修改及调试方法。

电动门、电动机、电磁阀的控制是通过HSSCS5模块完成的。

电动门的控制都已经做好了,但调试时,1、顺控调试。

电动门、电动机、电磁阀的控制是通过HSSCS5模块完成的。

电动门的控制都已经做好了,但调试时,理解HSSCS5的工作原理还是比较重要。

1,工作原理:HSSCS5输入端的“V1”连接的是“开反馈点”,“V2”连接的是“关反馈点”。

V1为TEUE,则画面上对应设备的“开状态”显示红色,V2为TEUE,则画面上对应设备的“关状态”显示绿色。

HSSCS5输出端的“DV”连接的是“开命令”,“RV”连接的是“关命令”。

DCS系统操作维护说明

DCS系统操作维护说明

DCS系统操作维护说明DCS操作维护说明一、查询点通道位置:右键点击图上点---点详细---点名,SN站号、DN设备号、CN通道号二、控制器算法组态:1、进入:开始--程序--MACSV组态--选择工程名(JYKEQ1/JYKEQ2/JYKGY)--选择站号,进入控制器算法组态2、在线:点击“在线”--下拉菜单选择“登陆”,如果登陆不上去,点击“在线”--通讯参数,选择另外3个通讯IP尝试登陆,如全登陆不上,请检查I/O站DPU及网线。

3、强制点:在线状态下,双击点名,按F7按钮,强制点颜色变红。

如需取消强制点:在线状态下,双击变红点名,按F7按钮,恢复原色,强制恢复。

看管脚,如反馈、指令、开许可、自动开、关等。

注意:修改逻辑及点后需再次登陆,先编译再下装且只可无扰下装。

设备运行时不允许初始化下装,否则所有设备状态及指令清零。

三、修改通道:1、编辑数据库:程序--MACSV组态软件--进入数据库总控下拉菜单内选择工程名(JYKGY/JYKEQ2/JYKEQ1)--点击“编辑”--编辑数据库--点击“系统”--数据操作--选择需修改的点类型--点选“旧风格”进入数据库编辑文本窗口。

按照站号、设备号、通道号查找需修改的点,修改其点名、量程、报警等。

修改完成后,点击左上角菜单中第一个红色对号按钮即“更新数据库”,点击第二个红色对号按钮即“校验”,如校验后无错误信息,关闭数据库编辑文本窗口。

编辑数据库后在数据控总控窗口点击红色向下箭头,进行完全编译,待完全编译完成后自动生成下装文件。

2、下装:程序--MACSV组态软件--工程师在线下装--输入用户名及口令(eng0/eng1/eng2用户名与口令相同)--选择工程点击“系统命令”--“下装”--“服务器”--全选所有服务器--选择服务器IP(注意:此处需查看当前下装服务器是否为备用状态),勾选“下装后自动注销重启服务器”--直接下装下装完成后,待服务器网线恢复绿色状态,画面上点击“服务器切换”切换完成后,重复工程师下装操作,下装另外一台已切换为备用的服务器,最后,进入控制器算法组态逻辑,编译,在线登陆,检查修改点状态是否已修改完成。

  1. 1、下载文档前请自行甄别文档内容的完整性,平台不提供额外的编辑、内容补充、找答案等附加服务。
  2. 2、"仅部分预览"的文档,不可在线预览部分如存在完整性等问题,可反馈申请退款(可完整预览的文档不适用该条件!)。
  3. 3、如文档侵犯您的权益,请联系客服反馈,我们会尽快为您处理(人工客服工作时间:9:00-18:30)。

江苏镇江发电有限公司三期2X600MW机组DCS系统维护手册上海福克斯波罗有限公司二零零四年九月第一章系统概述本手册为I/A’S系列DCS系统维护手册,并作为I/A’S培训手册的补充。

用户可以结合两本手册来进行系统操作、软件组态及系统维护。

必要时还应参考随机的原版资料及福克斯波罗公司提供的中文培训手册。

镇江发电厂5#机组控制系统采用了福克斯波罗制造的I/A’S系列DCS系统。

整个系统为三个独立节点,其中5#号机为一个节点、6#号机为一个节点、公用系统为一个节点,三个节点之间互不相连。

在5#号机冗余的节点总线上挂有:●一台工程师站AW5001该站作为锅炉侧工程师站,内置512M内存及80GB硬盘,外挂一台80GB的磁带机,并配有一个21”的LCD。

同时该工作站通过第二以太网卡与5#机组16端口HUB相连。

●一台工程师站AW5002(属于DEH系统)该站作为汽机侧工程师站,内置512M内存及80GB硬盘,并配有一个21”的LCD。

同时该工作站通过第二以太网卡与5#机组16端口HUB相连。

●一台工程师站AW5003该站作为SIS系统通讯接口工程师站,内置512M内存及80GB硬盘,并配有一个21”的LCD。

同时该工作站通过第二以太网卡与5#机组16端口HUB相连。

HUB在与电厂SIS系统相连。

●一台操作员站WP5001该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘,并配有一台21”的LCD以及提供一个大屏幕相连的第二以太网卡。

●一台操作员站WP5002该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘,并配有一台21”的LCD以及提供一个大屏幕相连的接口。

●一台操作员站WP5003该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘,并配有一台21”的LCD以及提供一个大屏幕相连的第二以太网卡。

●一台操作员站WP5004该站作为全能值班操作站,内置256M内存及80GB硬盘,外挂一台数字/告示键盘和,并配有一台21”的LCD以及提供一个大屏幕相连的第二以太网卡。

●21对控制处理站CP5001-CP5021此21对控制处理器为容错型控制处理站CP60FT,用于实现5#机组DAS、MCS、FSSS、ECS、SCS、DEH和MEH系统的数据采集及控制。

其中CP5001~CP5002控制锅炉侧MCS系统,CP5003~CP5005控制FSSS系统,CP5006~CP5007控制锅炉SCS系统,CP5008控制吹灰SB 系统,CP5009控制锅炉侧DAS系统,CP5010控制锅炉侧远程DAS系统,CP5011控制汽机侧MCS系统,CP5012~CP5014控制汽机侧SCS系统,CP5015控制机侧DAS系统,CP5016控制机侧远程DAS系统,CP5017控制单元发变组ECS系统,CP5018控制DEH系统,CP5019控制ATC系统,CP5020控制MEHA系统,CP5021控制MEHB系统,TRI501控制OPC系统。

现场级由34个装有现场总线组件DIN FBM的现场机柜及15个继电器柜组成,采用冗余的现场总线FCM10E连接方式。

实现5#机组控制系统相关输入输出信号的采集、A/D,D/A转换、故障处理及光电隔离。

在公用系统冗余的节点总线上挂有:●一台工程师站AW0001该站作为公用系统工程师站,内置512M内存及80GB硬盘,并配有一个21”的LCD以及提供一个与公用系统16端口HUB相连的第二以太网卡。

通过16端口HUB可以与SIS系统●一台工程师站AW0002该站作为公用系统操作员,内置256M内存及80GB硬盘,并配有一个21”的LCD以及提供一个大屏幕相连的第二显卡。

●一台工程师站AW0003该站作为公用系统操作员,内置256M内存及80GB硬盘,并配有一个21”的LCD以及提供一个大屏幕相连的第二显卡。

●3对控制处理站CP0001-CP0003此3对控制处理器为容错型控制处理站CP60FT,用于实现电气公用系统及循泵的控制。

其中CP0001控制部分公用电气系统、1#/2#循泵远程系统、燃油泵房远程系统、5#机备用操作系统;CP0002控制部分公用电气系统、3#/4#循泵远程系统以及6#机备用操作系统;CP0003控制等离子点火系统。

现场级由4个装有现场总线组件DIN FBM的现场机柜及一个继电器柜组成,采用冗余的现场总线FCM10E连接方式。

实现电气公用系统及循泵控制相关输入输出信号的采集、A/D,D/A 转换、故障处理及光电隔离。

6#机的网络拓朴结构与5#机组类似,区别在于工作站名称、CP控制处理器名称由“5”改为“6”。

第二章文件结构5#机组DCS系统包括DAS、MCS、SCS、FSSS、SB、ECS、DEH、MEH系统等,其中DAS、MCS、SCS又包括锅炉部分及汽机部分,此外还有各系统的成组显示、流程画面、趋势图、覆盖画面等,文件数量较多,了解本套DCS系统的文件结构对系统的维护、文件的修改、文件的备份十分重要。

除有关于DCS画面的文件外,系统中还有许多与DCS系统有关的文件,诸如:环境文件、报表文件、AM过程报警文件、报警键盘文件、DM管理文件等等,在此一并描述。

1./opt/dcs/das/ DAS系统流程画面及操作器画面主目录boiler/ 锅炉侧流程画面主目录turbine/ 汽机侧流程画面主目录trend/ 趋势画面主目录,包括炉侧、机侧及电气系统group/ 成组画面主目录,包括炉侧、机侧及电气系统ovl/ I/O描述覆盖画面主目录,包括炉侧、机侧及电气系统2./opt/dcs/btg/ 软光字牌报警画面主目录,炉侧、机侧及电气系统3./opt/dcs/mcs/ MCS系统流程画面及操作器画面文件主目录boiler/ 炉侧MCS系统画面主目录turbine/ 机侧MCS系统画面主目录cbovl/ 炉侧MCS系统操作器画面主目录ctovl/ 机侧MCS系统操作器画面主目录4./opt/dcs/scs/ SCS系统流程画面及操作器画面文件主目录boiler/ 炉侧SCS系统画面主目录turbine/ 机侧SCS系统画面主目录bovl/ 炉侧SCS系统操作器画面主目录tovl/ 机侧SCS系统操作器画面主目录disable/ 禁操画面主目录,包括锅炉、汽机及电气5./opt/dcs/fsss FSSS系统流程画面及操作器画面文件主目录fsovl/ FSSS操作画面文件目录disable/ FSSS系统禁操画面主目录6./opt/dcs/ecs 单元发变组ECS系统流程画面及操作器画面主目录edas/ 单元发变组ECS系统流程画面主目录escs/ 单元发变组ECS系统顺控画面主目录eovl/ 单元发变组ECS系统操作器画面主目录edisable/ ECS系统禁操画面主目录7./opt/dcs/sb 吹灰系统流程画面及操作器画面主目录8./opt/dcs/comm/ 公用系统流程画面及操作器画面主目录dascomm/ I/O描述覆盖画面主目录,包括所有公用系统grpcomm/ 成组画面主目录,包括所有公用系统btg/ 软光字牌报警画面主目录,包括所有公用系统disable/ 禁操画面目录,包括所有公用系统xp/ 循泵系统流程画面及操作器画面主目录xpovl/ 循泵系统操作器主目录ecomm/ 公用电气系统流程画面及操作器画面主目录eovl/ 公用系统操作器主目录oilpump/ 燃油系统流程画面及操作器画面主目录opovl/ 燃油泵房操作器主目录dlz/ 等离子点火系统流程画面及操作器画面主目录back/unit5 5#机组备用操作流程画面及操作器画面主目录back/unit6 6#机组备用操作流程花蜜拉及操作器画面主目录9./opt/dcs/BAK 应用文件备份主目录(此目录下的文件不要修改)10./opt/dcs/PREBAK 应用文件上一次备份主目录(此目录下的文件不要修改)11./opt/dcs/tools 系统工具目录(包括自动备份、自动恢复、CP检查、系统自动维护等文件、以及系统关键信息如:C语言许可证等的备份记录)12./opt/dcs/meh/ MEH系统流程画面及操作器画面主目录13./opt/dcs/deh/ DEH系统流程画面及操作器画面主目录14.环境文件/opt/fox/env 环境文件主目录/opt/fox/env/.pulldown 环境保护级别定义文件/opt/fox/env/*.env 环境文件(包括初始环境Initial、锅炉环境Boiler_Opr、汽机环境Jurbine_Opr、工程师环境Process_Eng、电气操作环境Elec_Opr等)/opt/fox/env/*.dbr 相应环境的快捷按钮定义文件/opt/fox/env/*.mbr 相应环境的顶部菜单定义文件/opt/fox/env/*.mnu 下拉菜单定义文件15./usr/fox/wp/data/wp51_glbls.all 系统宏参数定义文件16./usr/fox/wp/data/er 系统宏定义参数定义文件17./usr/fox/wp/data/dmpasswd_cfg 环境密码文件18./usr/fox/customer/hi/dmcfg 系统定义的DM管理文件19./usr/fox/customer/alarms/cfg/*.cfg 系统定义的AM管理文件,*代表工作站的LETTERBUG。

20./opt/customer/displib/Markers/*.m1 汉字MARKER文件21./opt/customer/displib/Palettes/*.m1 汉字PALETTES文件22./opt/customer/displib/Faceplate/*.m1 用户自定义的面板文件23./opt/customer/data/usr_conventions.dat 画面使用的bitmap文件24./usr/fox/alarms/*AAtab 系统定义的报警键盘组态文件,包括/usr/fox/alarms/*AApan 报警面板、报警表格、报警喇叭组态/usr/fox/alarms/*.acr文件/usr/fox/alarms/horn.cfg25./opt/foxind SOE顺序事件记录、Post Trip事故追忆文件目录(此目录仅AW5001、AW0001有)26./opt/sfcl/oaj/bin/ 操作员行为记录文件目录(此目录/opt/sfcl/oaj/result 仅AW5001、AW0001有)27./ etc/hosts 有关SIS通讯的文件(仅AW5001、AW0001有)/ etc/hostname.hme1第三章 基本操作1. 过程报警当发生过程报警时,顶部按钮“Process ” 将会有颜色的变化用于显示当前的过程报警状态;同时,报警键盘上与该报警有关的LED 灯颜色亦会发生变化;其颜色状态含义为:绿色 过程运行正常,无过程报警 闪烁绿色 当前过程运行正常,无报警,但有未确认的过程报警存在 红色 过程发生报警且已确认,但报警信号仍然存在 闪烁红色 过程发生报警且未经确认当过程发生报警后,可用球标单击Alarm 进入报警信息画面。

相关文档
最新文档